HVAC Excellence Refrigeration flashcards
HVAC Excellence Refrigeration · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ton of refrigeration
- A cooling rate equal to 12,000 Btu per hour, or 200 Btu per minute, or 3.517 kilowatts. It equals the heat absorbed to melt one ton of ice in 24 hours.
- Sensible heat
- Heat that changes a substance's temperature without changing its state. For air, the rate is Btu/h = 1.08 × CFM × temperature difference; for water, 500 × GPM × temperature difference.
- Latent heat of vaporization
- Heat absorbed when a liquid changes to vapor at constant temperature. For water at 212°F it is about 970 Btu per pound and rises as saturation pressure falls.
- Superheat
- The number of degrees a vapor is above its saturation temperature at the measured pressure. It is calculated as actual suction temperature minus saturation temperature at suction pressure.
- Subcooling
- The number of degrees a liquid is below its saturation temperature at the measured pressure. It is calculated as saturation temperature at liquid pressure minus actual liquid temperature.
- Refrigeration cycle order
- Compression, condensation, expansion, evaporation. The compressor raises pressure and temperature, the condenser rejects heat, the metering device drops pressure, and the evaporator absorbs heat.
- Carnot COP
- The maximum theoretical coefficient of performance: evaporating absolute temperature divided by the difference between condensing and evaporating absolute temperatures. Real systems always perform below this limit.
- ASHRAE safety group A1
- A refrigerant classification meaning lower toxicity (A) and no flame propagation (1). R-410A and R-134a are examples; R-32 is A2L and propane is A3.
- R-410A composition
- A near-azeotropic blend of 50% R-32 and 50% R-125. It has zero ozone depletion potential, must be charged as a liquid, and operates at pressures roughly 50-70% higher than R-22.
- POE lubricant
- Polyol ester oil required with HFC refrigerants because it is miscible with them. It is hygroscopic, so moisture must be excluded to prevent acid formation and compressor damage.
- Mineral oil use
- The traditional lubricant for CFC and HCFC refrigerants such as R-22. It is not miscible with HFC refrigerants, so it must not be used in HFC systems without an approved retrofit plan.
- Temperature glide
- The temperature range over which a zeotropic blend boils or condenses at a single pressure. Blends with glide fractionate when they leak, so systems must be recharged with virgin refrigerant.
- R-744 refrigerant
- Carbon dioxide, an A1 refrigerant with a global warming potential of 1. It operates at very high pressures and is used in commercial refrigeration and heat pump applications.
- Recovery cylinder fill limit
- Recovery cylinders must not be filled more than 80% of their capacity by liquid weight, leaving room for thermal expansion of the refrigerant as it warms.
- Compressor function
- The component that raises refrigerant pressure and temperature so the condenser can reject heat. Common types include reciprocating, scroll, rotary, and centrifugal; scroll compressors must not run in reverse.
- Condenser subcooling check
- Measuring liquid temperature below saturation temperature at the condenser outlet. A reading of about 8-15°F confirms adequate charge and heat rejection on a properly operating system.
- Thermostatic expansion valve
- A metering device that modulates refrigerant flow to maintain a set evaporator superheat, typically 8-12°F at the evaporator outlet, in response to bulb temperature and pressure.
- Fixed orifice metering
- A metering device with a fixed opening, such as a piston or capillary tube. Charge and superheat vary with load, so the system must be charged by weight or by superheat method.
- Liquid-line filter-drier
- A device that removes moisture and acid from the liquid refrigerant. A temperature drop across it of more than a few degrees indicates a restriction that should be corrected.
- Sight glass purpose
- A liquid-line window that shows bubbles when the liquid line is starved by low charge, a restriction, or flashing. A moisture indicator changes color as water content rises.
- Suction accumulator
- A device on the suction line that traps liquid refrigerant and meters it back to the compressor as vapor, protecting the compressor from liquid slugging during low-load or defrost operation.
- Evacuation target
- Pulling a system down to 500 microns or below and holding it under 500 for 10 minutes with the pump isolated. A rising micron gauge indicates moisture or a leak.
- Nitrogen pressure test
- Pressurizing a system with dry nitrogen, typically 150-300 psig for R-410A, before evacuation. Refrigerant or oxygen must never be used for pressure testing.
- Brazing with nitrogen
- Flowing dry nitrogen through piping while brazing to prevent internal oxidation. Without the purge, scale forms inside the lines and can clog the metering device and damage the compressor.
- Charging by weight
- Adding refrigerant measured on a scale to the manufacturer's specified amount. It is required for blends and critical systems, and is verified afterward by superheat or subcooling.
- Comfort airflow rate
- A design airflow of about 350-450 CFM per ton of cooling capacity. Low airflow causes low suction pressure, high superheat, and possible evaporator coil icing.
- High head, high suction
- A symptom pattern of high suction and high head pressure with a cool compressor, suggesting an overcharge or a condenser airflow problem. Check condenser coil and fan first.
- Low suction, high superheat
- A symptom pattern of low suction pressure, high superheat, and normal head pressure, suggesting a starved evaporator from low charge, a restriction, or an underfeeding expansion valve.
- Overcharge symptom pattern
- Low superheat with high subcooling indicates excess refrigerant. High superheat with low subcooling indicates undercharge; high superheat with high subcooling indicates a restriction or low airflow.
- Liquid-line restriction test
- Measuring temperature on both sides of a filter-drier or restriction. A temperature drop of more than a few degrees across the drier confirms a restriction that must be replaced.
- Compressor overload trip
- A compressor that trips on overload with high amp draw and hot windings. Check supply voltage, start components, and mechanical binding before condemning or replacing the compressor.
- Recovery requirement
- Refrigerant must be recovered rather than vented, using EPA Section 608 recovery equipment to the required vacuum level, with the recovered amount recorded on the service record.