The ICC Commercial Building Inspector (B2) credential is one of the certification opportunities the International Code Council describes as supporting career development for building safety professionals. ICC Credentialing states that its credentials "demonstrate a confirmed commitment to protect public health, safety, and welfare," and positions certification as a way to raise the professionalism of a department while furthering an individual's career. The ICC Commercial B2 case studies are 5 cases and about 2,452 words.

1

Accessory Office in a Warehouse: Exit Count Trap

A permit application proposes to convert a 14,500-square-foot, single-story Type II-B warehouse (Group S-1) into a storage and distribution facility with a 1,300-square-foot office at the front. The existing building has one 36-inch side-hinged door at the main entrance and one 10-foot roll-up door at the loading dock.

549 words, about 3 min
2

Mezzanine Dining: One Stair and No Accessible Route

A 9,000-square-foot, single-story Group A-2 restaurant is proposed in Type V-B construction without sprinklers. The design adds a 1,200-square-foot dining mezzanine with fixed tables and chairs and an occupant load of 80.

478 words, about 2 min
3

Sprinkler Trigger in a 12,000-Square-Foot Restaurant

A 12,000-square-foot Group A-2 restaurant is proposed in a one-story Type II-B building. The building has no automatic sprinkler system.

473 words, about 2 min
4

Evaluation Report Does Not Match the Wall Assembly

A two-story Type II-B office building is proposed with an exterior wall 8 feet from the property line. The wall is required to have a 1-hour fire-resistance rating.

470 words, about 2 min
5

Open Parking Garage Claim Fails Perimeter Opening Test

A five-story parking garage, 300 feet by 150 feet with 10-foot floor-to-floor heights, is proposed as an open parking garage. The north wall has openings equal to 18 percent of its wall area, and the east wall has openings equal to 22 percent.

482 words, about 2 min