IA Electrician flashcards
IA Electrician · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's law formula
- Ohm's law states E = I × R, where E is voltage in volts, I is current in amperes, and R is resistance in ohms. Power equals E × I.
- Three-phase power formula
- For a balanced three-phase load, real power in watts equals √3 times line voltage times line current times power factor: P = √3 × VL × IL × PF.
- Impedance formula
- Impedance combines resistance and reactance: Z = √(R² + X²). Inductive reactance XL = 2πfL and capacitive reactance XC = 1/(2πfC).
- GFCI trip threshold
- A Class A GFCI trips when current to ground reaches approximately 4 to 6 milliamperes, protecting personnel from electric shock.
- Lockout/tagout sequence
- De-energize equipment, apply locks and tags, release stored energy, and verify absence of voltage with a tester before work begins.
- Limited approach boundary
- The limited approach boundary is a distance from exposed energized parts that unqualified persons may not cross; qualified persons need PPE and a risk assessment.
- Small appliance branch circuits
- Dwelling units require at least two 20-ampere small-appliance branch circuits for kitchen, dining, pantry, and similar areas; GFCI protection is required.
- Service disconnect maximum
- A service may have no more than six disconnecting means grouped in one location, and each must be marked to identify the load served.
- Receptacle spacing rule
- In dwelling units, receptacle outlets along walls must be spaced so no point on the wall is more than six feet from a receptacle.
- 14 AWG overcurrent limit
- Copper 14 AWG conductors are generally limited to 15-ampere overcurrent protection by NEC 240.4(D), unless specific code exceptions apply.
- Conductor adjustment for 4-6
- Where four to six current-carrying conductors share a raceway or cable, conductor ampacity is adjusted to 80 percent of the table value.
- NM-B ampacity column
- NM-B cable ampacity is taken from the 60°C column of the ampacity tables, per NEC 334.80, unless termination limits allow otherwise.
- EMT support spacing
- EMT must be supported within 3 feet of each box and at intervals not exceeding 10 feet; support methods must be listed.
- Raceway bend limit
- Between pull points such as boxes or conduit bodies, a raceway may contain no more than 360 degrees total of bends.
- NM cable securing
- NM cable must be secured within 12 inches of each box and at intervals not exceeding 4.5 feet; protection from damage is required where needed.
- 14 AWG box fill volume
- Each 14 AWG conductor in a box requires 2.0 cubic inches of free space; 12 AWG requires 2.25 and 10 AWG requires 2.5.
- Device yoke fill count
- Each device yoke or strap counts as two conductor volumes based on the largest conductor connected to the device.
- Junction box accessibility
- Junction boxes, splices, and termination points must remain accessible without removing permanent building finish; they cannot be concealed.
- 15A receptacle on 20A circuit
- NEC Table 210.21(B)(3) permits 15-ampere receptacles on 20-ampere branch circuits under specified conditions, including receptacle rating and circuit use.
- Tamper-resistant receptacle requirement
- Tamper-resistant receptacles are required in dwelling units and in other specified child-care and guest-room locations to reduce foreign-object insertion.
- Ungrounded GFCI marking
- A GFCI receptacle may replace an ungrounded receptacle where no equipment grounding conductor exists; it must be marked 'No Equipment Ground.'
- Standard OCPD sizes
- Standard overcurrent device ratings include 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, and 100 amperes, continuing in standard steps.
- Next-size-up rule
- If a conductor's ampacity does not match a standard overcurrent device rating, the next higher standard rating is permitted when it does not exceed 800 amperes and conditions of 240.4(B) are met.
- Motor overload versus branch protection
- Motor overload protection protects the motor from overheating and is sized from motor nameplate current; branch-circuit overcurrent protection protects conductors against short circuits and ground faults.
- Service neutral bonding point
- The service grounded conductor is bonded to the service enclosure and grounding electrode system only at the service disconnect; downstream neutral-to-ground connections are prohibited.
- EGC sizing table
- Equipment grounding conductor size is selected from NEC Table 250.122 based on the rating of the overcurrent device protecting the circuit, with upsizing rules.
- Motor branch conductor 125%
- Motor branch-circuit conductors must have ampacity at least 125 percent of the motor full-load current, unless permitted otherwise by Article 430.
- HVAC MCA and MOP
- For hermetic refrigerant motor-compressors, nameplate minimum circuit ampacity (MCA) sizes conductors, and maximum overcurrent protection (MOP) sizes the branch-circuit protection.
- Class I Division 1 seal
- In Class I, Division 1 locations, conduit seals are required within 18 inches of the enclosure for certain arcing or sparking equipment.
- Pool receptacle distance
- Receptacles serving swimming pools must be located at least 6 feet from the inside wall of the pool and must have GFCI protection.
- Dwelling lighting load
- Dwelling-unit general lighting load is calculated at 3 volt-amperes per square foot for the floor area, subject to demand factors.
- Voltage drop single-phase
- Single-phase voltage drop can be estimated as VD = 2 × K × I × L / CM, where K is conductor resistivity, I is amperes, L is one-way length, and CM is circular mils.