ICC M1 flashcards
ICC M1 · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Permit required
- A permit must be obtained before installing, altering, replacing, or repairing a mechanical system; ordinary repairs that do not affect capacity or safety are exempt.
- Concealed work inspection
- Ducts, piping, vents, and other mechanical work that will be concealed must be inspected and approved by the code official before being covered.
- Listed and labeled
- Equipment or materials must be tested by an approved agency, included in a published list, and bear the agency's label; installation must follow the listing and manufacturer instructions.
- Stop-work order
- The code official may issue a written stop-work order for work done without a permit or contrary to the code; work must stop until the order is resolved.
- Approved
- A material, appliance, or method accepted by the code official as meeting the code, usually because it is listed, labeled, or otherwise shown to be suitable.
- Occupiable space
- An enclosed space intended for human occupancy, excluding spaces such as closets, storage rooms, parking garages, and crawl spaces that are not normally occupied.
- Plenum
- A space used for air distribution that is part of a heating, ventilating, or air-conditioning system; plenums have restrictions on combustible materials and stored items.
- Combustion air
- Air supplied to a fuel-burning appliance for combustion and draft; it must be provided from indoors, outdoors, or a combination in the required quantity.
- Dwelling unit
- A single housekeeping unit providing complete independent living facilities, including permanent provisions for living, sleeping, eating, cooking, and sanitation.
- Garage ignition source
- In a private garage, ignition sources of heating appliances must be elevated at least 18 inches above the floor unless the appliance is listed for installation at a lower height.
- Clearance to combustibles
- The minimum distance between heat-producing equipment and combustible material, as specified by the listing, label, or code; it may be reduced only with approved protection.
- Natural ventilation openings
- Natural ventilation requires operable openings to the outdoors with a minimum openable area of 4 percent of the floor area of the space being ventilated.
- Mechanical ventilation rate
- The minimum outdoor airflow for an occupancy is determined from code tables using occupant density and floor area, then supplied continuously during occupied periods.
- Appliance service access
- Heating appliances must be accessible for inspection, service, repair, and replacement; access openings and working space must allow removal of the largest component.
- Primary condensate drain
- A condensate drain from air-conditioning equipment must be at least 3/4 inch nominal size and slope at least 1/8 inch per foot toward an approved disposal point.
- Secondary condensate pan
- A secondary drain pan is required where condensate overflow could cause damage; it must be watertight, at least 1.5 inches deep, and drain to an approved location.
- Condensate trap
- A condensate trap prevents air from being drawn through the drain line; it must be installed per manufacturer instructions and have a depth sufficient to overcome the fan pressure.
- Outdoor condenser clearance
- Outdoor air-conditioning condensing units need clearance per the manufacturer's instructions so discharge air is not recirculated and service access is maintained.
- Refrigerant piping protection
- Refrigerant lines must be supported, protected from physical damage, and installed with approved fittings and insulation where required to prevent condensation or energy loss.
- A1 refrigerant
- A refrigerant classification indicating lower toxicity and no flame propagation; it is the least hazardous group under the standard safety classification.
- Machinery room
- A room used to house refrigeration equipment that must meet special construction, ventilation, detection, and access requirements when refrigerant quantities exceed code thresholds.
- Refrigerant detector
- A device installed in a machinery room or occupied space to sense refrigerant concentration and activate alarm or ventilation before the concentration becomes hazardous.
- Relief device discharge
- Pressure-relief devices on refrigeration systems must discharge to a safe outdoor location away from windows, doors, and air intakes, and must not discharge into the occupied space.
- Duct sealing
- Duct joints, seams, and connections must be sealed with approved materials to prevent air leakage; sealing must meet the required seal class for the system.
- Return air prohibition
- Return air cannot be taken from bathrooms, kitchens, garages, closets, mechanical rooms, or unconditioned attics because of contaminants, moisture, or fire risk.
- Flexible duct installation
- Flexible air ducts must be installed fully extended, supported per the manufacturer, and with bends not sharper than the listing allows to maintain airflow.
- Fire damper
- A listed device installed where a duct penetrates a fire-resistance-rated assembly to close automatically and prevent fire spread through the duct opening.
- Duct support spacing
- Horizontal metal ducts must be supported at intervals allowed by the duct construction standard, and supports must be independent of the duct joints and connections.
- Chimney height rule
- A chimney must extend at least 3 feet above the highest point where it passes through the roof and at least 2 feet above any building within 10 feet.
- Combustion air openings
- Confined spaces require two permanent openings, one within 12 inches of the top and one within 12 inches of the bottom, sized by the appliance input and air source.
- Indoor combustion air
- When combustion air comes from indoors through two openings, each opening must have at least 1 square inch of free area per 1,000 Btu/h input, with a minimum of 100 square inches.
- Outdoor combustion air
- When combustion air is taken directly from outdoors through two openings, each opening must have at least 1 square inch free area per 4,000 Btu/h total input.