HVAC Excellence Refrigeration study materials
HVAC Excellence Refrigeration study resources

HVAC Excellence Refrigeration cheat sheet

HVAC Excellence Refrigeration · Keep the key ideas within reach.

Quick reference

Refrigeration Fundamentals

  • Sensible heat changes temperature without a phase change: Q = 1.08 × CFM × ΔT for air (Btu/h), or Q = 500 × GPM × ΔT for water.

  • Latent heat changes state at constant temperature; for water, latent heat of vaporization is about 970 Btu/lb at 212°F and rises as pressure falls.

  • Total heat (enthalpy) = sensible + latent; on a pressure-enthalpy diagram, the evaporator effect is the enthalpy difference between evaporator outlet and expansion-valve inlet.

  • The refrigeration cycle: compression, condensation (reject heat), expansion (drop pressure), evaporation (absorb heat); the compressor only moves heat, it does not create cold.

  • Superheat = actual suction temperature minus saturation temperature at suction pressure; subcooling = saturation temperature at liquid pressure minus actual liquid temperature.

  • One ton of refrigeration = 12,000 Btu/h = 200 Btu/min = 3.517 kW; it equals melting 1 ton (2,000 lb) of ice in 24 hours.

  • Carnot/thermodynamic limit: COP = evaporating absolute temperature ÷ (condensing absolute temperature − evaporating absolute temperature); real COP is always lower.

  • Pressure-temperature relationship is fixed for a pure refrigerant at saturation; a glide refrigerant (zeotrope) has a temperature range at one pressure.

  • Heat flows only from warmer to cooler; the evaporator must be colder than the load, and the condenser warmer than outdoor air, for heat transfer to occur.

Quick reference

Refrigerants and Lubricants

  • ASHRAE safety groups combine toxicity (A lower, B higher) and flammability (1 none, 2L low, 2 moderate, 3 high): R-410A is A1, R-32 is A2L, R-290 propane is A3.

  • R-22 is a HCFC (ozone-depleting, Montreal Protocol phase-out); R-410A and R-32 are HFCs with zero ODP but high GWP; R-744 (CO2) is A1 with GWP of 1.

  • R-410A is a near-azeotropic blend of R-32/R-125 (50/50); it must be charged as liquid to avoid fractionation, and operating pressures run roughly 50-70% higher than R-22.

  • R-134a is a single-component HFC used in medium-temperature and centrifugal chillers; it is not a drop-in for R-12 without an oil/retrofit review.

  • Mineral oil and alkylbenzene (AB) are used with CFC/HCFC refrigerants; POE (polyol ester) and PVE are required with HFCs because they are miscible with HFCs.

  • POE oil is hygroscopic: it absorbs moisture rapidly, so lines must be kept sealed and a liquid-line filter-drier is required; moisture forms acids that degrade the oil and windings.

  • A refrigerant blend with glide (e.g., R-407C) leaks fractionated; the correct repair is to recover, evacuate, and recharge with virgin refrigerant, not top off.

  • Never mix refrigerants or use a refrigerant with a different pressure-temperature curve; recovery cylinders are filled to 80% liquid by weight to allow thermal expansion.

Quick reference

System Components

  • The compressor raises refrigerant pressure and temperature; types include reciprocating, scroll, rotary, and centrifugal, and a scroll must not be run in reverse.

  • The condenser rejects heat; subcooling at the condenser outlet (typically 8-15°F) confirms adequate charge and heat rejection.

  • The metering device (TXV, fixed orifice, capillary, EEV) maintains the pressure difference; a TXV modulates on evaporator superheat, usually 8-12°F at the outlet.

  • The evaporator absorbs heat; a starved coil shows high superheat and low capacity, while a flooded coil risks liquid slugging the compressor.

  • A liquid-line filter-drier removes moisture and acid; a suction-line accumulator or filter protects the compressor from liquid return.

  • The liquid-line sight glass shows bubbles when the liquid line is starved (low charge, restriction, or flashing); moisture indicator color changes with water content.

  • An accumulator stores liquid on the suction side; a receiver stores liquid on the high side of systems with a receiver (e.g., some commercial and heat pump systems).

  • Defrost controls, crankcase heaters, and low-ambient fan cycling protect the compressor and maintain head pressure during cold weather.

Quick reference

Installation and Commissioning

  • Evacuation to 500 microns or below (and holding under 500 for 10 minutes with the pump isolated) confirms a dry, tight system; a rising micron gauge indicates moisture or a leak.

  • Nitrogen pressure test (typically 150-300 psig for R-410A systems) before evacuation; never pressure-test with refrigerant or oxygen.

  • Line sizing must follow manufacturer tables; undersized suction lines cause excessive pressure drop and reduced capacity, oversized lines reduce oil return.

  • Brazing requires flowing dry nitrogen to prevent internal oxidation (scale); use silver-phosphorus or silver brazing alloys and purge while hot.

  • Charge by weight for blends and critical systems; use superheat (fixed orifice/TXV) or subcooling (TXV) as the field verification method.

  • Electrical: match supply voltage and phase, verify compressor rotation on three-phase scrolls, and confirm correct breaker and disconnect sizing per nameplate MCA/MOP.

  • Airflow: 350-450 CFM per ton for comfort cooling; low airflow causes low suction pressure, high superheat, and coil icing.

  • Commissioning records should include static pressures, superheat/subcooling, amp draw, voltage, and refrigerant weight charged, compared to nameplate values.

Quick reference

Troubleshooting and Service

  • High suction and high head pressure with a cool compressor and normal-to-high superheat suggests an overcharge or a condenser airflow problem; high head with normal suction points to condenser restriction.

  • Low suction and high superheat with a normal head pressure suggests a starved evaporator (low charge, restriction, or TXV underfeeding).

  • Low suction and low head pressure with low superheat and a frosted suction line suggests an overfeeding TXV or a restriction at the evaporator inlet.

  • A compressor that trips on overload with high amp draw and hot windings: check supply voltage, start components, and mechanical binding before replacing.

  • A liquid-line restriction (e.g., clogged drier) shows a temperature drop across the drier; more than a few degrees ΔT indicates a restriction.

  • Superheat/subcooling diagnosis: high superheat + low subcooling = undercharge; low superheat + high subcooling = overcharge; high superheat + high subcooling = restriction or low airflow.

  • Recovery: recover refrigerant to the required vacuum level, never vent; use EPA Section 608 recovery equipment and record amounts on service records.

  • Leak detection: electronic leak detectors for HFCs, nitrogen pressure tests, and soap bubbles; dye is a last resort and may void warranties.

Quick reference

Refrigeration Fundamentals

  • Sensible heat formula for air: Btu/h = 1.08 × CFM × ΔT; for water: Btu/h = 500 × GPM × ΔT.

  • Latent heat of vaporization of water ≈ 970 Btu/lb at 212°F; it increases as saturation pressure decreases.

  • One ton = 12,000 Btu/h = 3.517 kW; superheat = suction temp − saturation temp; subcooling = saturation temp − liquid temp.

  • The compressor moves heat; it does not create cold. Heat always flows from warmer to cooler.

Quick reference

Refrigerants and Lubricants

  • ASHRAE safety groups: A1 (R-410A), A2L (R-32), A3 (R-290); R-22 is an HCFC with ODP; R-744 is CO2 with GWP 1.

  • R-410A is a 50/50 R-32/R-125 near-azeotrope; charge as liquid; pressures run 50-70% higher than R-22.

  • HFCs require POE or PVE oil; CFC/HCFC systems use mineral oil or alkylbenzene. POE is hygroscopic and forms acids with moisture.

  • Blends with glide (e.g., R-407C) fractionate on leaks; recover, evacuate, and recharge with virgin refrigerant rather than topping off.

Quick reference

System Components

  • Compressor raises pressure/temperature; scroll compressors must not run in reverse.

  • Condenser rejects heat; 8-15°F subcooling confirms adequate charge and heat rejection.

  • TXV modulates on evaporator superheat (typically 8-12°F); a fixed orifice relies on charge and load.

  • Filter-drier removes moisture and acid; sight glass bubbles indicate a starved liquid line or flashing.

Quick reference

Installation and Commissioning

  • Evacuate to 500 microns or below and hold under 500 for 10 minutes with the pump isolated.

  • Nitrogen pressure test before evacuation; never pressure-test with refrigerant or oxygen.

  • Flow dry nitrogen while brazing to prevent internal oxidation (scale).

  • Charge by weight for blends; verify with superheat (fixed orifice) or subcooling (TXV); 350-450 CFM per ton for comfort cooling.

Quick reference

Troubleshooting and Service

  • High suction + high head + cool compressor = overcharge or condenser airflow problem.

  • Low suction + high superheat + normal head = starved evaporator (low charge, restriction, TXV underfeeding).

  • A temperature drop across the liquid-line drier of more than a few degrees indicates a restriction.

  • High superheat + low subcooling = undercharge; low superheat + high subcooling = overcharge; high superheat + high subcooling = restriction or low airflow.