Heat content of No. 2 oil
No. 2 heating oil releases roughly 138,000 to 140,000 Btu per gallon when burned, the figure used to compute input rate from nozzle size and pump pressure.
Nozzle flow vs pressure
Flow changes with the square root of pressure: new gph equals rated gph times the square root of new psi divided by rated psi. Doubling pressure raises flow about 41 percent.
Hollow-cone nozzle use
Hollow-cone nozzles produce a ring-shaped pattern used in most residential retention-head burners; they atomize well at 100 psi and match the burner's air pattern.
Solid-cone nozzle use
Solid-cone nozzles deliver a filled spray pattern, often used in low-input or certain commercial burners where a fuller pattern improves mixing with combustion air.
Electrode tip gap
Electrode tips are typically set 1/8 to 5/32 inch apart; too wide a gap weakens the spark, too narrow promotes carbon bridging and hard starts.
Electrode position above nozzle
On retention-head burners the electrodes usually sit about 1/8 to 5/32 inch above the nozzle centerline and 5/32 to 3/16 inch ahead of the nozzle face.
Cad cell dark resistance
A clean cad cell in darkness reads well above 20,000 ohms, often 50,000 or more; low dark resistance suggests a shorted or contaminated cell.
Cad cell flame resistance
When viewing flame, cad cell resistance drops below about 1,600 ohms; the primary control uses this threshold to prove flame and prevent lockout.
Trial for ignition
The timed period after the burner starts when the primary control looks for flame proof; if the cad cell stays dark beyond this period, the control locks out.
Primary control lockout
On flame failure the primary control shuts off the burner and locks out, requiring manual reset; repeated lockouts indicate nozzle, electrode, or cad cell problems.
Overfire draft target
Most oil-fired appliances are set to about minus 0.02 to minus 0.04 inches water column overfire draft, measured through the inspection port at steady state.
Breech draft target
Breech draft is typically minus 0.02 to minus 0.06 inches water column; the barometric damper is adjusted to hold this range as the burner cycles.
Barometric damper function
A barometric damper opens to admit room air into the flue, stabilizing draft so changing chimney conditions do not alter combustion air or efficiency.
Smoke test meaning
A smoke test measures unburned carbon in flue gas on a 0 to 9 scale; a trace (No. 1) or zero indicates clean combustion, while higher numbers mean soot and wasted fuel.
Target CO2 range
A well-tuned oil burner typically produces about 11.5 to 12.5 percent CO2 in the flue gas, corresponding to moderate excess air and good efficiency.
Excess air effect
Excess air above roughly 50 percent lowers flue-gas temperature but raises stack loss, reducing steady-state efficiency; air is set by the burner's air shutter or band.
Steady-state efficiency
Calculated from flue temperature, room temperature, and CO2 or O2, a clean residential oil burner usually reaches about 85 to 87 percent steady-state efficiency.
Stoichiometric air for oil
Complete combustion of No. 2 oil needs about 14.4 pounds of air per pound of fuel, roughly 1,920 cubic feet of air per gallon of oil.
Two-line fuel system
A two-pipe system returns unused oil to the tank, allowing lifts beyond about 8 feet and preventing air lock; the bypass plug must be removed from the pump.
Single-line fuel system
Used when the tank is above or near the burner with limited lift; oil is drawn from the tank and any excess returns through the pump's internal relief.
Oil filter placement
A listed filter is installed in the suction line between tank and pump, protecting the nozzle and pump from grit; clogged filters cause delayed ignition and lockout.
Fusible oil valve
A heat-actuated valve on the tank outlet closes when exposed to fire, stopping gravity flow of oil to the burner area during a fire.
Tank gauge purpose
A gauge or sight device indicates oil level so the tank can be filled safely and the burner not run dry; running dry introduces air and causes lockout.
Nozzle sizing basis
Nozzle gph is chosen from the appliance input rate divided by oil Btu content, then adjusted for actual pump pressure using the square-root flow rule.
Delayed ignition causes
Delayed ignition, a puff or rumble at startup, usually comes from worn electrodes, wrong gaps, a dirty nozzle, low pump pressure, or insufficient draft.
Puffback definition
A puffback is a small explosion of unburned oil vapor in the combustion chamber, often from delayed ignition or a flooded chamber; it coats surfaces with soot.
Combustion air requirements
Oil burners need adequate combustion air from outdoors or a large indoor volume; a confined boiler room requires dedicated openings sized to the appliance input.
Flue gas temperature
Stack temperature on a clean residential oil appliance is typically 350 to 500 degrees Fahrenheit; rising stack temperature signals soot or heat exchanger fouling.
CO in flue gas
Carbon monoxide above about 100 ppm in the flue gas of an oil burner suggests incomplete combustion from poor air adjustment, soot, or a blocked flue.
Heat exchanger cleaning
Soot on heat exchanger surfaces insulates them, raising stack temperature and lowering efficiency; brushing and vacuuming restore heat transfer.
Chimney vs power venting
Natural-draft oil appliances vent into a lined chimney; side-wall power venters are used where a chimney is unavailable and must be interlocked with the burner.
Fuel unit bypass plug
The bypass plug in a two-pipe oil pump directs return oil to the tank; leaving it in on a single-pipe system overpressures the pump and can damage the seal.