ICC M3 study materials
ICC M3 study resources

ICC M3 cheat sheet

ICC M3 · Keep the key ideas within reach.

Quick reference

Mechanical Code - General Requirements and Administration

  • Permits are required for installation, alteration, replacement, or relocation of mechanical systems; ordinary repairs and routine maintenance do not require a permit.

  • Permit applications must include construction documents drawn to scale showing the size, location, and type of equipment, ductwork, and piping.

  • Inspection stages typically include rough-in inspection before concealment and final inspection after the system is complete and operational.

  • The code official may require tests to demonstrate compliance; work not approved must be corrected and reinspected before use.

  • Approved materials and appliances must be listed or labeled by an approved agency where the code requires listing.

  • Defective or noncompliant work may be ordered stopped by a stop-work order until the condition is corrected.

  • Appeals of code official decisions go to the board of appeals within the time specified by the adopting jurisdiction.

  • Equipment must be installed per the manufacturer's listed instructions; where instructions conflict with the code, the more restrictive applies.

  • Unsafe conditions constitute grounds for the code official to order the equipment or system disconnected from its energy source.

Quick reference

Mechanical Code - Heating, Cooling and Ventilation Systems

  • Return air from a dwelling unit must not be taken from a different dwelling unit, and return air plenums must not draw from bathrooms, kitchens, or closets.

  • Combustion appliances located in a garage must have ignition sources elevated not less than 18 inches above the floor unless listed for garage installation.

  • Appliances in attics and crawl spaces need a permanently installed walkway or service platform and a lighting outlet near the service access.

  • Working clearance in front of heating and cooling equipment is generally 30 inches wide by 30 inches deep, or the manufacturer's larger requirement.

  • A cooling coil condensate drain must be trapped and discharged to an approved receptor; a secondary drain or pan with a switch is required where damage could occur.

  • Outdoor condensing units require clearance per the manufacturer's instructions for airflow and service access.

  • Ventilation air quantities for occupancies are determined from the adopted mechanical code or referenced ventilation standard tables.

  • Equipment must be accessible for inspection, service, repair, and replacement without removing permanent construction.

Quick reference

Mechanical Code - Exhaust Systems

  • Bathroom and toilet room exhaust must discharge outdoors, not into an attic, crawl space, or other interior space.

  • Domestic kitchen exhaust hoods must discharge outdoors except where listed recirculating systems are permitted by the code.

  • Clothes dryer exhaust ducts must terminate outdoors with a backdraft damper and must not use screws or fasteners that penetrate the duct interior.

  • Dryer exhaust duct length limits and equivalent lengths for fittings are set by the manufacturer and the code; transitions to smaller duct sizes are prohibited.

  • Type I commercial kitchen hoods require grease duct enclosure, clearance to combustibles, and a fire suppression system.

  • Type II hoods are for heat, moisture, and odors without grease or smoke and do not require grease duct protection.

  • Exhaust ducts from hazardous or noxious sources must not connect to other exhaust systems and must discharge to a location that protects building openings.

  • Makeup air must be provided for exhausted air in quantities sufficient to maintain the required pressure relationships and appliance draft.

Quick reference

Mechanical Code - Duct Systems and Combustion Air

  • Duct systems must be sized, installed, and sealed to convey air without leakage into or from the building envelope beyond code allowances.

  • Ducts in unconditioned spaces must be insulated to the required R-value and have a vapor retarder on the exterior of the insulation.

  • Factory-made flexible duct must be supported at intervals not exceeding 4 feet and not be compressed or bent sharply.

  • Duct penetrations of fire-rated assemblies require listed fire dampers installed per their listing and the assembly's rating.

  • Combustion air for fuel-burning appliances is provided by the indoor air method, outdoor air method, or a combination, per code volume and opening sizing rules.

  • Two permanent openings to outdoors are sized based on the total input rating of appliances in the space, using the code's ratio of free area to Btu/h input.

  • Where combustion air is taken from indoors, the space must meet the code's minimum volume per Btu/h of appliance input or be provided with outdoor air.

  • Duct joints, seams, and connections must be sealed with approved materials; tapes and mastics must be listed for the application.

  • Return air ducts must not pass through or connect spaces prohibited by the code, such as bathrooms, kitchens, or garages.

Quick reference

Mechanical Code - Chimneys, Vents and Refrigeration

  • Chimney and vent connectors must be sized to the appliance input and installed with the required rise and slope toward the chimney.

  • Vent termination height above roofs is determined by roof pitch and proximity to walls, dormers, and air intakes.

  • Category I appliances vent under negative pressure and require a properly sized vertical vent or chimney; Category IV appliances are positive pressure and require listed venting.

  • A vent connector must not be smaller than the appliance flue collar and must slope upward toward the chimney at the code-required rate.

  • Mechanical draft systems must be listed and installed so that flue gases are safely vented under all operating conditions.

  • Refrigerant systems must use refrigerants classified by safety group, and refrigerant quantity limits per occupied space apply.

  • Refrigerant piping must be supported, protected from physical damage, and tested for leaks before being placed in service.

  • Machinery rooms for refrigeration systems require the ventilation, detection, and access provisions specified for the refrigerant class and charge.

  • Chimneys must be supported independently and provided with the required clearance to combustibles or listed clearance reduction methods.