IA Electrician: Grounding and Bonding

IA Electrician · Work through your exam, one topic at a time.

All guide sections

Grounding and Bonding

Grounding and bonding questions are usually about paths and points. The system grounded conductor (neutral) is grounded at the service; the equipment grounding conductor provides a low-impedance fault path back to the source so the overcurrent device opens. These are separate functions and must remain separate downstream of the service.

Concepts to understand

  • The grounding electrode system ties the service to earth through electrodes and a grounding electrode conductor sized from the service conductor size.
  • Main bonding jumper connects the neutral bus to the enclosure at the service only.
  • At sub-panels, the neutral and ground buses are isolated and the enclosure is bonded by the equipment grounding conductor.
  • Bonding jumpers are required around water meters, at metallic raceway terminations, and wherever the fault path could otherwise be interrupted.
  • Equipment must be bonded to provide a fault path; a grounding electrode alone will not open a breaker.
  • Special rules apply to separately derived systems, isolated receptacles, and patient-care areas.

Traps

  • Re-bonding neutral and ground at a sub-panel (objectionable current on the ground path).
  • Sizing the grounding electrode conductor from the load rather than the service conductors.
  • Assuming a ground rod clears faults; the earth path is too high-impedance.
  • Lifting grounds to reduce noise.

Rule of thumb

Trace the fault path from the faulted enclosure back to the source: it must be metallic, continuous, and bonded at every joint. If any joint could open, a bonding jumper is required there.