IA Electrician · Work through your exam, one topic at a time.

All guide sections

Code Calculations, Load Computations, and Plan/Print Reading

Calculation questions are procedural. Set out the load components in a table and step through them in the order the Code requires; most errors come from skipping a step or mixing up demand factors.

Load computation order

  1. General lighting load from floor area and the basic load value in the applicable table.
  2. Small-appliance and laundry branch circuits at their required ratings.
  3. Specific appliances: ranges, dryers, water heaters, space heating, air conditioning, motors.
  4. Apply demand factors to the applicable components-lighting demand, range and dryer demand, and heating versus cooling (use the larger, not both).
  5. Add the largest motor at 25 percent.
  6. Compare the result with the service size and apply the continuous-load factor; then check neutral and grounding conductor sizing and voltage drop.

Plan and print reading

Know the symbols for receptacles, switches, panels, junction boxes, and equipment; read the scale and the title block; locate the panel schedules, riser diagram, and specifications. Panel schedules give circuit numbers, breaker sizes, and connected loads; the riser diagram shows feeder routing and ratings; specifications tell you which code edition and which listed products apply.

Traps

Adding heating and cooling together, forgetting the 25 percent largest-motor adder, using connected load instead of demand load, misreading a panel schedule, and ignoring notes on the drawing that override the plan.

Worked example

A feeder supplies a 60 A continuous load and a 40 A non-continuous load: 60 × 1.25 + 40 = 115 A. Choose conductors and overcurrent protection for at least 115 A, then verify voltage drop at the actual run length.