Permit abandonment period
A permit is deemed abandoned when work does not begin within 180 days of issuance or is suspended for 180 days; the building official may revoke it afterward.
Certificate of occupancy
Issued by the building official after a final inspection confirms compliance with approved documents and code; the building may not be occupied before it is issued.
Board of appeals function
The board hears appeals of building official interpretations and requests for code variances. Filing an appeal does not stay an enforcement action unless the board orders a stay.
Approved construction documents
A permit holder must keep one approved set of construction documents on the job site at all times during construction, and all work must conform to them.
Occupancy Group R
Residential occupancies providing sleeping accommodations other than institutional. R-1 includes hotels, R-2 apartments, R-3 one- and two-family dwellings, and R-4 residential care.
Accessory occupancy limit
An accessory occupancy must be ancillary to the principal occupancy and may not exceed 10 percent of the floor area of the story in which it is located.
Grade plane definition
A reference plane representing the average finished ground level adjoining the building at all exterior walls; it is the datum for measuring building height and stories above grade plane.
Incidental use
A subordinate use listed in Table 509, such as a furnace room or hazardous storage, that requires separation from the remainder of the building but is not a separate occupancy.
Type IA construction
Noncombustible construction in which structural members have a 3-hour fire-resistance rating; it is the most restrictive type and permits the greatest height and area.
Frontage increase formula
If = (F/P - 0.25) x W/30, where F is the building perimeter on open frontage, P is total perimeter, and W is open width capped at 30 feet.
Fire wall function
A fire wall divides a building into separate buildings, is continuous from the foundation to above the roof, and is rated between 2 and 4 hours.
Sprinkler area increase
A fully sprinklered building may increase its allowable area by 200 percent if one story, or 300 percent if more than one story, under Section 506.3.
Shaft enclosure requirement
Stairways, elevators, chutes, and ducts must be enclosed in fire-resistance-rated construction under Section 713, with rated opening protectives provided at each floor level.
Smoke barrier rating
A smoke barrier is a continuous membrane with at least a 1-hour fire-resistance rating extending from the floor to the underside of the deck above.
Draftstopping in attics
In combustible attic and crawl space areas, draftstopping must subdivide the concealed space into areas not exceeding 3,000 square feet.
Penetration firestop system
An approved assembly tested to ASTM E814 or UL 1479 that restores the fire-resistance rating of a floor or wall penetrated by pipes, cables, or ducts.
Business occupant load factor
The occupant load factor for business use is 150 gross square feet per occupant, used to compute the number of occupants from the floor area.
Stair egress width factor
Egress width for stairs is 0.3 inch per occupant in unsprinklered buildings and 0.2 inch per occupant in sprinklered buildings.
Accessible route width
The accessible route must provide at least 36 inches of clear width; the clear floor space needed for a wheelchair is 30 by 48 inches.
Ramp slope limit
Ramps on an accessible route have a maximum slope of 1:12, a maximum rise of 30 inches between landings, and landings at least 60 inches long.
Office live load
The uniformly distributed live load for office floors is 50 psf, while corridors serving the public are typically designed for 100 psf.
Floor deflection limit
Floor members are limited to L/360 deflection under live load where they support plaster or stucco ceilings, and L/240 where they do not.
Seismic design category
A classification from A through F assigned using mapped spectral accelerations Ss and S1, the site class, and the risk category; higher categories impose stricter detailing.
Special inspection
Quality assurance inspection required by Chapter 17 for items such as welding, high-strength bolting, concrete placement, and soils, performed by an approved agency.
Weather-resistant barrier
A water-resistive membrane installed behind exterior wall cladding over the sheathing to drain water and protect the structure from moisture intrusion.
Combustible wall covering limits
Combustible exterior wall coverings are restricted by building height, fire separation distance, and sprinkler protection under the tables in Chapter 14.
Roof covering class
Roof coverings are rated Class A, B, or C by ASTM E108 testing; the required class depends on the occupancy and the fire separation distance.
Fire separation distance
Measured from the exterior wall face to the lot line, the centerline of a street, or another building; it determines required wall ratings and opening limits.
NFPA 13R system
An automatic sprinkler system designed to NFPA 13R for residential occupancies up to and including four stories, with reduced requirements compared to NFPA 13.
High-rise threshold
A building with an occupied floor more than 75 feet above the lowest level of fire department vehicle access, triggering additional life-safety and fire protection features.
Standpipe classes
Class I standpipes provide 2.5-inch outlets for fire department use, Class II provides 1.5-inch hose for occupants, and Class III provides both.
Climate zone envelope
The IECC assigns climate zones 1 through 8; envelope insulation and fenestration requirements become more stringent in colder zones, adopted locally through Chapter 13.