IA HVAC · Give each week a clear focus.

8 weeks · About 7 hours per week

Week 1

HVAC Fundamentals and Psychrometrics

  • Define dry-bulb, wet-bulb, dew point, relative humidity, humidity ratio, and enthalpy, and state which pairs fully fix a moist-air state point.

  • Read psychrometric chart values for at least 12 given state points and convert between humidity ratio and relative humidity without a calculator shortcut.

  • Compute sensible heat ratio and identify the apparatus dew point for a simple cooling-coil process line on the chart.

  • Sketch and label the four basic air processes (sensible heating, sensible cooling, humidification, dehumidification) with the direction of state-point movement.

Your checkpoint

A one-page psychrometric cheat sheet plus 15 worked chart-reading problems solved with answers and units shown.

Week 2

Load Calculation and System Sizing & HVAC Fundamentals and Psychrometrics

  • Perform a manual block load for a single-zone space: conduction through walls, roof, and glass, plus solar, internal, infiltration, and ventilation loads.

  • Distinguish heating design load from cooling design load and justify why they use different outdoor design conditions.

  • Apply the sensible heat equation Q = 1.08 x cfm x delta-T and the latent form Q = 4.5 x cfm x delta-W to at least six load scenarios.

  • Estimate ventilation load using outdoor-air fraction and compare it against total coil load.

  • Explain how load calculation output feeds equipment selection, including safety factor and oversizing penalties.

Your checkpoint

A completed room-by-room load estimate for a sample single-story building with totals, assumptions, and a short note on oversizing risk.

Week 3

Cooling Systems and Refrigeration Cycle & Load Calculation and System Sizing

  • Trace the vapor-compression cycle on a pressure-enthalpy diagram and label all four components and state points.

  • Calculate cooling capacity, compressor power, and coefficient of performance from given enthalpy values.

  • Explain superheat, subcooling, and how each is measured and used as a charging and diagnostic indicator.

  • Compare the operating characteristics of reciprocating, scroll, and screw compressors and of air-cooled versus water-cooled condensers.

  • Match system type (split, packaged, chiller, VRF) to a given load profile and building constraint.

Your checkpoint

A labeled P-h diagram with a solved example cycle (capacity, power, COP) plus a one-page equipment selection comparison table.

Week 4

Air Distribution, Duct Design and Ventilation

  • Size supply and return ducts using the equal-friction and velocity-reduction methods and compare the results.

  • Calculate friction loss, equivalent length, and available static pressure for a simple duct run.

  • Select grilles and diffusers to meet throw, drop, and noise criteria for a given room.

  • Apply the ASHRAE 62.1 ventilation-rate procedure to compute outdoor air required for a multi-zone system.

  • Identify causes of poor air balance and describe how to correct them.

Your checkpoint

A duct layout with sizing table, static pressure budget, and calculated outdoor-air requirement for a three-zone example.

Week 5

Heating Systems and Equipment

  • Compare furnace types (natural draft, induced draft, condensing) and state efficiency ranges and venting implications for each.

  • Compute heating output from fuel input and steady-state efficiency, and explain derating for altitude.

  • Describe hydronic boiler components, expansion tank sizing logic, and the role of circulators and air elimination.

  • Explain combustion safety checks: draft, carbon monoxide, excess air, and flue gas temperature.

  • Select a heat pump and explain balance point, auxiliary heat, and defrost behavior.

Your checkpoint

A heating equipment comparison matrix with efficiency, venting, and control requirements, plus three solved output and balance-point problems.

Week 6

Controls, Electrical and Safety & Commissioning, Maintenance and Troubleshooting

  • Read a ladder diagram for a basic fan and compressor circuit and identify the control, safety, and load devices.

  • Explain thermostat types, deadband, staging, and proportional versus on/off control behavior.

  • Size overcurrent protection and conductor ampacity for a given motor using nameplate data and standard tables.

  • List required safety devices (high-limit, low-pressure, freeze stat, flow switch) and state what each protects.

  • Describe a commissioning sequence for a new rooftop unit from pre-start checks through functional performance testing.

Your checkpoint

An annotated control schematic plus a one-page commissioning checklist with acceptance criteria for each step.

Week 7

Commissioning, Maintenance and Troubleshooting & Cooling Systems and Refrigeration Cycle

  • Build a troubleshooting decision tree for low suction pressure, high head pressure, and low capacity.

  • Interpret superheat, subcooling, delta-T, and amp draw together to isolate a fault rather than guess.

  • Distinguish airflow problems from refrigerant problems using measured data.

  • Write preventive maintenance tasks with frequencies for coils, belts, filters, drains, and safeties.

  • Practice documenting a fault, the evidence, and the corrective action in a service report format.

Your checkpoint

Three completed case-study diagnostics with measured readings, the fault identified, and the corrective action written as a service report.

Week 8

Codes, Standards and Energy Efficiency & Load Calculation and System Sizing

  • Summarize the scope of the key codes and standards affecting HVAC design, installation, and energy use without quoting them verbatim.

  • Explain how energy code requirements drive equipment efficiency minimums, economizer use, and duct insulation.

  • Apply economizer and outside-air control logic to a given climate and load scenario.

  • Review your week 2 load estimate against energy code ventilation and insulation assumptions and correct any gaps.

  • Complete a timed mixed-domain practice set and review every missed item to its root concept.

Your checkpoint

A two-page code and efficiency summary plus a scored 60-question mixed practice exam with a written error log.

Milestones

Week 2: Can complete a single-zone cooling and heating load estimate unaided and explain each load component.

Week 4: Can size a simple duct run, produce a static pressure budget, and calculate outdoor air by procedure without notes.

Week 6: Can read a control schematic, identify safety devices, and describe a commissioning sequence from memory.

Week 8: Scores at least 75 percent on the 60-question mixed practice exam with every miss traced to a domain.