ICC M1 study materials
ICC M1 study resources

ICC M1 cheat sheet

ICC M1 · Keep the key ideas within reach.

Quick reference

General Administration

  • A permit is required before installing, altering, replacing, or repairing a mechanical system; ordinary repairs that do not change capacity or safety are exempt.

  • Approved construction documents and the permit must remain available on site, and field changes require revised approval before the work proceeds.

  • Concealed mechanical work such as ducts, piping, and vents must be inspected and approved before it is covered.

  • Materials and equipment must be listed and labeled by an approved agency and installed in accordance with the listing and manufacturer instructions.

  • The code official may issue a stop-work order for work performed without a permit or contrary to the code; work stops until the order is resolved.

  • Appeals of code official decisions are heard by the board of appeals, and the appeal must be filed within the time specified by the jurisdiction.

  • A permit becomes invalid if work does not commence within 180 days of issuance or is suspended or abandoned for 180 days, unless extended.

  • In code language, 'shall' is mandatory, 'may' is permissive, and 'approved' means accepted by the code official.

Quick reference

Definitions and Referenced Standards

  • Approved: accepted by the code official as meeting the code, typically through listing, labeling, or other evidence of suitability.

  • Listed: equipment or materials included in a list published by an approved agency that maintains periodic inspection of production.

  • Labeled: equipment or materials bearing the label, symbol, or mark of an approved listing agency.

  • Occupiable space: an enclosed space intended for human occupancy, excluding closets, storage rooms, parking garages, and crawl spaces.

  • Plenum: a space used for air distribution that is part of an HVAC system; combustible materials and storage in plenums are restricted.

  • Combustion air: the air required by a fuel-burning appliance for combustion and draft, supplied from indoors, outdoors, or both.

  • Dwelling unit: a single housekeeping unit with permanent provisions for living, sleeping, eating, cooking, and sanitation.

  • Referenced standards are enforceable as part of the code for the specific subject matter and edition adopted by the jurisdiction.

Quick reference

Heating and Ventilation Equipment and Appliances

  • Heating appliances in private garages must have ignition sources elevated at least 18 inches above the floor unless listed for a lower installation height.

  • Clearances to combustible materials must follow the listing, label, or code table and may be reduced only with approved protection.

  • Appliances located in closets or alcoves must have adequate combustion air, access for service, and protection from obstruction by doors or stored items.

  • Service access must allow inspection, repair, and replacement, including removal of the largest component of the appliance.

  • Natural ventilation requires operable openings to the outdoors with openable area not less than 4 percent of the floor area being ventilated.

  • Mechanical ventilation rates are determined from occupancy tables using occupant density and floor area, then supplied during occupied periods.

  • Direct-fired heating equipment must be installed according to its listing and the occupancy restrictions applicable to the space served.

  • Heating and ventilation equipment must be supported and fastened securely, and joints and connections must be tight and approved for the application.

Quick reference

Air Conditioning

  • The primary condensate drain must be at least 3/4 inch nominal size and slope at least 1/8 inch per foot toward an approved disposal point.

  • A secondary drain pan is required where condensate overflow could cause damage; the pan must be watertight, at least 1.5 inches deep, and drained.

  • Condensate traps must be installed per manufacturer instructions with sufficient depth to overcome fan pressure and prevent air from being drawn through the drain.

  • Condensate must discharge to an approved location and must not create a nuisance or discharge onto a public way or adjacent property.

  • Outdoor condensing units require manufacturer-specified clearances so discharge air is not recirculated and service access is maintained.

  • Air-conditioning equipment must be accessible for service and installed level or at the slope required by the manufacturer.

  • Refrigerant lines must be supported, protected from physical damage, and insulated where required to prevent condensation or energy loss.

  • Duct connections to air-conditioning equipment must be sealed and mechanically secured to prevent leakage.

Quick reference

Refrigeration and Cooling Systems

  • Refrigerants are classified by toxicity and flammability: A1 is lower toxicity and no flame propagation; B1 is higher toxicity and no flame propagation.

  • A2, A3, B2, and B3 refrigerants have flammability characteristics and require additional safety measures.

  • A machinery room is required when refrigerant quantity exceeds the code threshold or when required for the occupancy and refrigerant group.

  • Machinery rooms require mechanical ventilation, refrigerant detection where required, and access and construction features specified by the code.

  • Refrigerant detectors must activate alarm or ventilation before concentrations reach hazardous levels.

  • Pressure-relief devices must discharge outdoors to a safe location away from windows, doors, and air intakes.

  • Refrigerant piping must be supported and protected from physical damage, and joints must be accessible where required for service.

  • Refrigerant quantity limits in occupied spaces are based on refrigerant group, occupancy classification, and whether the system is high-probability.

Quick reference

Duct Systems

  • Ducts must be constructed and sealed in accordance with an approved duct construction standard such as SMACNA or an approved equivalent.

  • Duct joints, seams, and connections must be sealed to the required seal class to limit air leakage.

  • Return air cannot be taken from bathrooms, kitchens, garages, closets, mechanical rooms, or unconditioned attics.

  • Flexible air ducts must be installed fully extended, supported per the manufacturer, and with bends that do not restrict airflow.

  • Fire dampers are required where ducts penetrate fire-resistance-rated assemblies, and smoke dampers where required by the code.

  • Underground and under-floor plenums must be constructed and sealed to prevent entry of soil gas, moisture, and contaminants.

  • Duct insulation and vapor retarders must be installed to prevent condensation and must comply with the adopted energy code.

  • Horizontal ducts must be supported at intervals allowed by the duct construction standard, independent of duct joints and connections.

Quick reference

Chimneys, Vents and Combustion Air

  • A chimney must extend at least 3 feet above the highest point where it passes through the roof and at least 2 feet above any building within 10 feet.

  • Type B gas vents must terminate at least 2 feet above the highest roof point within 10 feet and at least 5 feet above the appliance draft hood.

  • Category I appliances use vertical chimneys or vents designed for negative pressure; Category IV appliances require special positive-pressure venting.

  • Vent connectors must slope upward toward the chimney or vent, be as short and direct as practicable, and be supported.

  • A confined space is one with a volume less than 50 cubic feet per 1,000 Btu/h of total appliance input.

  • Combustion air openings must be permanent, unobstructed, and located one within 12 inches of the top and one within 12 inches of the bottom of the enclosure.

  • Indoor combustion air through two openings requires at least 1 square inch free area per 1,000 Btu/h input, with a minimum of 100 square inches per opening.

  • Outdoor combustion air through two openings requires at least 1 square inch free area per 4,000 Btu/h input; vertical ducts use 1 per 4,000 and horizontal ducts use 1 per 2,000.