HVAC Excellence Gas Heat Certification Exam key terms
HVAC Excellence Gas Heat · Get comfortable with the vocabulary.
- Stoichiometric (theoretical) air
- Related: Excess air, Air-fuel ratio, Incomplete combustion
The exact volume of air needed to burn a given amount of gas completely, with no oxygen left over and no unburned fuel. Real appliances supply more than this to ensure clean combustion.
- Excess air
- Related: Stoichiometric (theoretical) air, Air-fuel ratio, Carbon monoxide (CO)
Air supplied beyond the theoretical requirement, usually expressed as a percentage. Enough excess air ensures complete burning, but too much cools the flame and lowers efficiency and heat transfer.
- Air-fuel ratio
- Related: Excess air, Primary air, Secondary air
The proportion of combustion air to fuel gas entering the burner. It determines flame shape, temperature, and completeness of burning, and is adjusted by gas manifold pressure and burner air shutters.
- Primary air
- Related: Secondary air, Air shutter, Air-fuel ratio
Air mixed with gas before ignition, drawn in at the burner orifice or by a blower. It sets the basic flame character and, in atmospheric burners, is controlled by the air shutter opening.
- Secondary air
- Related: Primary air, Carbon monoxide (CO), Lifting flame
Air that reaches the flame from around the burner after ignition, completing combustion of the remaining gas. Inadequate secondary air causes yellow tips, sooting, and carbon monoxide production.
- Limits of flammability
- Related: Air-fuel ratio, Flashback, Lifting flame
The upper and lower gas concentrations in air that will support ignition and sustained burning. Natural gas burns roughly between 4 and 15 percent in air; outside that band it is too lean or too rich to ignite.
- Flashback
- Related: Lifting flame, Limits of flammability, Burner port
A condition where flame travels back through the burner ports or air mixture tube instead of staying at the ports. It usually results from too little gas velocity, a clogged orifice, or a hot burner.
- Lifting flame
- Related: Flashback, Burner port, Primary air
A flame that pulls away from the burner ports and may blow out, caused by excessive gas pressure, too much primary air, or a damaged port. It risks delayed ignition and unburned gas release.
- Incomplete combustion
- Related: Carbon monoxide (CO), Excess air, Flue gas analysis
Burning that leaves unburned fuel or partially oxidized products such as carbon monoxide and soot. Causes include insufficient air, dirty burners, misalignment, and blocked flues.
- Carbon monoxide (CO)
- Related: Incomplete combustion, Flue gas analysis, Draft
A colorless, odorless, poisonous gas produced by incomplete combustion. In flue gas it signals a combustion or venting problem and is measured in parts per million during analysis.
- Heating value (BTU per cubic foot)
- Related: Orifice, Gas manifold pressure, Clock the meter
The heat released by burning a unit volume of gas. Natural gas is typically about 1,000 BTU per cubic foot and propane about 2,500 BTU per cubic foot, which drives orifice sizing.
- Specific gravity of gas
- Related: Gas leak detection, Orifice, Gas manifold pressure
The density of a gas compared with air, where air equals 1.0. Natural gas is lighter than air (about 0.6) and rises; propane is heavier (about 1.5) and settles in low areas.
- Gas piping sediment trap (drip leg)
- Related: Gas valve, Orifice, Gas manifold pressure
A capped vertical drop installed ahead of the appliance gas valve so dirt, scale, and pipe dope fall out of the gas stream. It protects the valve and orifice from debris and must be installed per code.
- Pipe sizing by length and load
- Related: Gas manifold pressure, Gas pressure regulator, Manifold
Selecting gas pipe diameter from the total connected BTU load, the allowable pressure drop, and the longest run length. Longer runs and larger loads require larger pipe to keep pressure at the appliance.
- Gas pressure regulator
- Related: Gas manifold pressure, Gas valve, Manifold
A device that reduces higher supply pressure to a steady lower pressure for the appliance or manifold. It responds to a diaphragm sensing downstream pressure and opens or closes a seat accordingly.
- Gas manifold pressure
- Related: Manometer, Gas pressure regulator, Orifice
The pressure measured at the burner manifold, set by the appliance regulator. It is checked with a manometer and adjusted to the nameplate value to control firing rate and flame quality.
- Manometer
- Related: Gas manifold pressure, Draft, Gas pressure regulator
An instrument that measures low gas pressures, commonly in inches of water column. Technicians use it to verify supply pressure, manifold pressure, and draft without disturbing gas flow.
- Gas leak detection
- Related: Specific gravity of gas, Gas piping sediment trap (drip leg), Gas valve
Finding escaping fuel using a combustible gas detector, soap bubbles, or pressure testing. Because natural gas rises and propane settles, checks cover high and low points of the piping.
- Category I venting
- Related: Draft, Flue gas analysis, Spillage
A vent system for appliances that operate with negative vent pressure and low flue gas temperature, usually a vertical metal or listed plastic vent. It depends on draft and proper vent height.
- Draft
- Related: Spillage, Category I venting, Manometer
The slight negative pressure in a vent or flue that carries combustion products outdoors. It is created by hot gas rising and by vent height, and is measured in inches of water column.
- Spillage
- Related: Draft, Carbon monoxide (CO), Combustion air
Flue gases escaping from the draft hood or vent connector into the room instead of going up the flue. It indicates a blocked flue, poor draft, or a backdraft from competing exhaust fans.
- Combustion air
- Related: Spillage, Primary air, Incomplete combustion
Air supplied to the appliance for burning fuel, distinct from dilution or ventilation air. Insufficient combustion air causes incomplete burning, carbon monoxide, and spillage.
- Flue gas analysis
- Related: Carbon monoxide (CO), Incomplete combustion, Draft
Measuring oxygen, carbon monoxide, carbon dioxide, and temperature in the exhaust to judge combustion quality and efficiency. Results guide air adjustment and reveal heat exchanger or venting faults.
- Gas valve
- Related: Gas pressure regulator, Redundant valve, Manifold
The electrically operated valve that opens and closes fuel flow to the burners. It contains an operator, a pressure regulator, and safety shutoff features, and is controlled by the furnace circuit board.
- Redundant valve
- Related: Gas valve, Gas manifold pressure, Flame sensor
A second safety shutoff inside a gas valve that closes independently if the main operator fails to seat. It prevents gas from passing to the burners when the valve is de-energized.
- Manifold
- Related: Orifice, Gas manifold pressure, Burner port
The pipe assembly that distributes gas from the valve to the individual burner orifices. It is where manifold pressure is measured and where burners are mounted and aligned.
- Orifice
- Related: Heating value (BTU per cubic foot), Specific gravity of gas, Manifold
A precisely sized hole that meters gas into a burner at the rated input. Its size depends on gas heating value, specific gravity, and manifold pressure, and must match the fuel being used.
- Burner port
- Related: Flashback, Lifting flame, Primary air
An opening in the burner head where the air-fuel mixture exits and burns. Ports must stay clean and evenly sized; clogging or damage causes flame distortion, flashback, or lifting.
- Standing pilot
- Related: Thermocouple, Intermittent pilot ignition, Flame sensor
A small continuously burning flame that lights the main burner when the gas valve opens. It is simple but wastes gas and can be extinguished by drafts or dirt, requiring a thermocouple safety.
- Thermocouple
- Related: Standing pilot, Flame sensor, Gas valve
A two-metal junction that generates a small voltage when heated by the pilot flame. That voltage holds the gas valve open, and loss of flame drops the valve closed for safety.
- Intermittent pilot ignition
- Related: Standing pilot, Direct spark ignition, Flame sensor
An ignition system that lights a pilot only when there is a call for heat, then proves flame before opening the main valve. It saves fuel compared with a standing pilot and uses a spark igniter.
- Hot surface ignition
- Related: Direct spark ignition, Flame sensor, Igniter resistance
A system that heats a silicon carbide or nitride igniter to glowing temperature to light the burners. The igniter also often serves as the flame-proving element, so its resistance matters.
- Direct spark ignition
- Related: Hot surface ignition, Intermittent pilot ignition, Flame sensor
A system that uses a high-voltage spark at the burner to light gas without a pilot flame. Flame must be proven by a separate sensor, or the valve closes on a lockout.
- Flame sensor
- Related: Thermocouple, Igniter resistance, Gas valve
A probe that detects flame by sensing current through the ionized gas flame. A dirty or poorly positioned sensor produces weak current, causing short cycling or ignition lockout.
- Igniter resistance
- Related: Hot surface ignition, Flame sensor, Sequence of operation
The electrical resistance of a hot surface igniter, checked with an ohmmeter to judge condition. Resistance rises with temperature and an open or cracked element reads infinite, requiring replacement.
- Sequence of operation
- Related: Pressure switch, Flame sensor, Limit switch
The ordered steps a furnace follows on a call for heat: thermostat demand, inducer start, pressure switch proof, ignition, valve opening, flame proving, blower start, and shutdown. Technicians compare observed behavior to it.
- Limit switch
- Related: Temperature rise, Sequence of operation, Rollout switch
A temperature-sensitive safety that opens the control circuit if the furnace overheats, shutting off the gas valve. It may be automatic-reset or manual-reset and often indicates an airflow problem.
- Rollout switch
- Related: Limit switch, Flame rollout, Spillage
A one-time or manual-reset safety mounted near the burners that opens if flame rolls out of the combustion chamber. It signals blocked flue, bad draft, or a cracked heat exchanger.
- Pressure switch
- Related: Sequence of operation, Draft, Inducer motor
A safety that proves the inducer is moving combustion air before ignition is allowed. It senses negative pressure through a hose and blocks the sequence if the vent or inducer fails.
- Inducer motor
- Related: Pressure switch, Draft, Sequence of operation
A blower that pulls flue gases through the heat exchanger and pushes them into the vent. It creates the draft that the pressure switch proves and must run before the gas valve opens.
- Temperature rise
- Related: Limit switch, Heat exchanger integrity, Static pressure
The difference between return air and supply air temperatures across the furnace. It must fall within the nameplate range; too high a rise signals low airflow and risks overheating the heat exchanger.
- Static pressure
- Related: Temperature rise, Limit switch, Heat exchanger integrity
The resistance to airflow in a duct system, measured in inches of water column. High static pressure reduces airflow, raises temperature rise, and can trip the limit switch.
- Heat exchanger integrity
- Related: Carbon monoxide (CO), Flame rollout, Flue gas analysis
The condition of the metal passages separating flue gases from supply air. Cracks or holes allow carbon monoxide into the home and are checked visually, by flame observation, and by combustion analysis.
- Flame rollout
- Related: Rollout switch, Spillage, Heat exchanger integrity
Flame burning outside the combustion chamber instead of inside it, often from a blocked flue or failed draft. It can trip a rollout switch and indicates a serious venting or heat exchanger fault.
- Clock the meter
- Related: Heating value (BTU per cubic foot), Gas manifold pressure, Orifice
Timing gas meter movement to calculate actual appliance input in BTU per hour. Comparing measured input with the nameplate rating confirms correct orifice sizing and manifold pressure.
- Lockout
- Related: Flame sensor, Sequence of operation, Gas valve
A control state that stops ignition attempts after a failed trial for ignition and requires a reset or delay. It protects against unburned gas release and points to flame proving or gas supply faults.
- Trial for ignition
- Related: Lockout, Flame sensor, Sequence of operation
The timed period during which the control energizes the igniter and opens the gas valve hoping to establish flame. If proof is not received within that window, the valve closes and lockout follows.