HVAC Air Distribution study materials
HVAC Air Distribution study resources

HVAC Air Distribution cheat sheet

HVAC Air Distribution · Keep the key ideas within reach.

Quick reference

HVAC Air Distribution

  • Total pressure equals static pressure plus velocity pressure: TP = SP + VP; velocity pressure VP = (V/4005)^2 when V is in fpm and VP in in. w.c. (standard air, 0.075 lb/ft^3).

  • Duct friction loss is commonly estimated with the Darcy-Weisbach form or the equal-friction chart: friction rate depends on velocity, duct roughness, and hydraulic diameter; doubling velocity roughly quadruples friction loss per unit length.

  • Equivalent length converts fittings to straight duct: total pressure drop = (straight length + sum of fitting equivalent lengths) x friction rate per 100 ft / 100.

  • Velocity pressure recovery at a transition is limited by the pressure recovery coefficient; a gradual expansion recovers more static pressure than an abrupt one, which dissipates energy in turbulence.

  • Airflow continuity: Q = V x A. For a rectangular duct A = W x H; for round duct A = pi x D^2 / 4; keep units consistent (cfm, fpm, ft^2).

  • Hydraulic diameter for a rectangular duct: D_h = 1.30 x (W x H)^0.625 / (W + H)^0.25; used to read round-duct friction charts for rectangular ducts.

  • Aspect ratio W/H above about 4:1 raises friction, increases surface area and insulation cost, and worsens fitting performance; design targets are usually 2:1 or lower.

  • Fan total pressure must equal the sum of supply and return/relief path total pressure losses plus any system effect; system effect arises from poor connections at the fan inlet and outlet.

Quick reference

HVAC Air Distribution

  • Face velocity at a return or exhaust grille is limited by noise and entrainment: typical design face velocities are about 300-500 fpm for occupied spaces and higher for non-critical areas.

  • Throw, drop, and spread characterize supply diffuser performance; a jet with higher initial velocity and smaller effective area produces greater throw but also higher noise (NC level).

  • Occupancy comfort criteria commonly cited: occupied-zone air speed below about 50 fpm in heating and 40-50 fpm in cooling, with neck-level velocity targets around 25-35 fpm.

  • The Air Diffusion Performance Index (ADPI) relates effective draft temperature to local velocity; ADPI of 80% or higher is a common design target for cooling operation.

  • Effective draft temperature combines local air temperature and velocity: EDT = (T_local - T_room) - 0.07 x (V - 30), with V in fpm; EDT between about -3 and +2 F indicates acceptable comfort.

  • Air change rate: ACH = Q x 60 / room volume; used for ventilation, dilution, and contaminant control rather than for thermal load alone.

  • Mixing ventilation relies on high induction and entrainment; displacement ventilation supplies low-velocity air near the floor and relies on buoyant stratification, requiring careful supply temperature control.

  • Duct leakage classes (e.g., per SMACNA) specify allowable leakage as a percentage of design flow at a test pressure; seal class A covers all transverse joints and seams.

Quick reference

HVAC Air Distribution

  • Duct static pressure reset: reduce fan speed (and thus power, approximately with the cube of speed) when the critical-zone damper is nearly open; a VAV box damper below about 90% open indicates excess static pressure.

  • Fan laws: flow varies with speed (Q ~ N), pressure with the square of speed (P ~ N^2), and power with the cube of speed (kW ~ N^3); use them for balancing and commissioning estimates.

  • VAV box minimum and maximum airflow settings must satisfy ventilation requirements at minimum flow; ASHRAE 62.1 ventilation rate procedure sets the outdoor air intake based on zone ventilation efficiency.

  • Duct static pressure sensor placement should be about two-thirds of the way along the longest supply run, not at the fan discharge, to reflect the critical zone's needs.

  • Balancing dampers should be placed so they do not create excessive noise; a damper at part-closed position generates self-noise and should be avoided as a permanent flow-control device.

  • Return air path design must provide a relief path; a tightly sealed building with inadequate relief pressurizes spaces, causing door-opening problems and reduced outdoor air intake.

  • Fire and smoke dampers are required where ducts penetrate rated assemblies; access doors are required for inspection and testing of dampers and smoke detectors.

Quick reference

HVAC Air Distribution

  • Duct insulation thickness depends on temperature difference, conductivity, and surface condensation control; vapor retarders must be on the warm side in cooling applications.

  • Flexible duct pressure drop per foot is much higher than rigid duct and increases sharply when compressed; keep bends gentle and avoid sharp radius bends and sagging.

  • Duct sizing methods: equal friction (constant pressure loss per length), static regain (sizing for pressure recovery at each branch), and velocity reduction (progressively lower velocities).

  • Static regain method sizes each downstream section so the regained static pressure equals the loss of the preceding section, aiming for uniform static pressure along the run.

  • Noise control: duct velocity limits are commonly about 1,000-1,200 fpm in main supply ducts near occupied spaces to keep regenerated noise low; branch velocities are lower.

  • Return air plenum design must limit plenum velocity and pressure drop across the ceiling; a plenum with high velocity causes ceiling tile lift and dirt staining.

  • Air terminal unit selection: a VAV box's minimum and maximum flows, pressure drop at design flow, and sound power level at the design static pressure determine its suitability for a zone.

  • Commissioning airflow measurement: use a calibrated flow hood at diffusers; pitot-tube traverse in ducts requires adequate straight duct length (often 7.5 diameters upstream, 2.5 downstream) for accuracy.