HVAC Excellence Gas Heat study materials
HVAC Excellence Gas Heat study resources

HVAC Excellence Gas Heat Certification cheat sheet

HVAC Excellence Gas Heat · Keep the key ideas within reach.

Quick reference

Gas Heating Fundamentals and Combustion

  • Complete combustion of methane: CH4 + 2O2 -> CO2 + 2H2O; each cubic foot of natural gas needs about 10 ft3 of air for stoichiometric (perfect) combustion, roughly 15 ft3 in practice with excess air.

  • Stoichiometric (theoretical) air for natural gas is about 10 ft3 air per ft3 gas; typical furnaces run 25-50% excess air (about 12.5-15 ft3 air per ft3 gas), verified by an O2 reading of roughly 4-9% in the flue.

  • Heating (gross) value of natural gas is about 1,000-1,050 Btu/ft3; LP gas about 2,500 Btu/ft3. Input = gas rate (ft3/hr) x heating value (Btu/ft3).

  • Flame color signals: steady blue flame = proper primary air and combustion; yellow, lazy, or floating flame = insufficient primary air, dirty burners, or misaligned orifice; lifting flame = too much primary air or excess draft.

  • Carbon monoxide (CO) is produced by incomplete combustion: insufficient oxygen, dirty or blocked burners, overfiring, or a cracked heat exchanger quenching the flame; CO is colorless and odorless, so it must be measured with an instrument.

  • Dew point of flue products: about 130°F for natural gas; a flue-gas temperature below roughly 140°F risks condensation and corrosion in a Category I (non-condensing) vent.

  • Limits of flammability of natural gas in air: about 4-5% lower to 15% upper; a gas concentration in this band can ignite. LP gas limits are roughly 2.2% to 9.6%.

  • Primary air is mixed with gas at the burner before ignition; secondary air is supplied around the flame from the combustion-air supply. Adjust primary air shutters for a stable blue flame with slight yellow tips.

Quick reference

Gas Furnace Components and Sequence of Operation

  • Standard induced-draft sequence: thermostat calls for heat -> inducer motor energizes -> pressure switch proves draft -> igniter energizes (hot surface) or pilot proves -> gas valve opens -> flame sensor proves flame -> blower starts after heat-on delay -> thermostat satisfied -> gas valve closes -> inducer runs post-purge -> blower runs off-delay -> cycle ends.

  • Standing-pilot (millivolt) sequence: thermostat closes -> gas valve main operator opens -> main burner lights from pilot -> fan/limit switch closes on temperature rise to start blower.

  • Pressure switch proves inducer airflow; it is normally open and closes on negative pressure. A blocked flue, blocked intake, water in the tubing, or a weak inducer prevents it from closing, and the gas valve will not open.

  • Hot-surface ignition (HSI) igniters draw roughly 2-4 amps at 120 V and glow orange; a cracked or open igniter reads infinite resistance and prevents ignition.

  • Flame sensor (flame rectification) proves flame: the control applies a small AC voltage to the sensor; the flame conducts current in one direction, producing a microamp DC signal (typically 1-6 microamps). A dirty sensor lowers the reading and causes short cycling.

  • Limit switch is a normally closed, temperature-actuated safety in the heat exchanger/supply air path; it opens on overheat and interrupts the gas valve. The blower/fan switch (normally open) starts the blower on temperature rise in standing-pilot designs.

  • Gas valve has a redundant and a main operator; the redundant operator opens only after the main operator and safety circuit are proven. Manifold (outlet) pressure for natural gas is typically 3.5 in. w.c.; LP about 10-11 in. w.c.

  • In-shot or inshot burners and the heat exchanger: burners deliver flame into the heat exchanger cells; a cracked heat exchanger can allow flue gases into supply air and is a CO hazard requiring shutdown and replacement.

Quick reference

Venting, Combustion Air, and Gas Piping

  • Category I appliances are non-condensing, negative-pressure vented, and use a vertical vent or chimney; Category IV appliances are condensing, positive-pressure vented, and use PVC/CPVC or other listed plastic vent.

  • Natural-draft (Category I) vent sizing depends on appliance input, vent height, and connector rise; follow the appliance's venting tables. A single appliance may use a Type B vent; a common vent requires careful sizing and a properly sized manifold.

  • Combustion air: the standard rule is 50 ft3 of space per 1,000 Btu/hr of input for an unconfined space. A confined space needs two permanent openings (high and low) or a listed combustion-air duct sized to the appliance input.

  • Two-permanent-opening rule (confined space, indoor air): each opening free area = 1 in2 per 1,000 Btu/hr of total input, with a minimum 100 in2 per opening; openings must be within 12 in. of the top and bottom of the enclosure.

  • Direct-vent (two-pipe) appliances take combustion air from outdoors and vent outdoors; keep intake and exhaust terminations separated per the manufacturer, typically at least 12 in. above grade and clear of snow and recirculation zones.

  • Gas piping: use black steel pipe, corrugated stainless steel tubing (CSST), or listed copper; never use galvanized pipe for gas. Use approved pipe dope on male threads only, leaving the first two threads bare.

  • Gas pressure: supply (line) pressure for natural gas is typically 7 in. w.c. (range about 5-10.5 in. w.c.); manifold pressure typically 3.5 in. w.c. natural gas, 10-11 in. w.c. LP. Test with a manometer, not a gauge.

  • Leak test: pressurize the piping and check joints with a non-corrosive leak-detection solution or electronic detector; never use an open flame. A drip leg (sediment trap) must be installed at the appliance connection.

Quick reference

Electrical Controls, Ignition Systems, and Safeties

  • 24 V control circuit: transformer steps 120 V down to 24 V; the thermostat, gas valve, pressure switch, limit, and flame sensor all operate on the 24 V circuit. A blown low-voltage fuse (typically 3-5 A) kills the whole control circuit.

  • Flame rectification: the control board supplies AC to the flame sensor; the flame acts as a rectifier and returns a DC microamp signal (typically 1-6 microamps). Below the board's threshold (often about 0.5-1 microamp) the board locks out.

  • Hot-surface ignition boards include an ignition trial period (often 15-30 seconds) followed by a flame-proving period; failure to prove flame causes lockout or retry, depending on the control.

  • Direct-spark ignition (DSI) uses a spark electrode to light the burner; the spark gap is typically about 1/8 in. (3 mm). A cracked ceramic insulator or a grounded electrode prevents spark.

  • Safety devices that interrupt the gas valve: limit switch (high temperature), rollout switch (flame rollout from the burner compartment, manual reset), pressure switch (draft), and flame sensor (flame proving).

  • Rollout switches are manual-reset, normally closed, and located at the burner opening; they trip if flame rolls out due to a blocked heat exchanger, sooted burners, or a bad inducer.

  • Inducer motor proving: the pressure switch must close before the gas valve is energized; the control board often checks the switch is open before starting the inducer to detect a stuck-closed switch.

  • Thermostat and control wiring: R (24 V hot), W (heat call), C (common), G (fan), Y (cooling). A heat call is R to W; the control board sequences the inducer, igniter, gas valve, and blower.

Quick reference

Installation, Startup, and Combustion Analysis

  • Combustion analysis instruments measure O2, CO, CO2, flue temperature, and draft; calculate excess air from O2 and check CO (air-free) against the appliance limit (commonly under 100 ppm air-free for clean combustion).

  • Set manifold pressure with a manometer at the gas valve outlet tap: natural gas typically 3.5 in. w.c., LP about 10-11 in. w.c. Adjust only to the manufacturer's rating plate value, then recheck gas input by clocking the meter.

  • Clock the gas meter to verify input: input (Btu/hr) = (3600 / seconds per revolution) x dial size (ft3) x heating value (Btu/ft3). Compare to the rating plate within about 5%.

  • Temperature rise = supply air temperature minus return air temperature; it must fall within the rating plate range (commonly 35-65°F). A low rise indicates excess airflow; a high rise indicates low airflow or overfiring.

  • Static pressure: measure supply and return static with a manometer; total external static pressure should be within the blower table for the required airflow. High static pressure reduces airflow and raises temperature rise.

  • Draft check: verify negative draft in the vent connector (about -0.02 to -0.04 in. w.c. for natural draft) and confirm no spillage at the draft hood with a smoke or flame test.

  • Startup steps: verify gas supply pressure and piping, check vent and combustion air, set manifold pressure, confirm ignition and flame proving, measure temperature rise and static pressure, then run a combustion analysis and record results.

  • A CO reading that rises when the blower starts suggests a cracked heat exchanger or a flue leak drawing into the supply air; shut down and inspect before returning the appliance to service.

Quick reference

Troubleshooting, Service, and Safety

  • No heat call, inducer runs but gas valve never opens: check pressure switch (blocked flue, water in tubing, weak inducer), then flame sensor and igniter, then gas valve and 24 V at the valve.

  • Igniter glows but no flame: verify gas supply and manifold pressure, check the gas valve operator (24 V at valve terminals), and confirm the igniter is positioned in the burner gas stream.

  • Burner lights then shuts off after a few seconds: dirty or misaligned flame sensor (low microamps), poor flame grounding, or a flame that lifts off the sensor. Clean the sensor with steel wool and recheck microamps.

  • Repeated lockout with a good flame: check the control board's flame-proving circuit, the sensor wire, and the burner ground. Many boards lock out after a set number of retries and require a power reset.

  • Short cycling on limit: restricted airflow (dirty filter, blocked coil, undersized duct), overfiring (high manifold pressure), or a failing blower. Verify temperature rise and static pressure before replacing the limit.

  • CO safety: if CO is detected or suspected, shut off the appliance, ventilate, and evacuate as needed; never return a unit with a cracked heat exchanger or a blocked vent to service. Use a CO detector and combustion analyzer.

  • Gas leak response: shut off the gas at the meter or appliance valve, ventilate, do not operate electrical switches, and call the gas utility. Use leak-detection solution or an electronic detector to locate the leak.

  • Service checks: verify supply pressure, manifold pressure, temperature rise, static pressure, draft, flame signal, and combustion readings; record all values and compare to the rating plate before signing off.