IAPMO UMC MI case studies
IAPMO UMC MI · Put your knowledge to work in context.
The IAPMO UMC MI credential is listed on this independent study platform as an IAPMO certification exam covering the Uniform Mechanical Code. IAPMO describes itself as a global team of experts engaging industry and government for a safer built environment, and states that its workforce training and certification mission is to provide code and trade professionals with industry-leading training and certification. The IAPMO UMC MI case studies are 5 cases and about 3,687 words.
1Common-Vented Furnace and Water Heater in a Finished Basement
Final mechanical inspection of a 1962 split-level house. The contractor replaced an 80% AFUE, 100,000 Btu/h Category I furnace that has a draft hood, and left the existing 40,000 Btu/h atmospheric water heater.
742 words, about 4 min2Four-Ton Heat Pump With High External Static and a Missing Condensate Trap
Final inspection of a new 2,000-square-foot house with a 4-ton variable-speed heat pump and a nominal 1,600 cfm air handler. The air handler is in a garage attic.
771 words, about 4 min3Failed Gas Piping Pressure Test and a Confined Water Heater Closet
A tenant build-out includes a new 1-1/4 inch Schedule 40 black steel gas line, 95 feet from the meter to a 250,000 Btu/h packaged rooftop unit. The contractor pressure-tests the new line with air at 3 psi using a 0 to 15 psi gauge marked in 0.1 psi increments.
744 words, about 4 min4Expired Rooftop Unit Permit With Concealed Work and No Final
A permit was issued on March 3 for replacement of a 5-ton rooftop unit at a restaurant. The approved plans show seismic restraint, 12-inch clearance to combustibles, an economizer, a disconnect within sight, and a condensate drain.
732 words, about 4 min5Carbon Monoxide Alarm and an Unpermitted Ductless Split in an Apartment
A complaint inspection at a 12-unit apartment building finds a carbon monoxide alarm in unit 2 reading 65 ppm. In the basement, a 300,000 Btu/h atmospheric boiler is connected to a 6-inch masonry chimney with spalling mortar and visible spillage at the draft hood.