ICC P3 flashcards
ICC P3 · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Plan review submission
- Plumbing permit drawings must be drawn to scale and show floor plans, riser or isometric diagrams, fixture locations and types, pipe sizes and materials, and the building occupancy classification.
- Permit expiration
- A plumbing permit lapses where work has not commenced within 180 days of issuance, or where work is suspended or abandoned for 180 days, unless an extension is granted.
- Work exempt from permit
- Clearing stoppages, repairing leaks in drains, water, soil, waste, or vent pipe, and reinstalling an existing water closet without disturbing the trap do not require a plumbing permit.
- Certificate of occupancy
- Issued only after the final plumbing inspection is approved; the code official may require water, air, or smoke tests and rough-in inspections before sign-off.
- Alternate materials approval
- Materials, methods, or designs not specifically listed in the code may be used only when the code official approves them in writing based on evidence of equivalent performance.
- Water closet flush volume
- The maximum flush is 1.6 gallons for a water closet, and 1.28-gpf water closets also comply; urinals are limited to 1.0 gallon per flush.
- Trap seal depth
- The water seal of a fixture trap must be not less than 2 inches and not more than 4 inches deep, measured at the trap weir.
- Trap arm length limits
- Maximum developed length from trap weir to vent is 5 feet for 1-1/4 inch, 6 feet for 1-1/2 inch, 8 feet for 2 inch, 12 feet for 3 inch, and 16 feet for 4 inch pipe.
- Bathroom group fixture units
- A private bathroom group of water closet, lavatory, and bathtub or shower equals 5 drainage fixture units with a flush tank and 6 with a flushometer valve.
- Accessible lavatory height
- An accessible lavatory has a rim no higher than 34 inches above the finished floor, with knee and toe clearance and insulated hot water and drain piping.
- Trap primer requirement
- Traps subject to evaporation, such as floor drains in infrequently used areas, must be protected by a trap primer or another approved means of maintaining the seal.
- T&P relief valve discharge
- The discharge pipe must be the full size of the valve outlet, gravity-drained, with no valves or traps, terminating not more than 6 inches above the floor or outside the building.
- Water heater drain pan
- A pan at least 1-1/2 inches deep with a drain of at least 3/4 inch is required where a tank leak would damage the structure, finish, or the ceiling below.
- Garage water heater elevation
- In private garages, a water heater whose ignition source is within 18 inches of the floor must be elevated so the ignition source is at least 18 inches above the floor.
- Thermal expansion tank
- Required where a check valve, backflow preventer, or pressure-reducing valve creates a closed system and expanding water cannot flow back into the supply main.
- Seismic water heater strapping
- Two straps are required where seismic design category C or greater applies, with one strap in the lower third and one in the upper third of the tank.
- Minimum water service size
- The building water service is not smaller than 3/4 inch, and no individual fixture supply is smaller than 3/8 inch except where the code permits otherwise.
- Pressure reducing valve threshold
- Where static water pressure exceeds 80 psi, a pressure-reducing valve must be installed and is typically set to deliver 50 to 60 psi downstream.
- Flushometer water closet supply
- A flushometer-valve water closet requires a minimum 1-inch fixture supply, while a flush-tank water closet requires only a 3/8-inch supply.
- Hydrostatic test
- Water distribution piping must be tested and proved tight under pressure at or above the working pressure, and the test must be approved before the piping is concealed.
- Water and sewer separation
- Where water service pipe crosses a building sewer, the water pipe must be laid at least 12 inches above the sewer, with additional separation required in the same trench.
- Air gap backflow protection
- An air gap provides complete backflow protection; hose bibbs and sill cocks also require an approved vacuum breaker or other listed backflow prevention device.
- Drain slope by pipe size
- Pipes 2-1/2 inches and smaller slope at 1/4 inch per foot; 3-inch and larger horizontal drains slope at 1/8 inch per foot, with 1/4 inch also permitted.
- Building sewer minimum size
- The building sewer must be at least 4 inches in diameter and is sized from the total drainage fixture units it serves using the building drain and sewer table.
- Cleanout locations
- Cleanouts are required at the base of each stack, at the upper end of each horizontal drain, at horizontal changes exceeding 45 degrees, and at intervals not over 100 feet.
- Vent termination height
- A vent stack extended through the roof must terminate at least 6 inches above the roof surface and must not end under an overhang or near an air intake.
- Secondary roof drainage
- Overflow drains or scuppers are required in addition to primary roof drains where a parapet wall or similar condition could allow water to pond if the primary drain blocks.
- Backwater valve
- Fixtures that drain to a point below the level of the next upstream manhole on the sewer must be protected by an automatically closing backwater valve.
- Gas piping test pressure
- Fuel gas piping is tested at not less than 1-1/2 times the maximum working pressure and never less than 3 psi, held for a minimum of 10 minutes.
- Sediment trap
- A drip leg or sediment trap is required at the inlet of each gas appliance, downstream of the shutoff valve, unless the appliance has an integral sediment trap.
- Combustion air openings
- Two permanent openings are required, sized at 1 square inch per 1,000 Btu/hr for indoor air, 1 per 2,000 for horizontal outdoor ducts, and 1 per 4,000 for vertical ducts.
- Grease interceptor
- Food-service sinks discharge through a grease interceptor sized to the fixture flow and grease retention capacity, with a vented, accessible cover and a solids-retaining compartment.