ICC M2 study materials
ICC M2 study resources

ICC M2 flashcards

ICC M2 · Build recall with a focused review session.

31 cards. Read the term and the definition here. The deck at the top of this page is optional.

Permit required for replacement
Replacing a mechanical appliance or system generally requires a permit, while ordinary repairs that do not involve fuel or electrical connections may be exempt.
Rough-in inspection timing
Rough-in inspection must occur after the installation of ductwork, piping, and equipment but before any of it is concealed by building finishes.
Listed and labeled
Equipment and materials must be tested by a recognized agency and bear a label showing compliance with a standard; field modification voids the listing.
Manufacturer instructions govern
Where the code is silent on an installation detail, the manufacturer's published installation instructions control and must be followed for the listed appliance.
Accessibility requirement
Appliances must be reachable for inspection, service, repair, and replacement without cutting or removing permanent parts of the building structure.
Garage ignition source height
In garages, burners and ignition sources of appliances must be at least 18 inches above the floor unless the appliance is specifically listed for a lower height.
Attic furnace platform
An attic or under-floor furnace needs a level service platform and a clear passageway sized to allow service of the burner, controls, and heat exchanger.
Clearance reduction shield
Reduced clearance to combustibles is allowed only with an approved shield or method, and the resulting clearance must match the listing or code table.
Prohibited return air sources
Return air may not be drawn from bathrooms, kitchens, garages, or unconditioned attics unless specific code conditions for that source are satisfied.
Condensate drain requirements
Cooling coils require a trapped condensate drain with proper slope and, where required, a secondary drain or auxiliary pan with a drain.
Duct sealing class
Duct systems must be sealed to the required leakage class, with joints, seams, and connections sealed using approved tape, mastic, or gaskets.
Duct insulation vapor retarder
Ducts located in unconditioned space need insulation with the vapor retarder on the warm side to prevent condensation on the duct surface.
Bath and kitchen exhaust
Exhaust from bathrooms and kitchens must discharge outdoors through an approved termination and may not discharge into an attic or crawl space.
Fire damper at rated assembly
Where a duct penetrates a fire-rated wall or floor assembly, an approved fire damper must be installed per its listing to maintain the rating.
Flexible duct support
Flexible duct must be supported at the spacing required by its listing, kept from excess sag, and limited in length and bend radius.
Outdoor air ventilation rate
Mechanical ventilation must supply outdoor air at the rate set by the code for the occupancy type, based on occupant load and floor area.
Two-opening combustion air
Indoor combustion air uses two permanent openings, one within 12 inches of the top and one within 12 inches of the bottom of the enclosure.
Indoor air opening free area
For the two-opening method, each opening needs at least 1 square inch of free area per 1,000 Btu/h of total input, with a 100 square inch minimum.
Vertical duct outdoor air
When combustion air openings connect to outdoors through vertical ducts, each opening must have free area of at least 1 square inch per 4,000 Btu/h.
Horizontal duct outdoor air
When combustion air openings connect to outdoors through horizontal ducts, each opening must have free area of at least 1 square inch per 2,000 Btu/h.
Single opening combustion air
A single permanent opening near the top of the enclosure may supply combustion air if it has free area of at least 1 square inch per 3,000 Btu/h.
Vent connector slope
A vent connector for a Category I appliance must slope upward toward the chimney or vent at not less than 1/4 inch per foot of run.
Chimney lining
A chimney must be lined with an approved material and sized to the appliance; an oversized flue promotes condensation and weak draft.
Type B vent clearance
Listed Type B vent maintains its clearance to combustibles as stated on the label; single-wall connectors need greater clearance unless shielded.
Refrigerant piping protection
Refrigerant lines must be supported, protected from damage, and joined with approved fittings; brazed joints require proper purging during installation.
Refrigerant quantity limit
The allowable refrigerant charge in an occupied space depends on the refrigerant safety classification and the volume of that space.
Boiler relief valve discharge
A boiler pressure-relief valve must not be capped or reduced and must discharge by gravity to a safe location where discharge causes no injury.
Hydronic air elimination
Hydronic systems require expansion control, air-elimination devices, and relief protection to operate safely and avoid air-bound loops.
Gas piping leak test
Fuel gas piping must be tested for leaks with air or inert gas at the specified pressure and duration before being placed in service.
Gas sediment trap
A sediment trap is required at the appliance connection to capture debris and protect the appliance controls from contamination.
Fuel gas pipe sizing
Gas piping must be sized using the total connected load and allowable pressure drop so every appliance receives adequate pressure at full demand.