Total pressure
The sum of static pressure and velocity pressure at a point in an air system; it represents the energy available to overcome downstream resistance.
Velocity pressure formula
VP = (V/4005)^2 for standard air at 0.075 lb/ft^3, where V is velocity in fpm and VP is in inches of water column.
Continuity equation
Q = V x A relates volumetric airflow to velocity and cross-sectional area; use consistent units such as cfm, fpm, and square feet.
Hydraulic diameter
For a rectangular duct, D_h = 1.30 x (W x H)^0.625 / (W + H)^0.25, allowing round-duct friction charts to be used for rectangular ducts.
Aspect ratio
The width-to-height ratio of a rectangular duct; ratios above about 4:1 increase friction, surface area, and installation cost.
Equal friction method
A duct sizing approach that selects sizes so pressure loss per unit length is constant throughout the system, simplifying design but not optimizing fan energy.
Static regain method
A sizing method where each downstream section is sized so the static pressure regained from velocity reduction equals the friction loss of the preceding section.
Equivalent length
A method of expressing fitting pressure loss as the length of straight duct that would produce the same pressure drop at the same velocity.
System effect
Additional pressure loss caused by non-ideal fan inlet or outlet connections, such as elbows close to the fan, that is not captured by fan curve ratings.
Fan laws
For a given fan, flow varies with speed, pressure with the square of speed, and power with the cube of speed; used to predict performance at other speeds.
Duct leakage class
A classification specifying allowable duct leakage as a percentage of design airflow at a specified test pressure, with seal classes defining which joints must be sealed.
Fire damper
A device installed where a duct penetrates a fire-rated assembly that closes on heat to prevent fire spread through the duct; requires an access door.
Smoke damper
A damper that closes on a smoke detector signal to limit smoke migration through ducts; it is often combined with a fire damper in rated assemblies.
Flexible duct compression
Compressing flexible duct increases its pressure loss sharply; even moderate sag or compression can multiply friction compared with the fully extended rating.
Vapor retarder placement
In cooling applications, the vapor retarder must be on the warm side of duct insulation to prevent condensation within the insulation.
Diffuser throw
The horizontal distance from the diffuser to the point where jet velocity falls to a specified terminal value, typically 50 or 100 fpm.
Diffuser drop
The vertical distance a supply jet travels from the diffuser before reaching a specified terminal velocity, important for heating operation and ceiling effects.
Coanda effect
The tendency of a supply jet to attach to and follow an adjacent surface such as a ceiling, extending throw and improving mixing in the occupied zone.
ADPI
Air Diffusion Performance Index: the percentage of occupied-zone measurement points meeting acceptable effective draft temperature and velocity criteria; 80% or higher is a common target.
Effective draft temperature
EDT = (T_local - T_room) - 0.07 x (V - 30), with V in fpm; values between about -3 and +2 F are considered comfortable.
Air change rate
ACH = Q x 60 / room volume, expressing how many times the room air volume is replaced per hour; used for ventilation and dilution design.
Mixing ventilation
A strategy that supplies high-velocity air to induce room air entrainment and create uniform temperature and contaminant concentration throughout the occupied space.
Displacement ventilation
A strategy that supplies low-velocity, slightly cool air near the floor and relies on buoyant plumes to carry contaminants upward to a high return.
Face velocity
The average air speed through the free area of a grille or diffuser; it influences noise generation, pressure drop, and entrainment of room air.
Noise criteria
NC or RC curves rate the sound level of air distribution devices; diffusers and grilles are selected to meet a space's NC limit at design airflow.
Static pressure reset
Reducing duct static pressure setpoint when the critical VAV damper is mostly open; fan power drops approximately with the cube of speed.
Critical zone
The VAV zone requiring the highest duct static pressure to deliver its design airflow; its damper position drives the supply fan static pressure setpoint.
Relief air path
A designed route for excess return air to exit the building, preventing overpressurization and ensuring outdoor air intake is maintained.
Return air plenum
A ceiling cavity used as a return air path; plenum velocity and pressure drop must be limited to avoid ceiling tile lift and dirt staining.
Pitot tube traverse
A method of measuring duct airflow using velocity pressure readings at multiple points across the duct; accuracy requires adequate straight duct upstream and downstream.
Flow hood
A calibrated instrument placed over a diffuser or grille to measure airflow directly; commonly used for balancing and commissioning air systems.
Balancing damper
A damper used to adjust airflow among branches during commissioning; it should be set once and not used as a routine flow-control device because of noise.