IA HVAC flashcards
IA HVAC · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Sensible heat ratio
- Ratio of sensible heat to total heat (sensible plus latent). A coil SHR at or below space SHR is needed to control humidity; higher SHR means drier supply air relative to load.
- Wet-bulb temperature
- The lowest temperature air can reach by evaporative cooling at constant pressure. It reflects both temperature and moisture content and is used with dry-bulb to locate a state on the psychrometric chart.
- Humidity ratio
- Mass of water vapor per mass of dry air, usually lb water per lb dry air. It changes only with moisture addition or removal, not with sensible heating or cooling.
- Sensible heat equation
- Qs equals 1.08 times CFM times dry-bulb temperature difference for standard air at sea level. At altitude, replace 1.08 with a density-corrected coefficient.
- Ton of refrigeration
- A cooling rate equal to 12,000 Btu per hour, 200 Btu per minute, or 3.517 kilowatts. Equipment capacity is commonly stated in tons.
- Manual J
- ACCA residential load calculation procedure. It estimates heating and cooling loads from envelope, infiltration, internal gains, and design conditions; Manual S then selects equipment.
- Design conditions
- Outdoor and indoor temperature and humidity values used for load calculation, typically ASHRAE 1% cooling and 99% heating design values adopted by local code.
- Conduction load formula
- Q equals U times area times temperature difference, where U equals 1 divided by R. Used for walls, roofs, windows, and doors in heating and cooling load estimates.
- Equipment oversizing effects
- Excess capacity causes short cycling, poor latent removal, higher indoor humidity, and greater energy use. Select equipment close to the calculated load rather than by rule of thumb.
- AFUE
- Annual Fuel Utilization Efficiency, the seasonal efficiency rating for furnaces and boilers. Values of 90 percent or more generally indicate condensing equipment with PVC venting.
- Hydronic heat output
- Boiler output in Btu per hour equals GPM times 500 times water temperature drop. One GPM at a 20 F drop delivers about 10,000 Btu per hour.
- Heat pump balance point
- Outdoor temperature where heat pump capacity equals building heating load. Below this point supplemental heat operates to maintain indoor temperature.
- Condensing furnace
- A furnace that recovers latent heat from flue gas, reaching 90 percent or higher AFUE. It produces acidic condensate, uses PVC venting, and requires a drain.
- Vapor-compression cycle
- Sequence of compressor, condenser, expansion device, and evaporator. Refrigerant absorbs heat in the evaporator and rejects it in the condenser while the compressor raises pressure.
- Superheat
- Evaporator outlet temperature minus evaporating saturation temperature. It confirms the evaporator is fully flooded with vapor and is the charging method for fixed-orifice systems.
- Subcooling
- Condensing saturation temperature minus liquid line temperature. It indicates liquid refrigerant is present at the expansion device and is the charging method for TXV systems.
- TXV operation
- A thermostatic expansion valve modulates refrigerant flow to hold constant superheat at the evaporator outlet, responding to load changes and maintaining evaporator efficiency.
- Compression ratio
- Absolute discharge pressure divided by absolute suction pressure. High ratios reduce capacity and stress the compressor; ratios above about 10 to 1 are usually excessive.
- Equal friction duct sizing
- A duct design method that selects sizes for a constant pressure drop per 100 feet, commonly 0.1 inch water column, producing a self-balancing low-noise layout.
- External static pressure
- Total resistance the blower works against, including supply and return ducts plus coils and filters. It is compared to the manufacturer fan curve to verify airflow.
- ASHRAE 62.2
- Residential ventilation standard specifying whole-house mechanical ventilation rates based on floor area and occupants, plus local exhaust rates for bathrooms and kitchens.
- Duct leakage class
- SMACNA classification of allowable duct leakage as a percentage of design airflow. Sealing joints and minimizing leakage to outside improves efficiency and comfort.
- 24V thermostat terminals
- Standard control terminals: R is 24V hot, C is common, W calls heat, Y calls cooling, G runs the fan, and O or B energizes the reversing valve.
- Lockout tagout
- Safety procedure that isolates energy sources, verifies de-energization with a meter, and prevents accidental startup during service on HVAC electrical equipment.
- RLA and LRA
- Rated load amps and locked rotor amps from the compressor nameplate. RLA guides running amp checks; LRA indicates inrush current at startup.
- CFM per ton
- Nominal cooling airflow target of about 400 CFM per ton, typically 350 to 450. Low airflow causes frozen coils, low suction pressure, and poor humidity control.
- Charge verification method
- Use superheat for fixed-orifice systems and subcooling for TXV systems. Verify airflow and static pressure first, since airflow errors distort charge readings.
- Frozen evaporator causes
- Low airflow from dirty filters or blower faults, low refrigerant charge, or restricted metering devices. Ice forms because coil temperature falls below freezing.
- High head pressure causes
- Dirty condenser coil, overcharge, non-condensable gases, or high outdoor ambient temperature. Head pressure rises and capacity and efficiency fall.
- SEER2 and HSPF2
- Current efficiency ratings for cooling and heat pump heating under updated test procedures. Values are generally lower than legacy SEER and HSPF for the same equipment.
- A2L refrigerant
- Lower-flammability refrigerant classification such as R-32 and R-454B. Handling requires updated leak detection, ventilation, and charging procedures per ASHRAE 15 and 34.
- ASHRAE 90.1
- Energy standard for commercial buildings covering envelope, lighting, HVAC efficiency, economizers, and controls. Local codes adopt or amend it as the minimum requirement.