ICC Soils Inspector EC study materials
ICC Soils Inspector EC study resources

ICC Soils Inspector EC cheat sheet

ICC Soils Inspector EC · Keep the key ideas within reach.

Quick reference

Site and Soil Evaluation

  • Site evaluation includes reviewing site plans, conducting a site visit, and documenting soil and site conditions that affect construction and stormwater management.

  • Soil borings or test pits must extend to a depth sufficient to evaluate the limiting layer, typically at least 5 feet below the proposed grade or to a restrictive layer.

  • The seasonal high water table is indicated by redoximorphic features (mottles) and must be determined to establish separation to the bottom of the infiltration system.

  • Slope is measured as vertical rise over horizontal run; slopes steeper than 15% often require special design or are prohibited for infiltration practices.

  • Depth to bedrock or impermeable layer must be verified; a minimum separation of 2 feet is commonly required between the bottom of an infiltration practice and bedrock.

  • Soil permeability is estimated from soil texture and structure; a percolation test or infiltration test may be required to confirm design rates.

  • Setbacks from property lines, wells, and foundations must be checked against local ordinances during site evaluation.

  • Documentation of site evaluation includes soil profile descriptions, photographs, and a site plan showing test pit locations and elevations.

Quick reference

Soil Classification and Identification

  • Soil texture is determined by the relative proportions of sand, silt, and clay using the USDA textural triangle.

  • The Unified Soil Classification System (USCS) uses group symbols such as GW, SP, CL, and CH based on grain size distribution, plasticity, and organic content.

  • Atterberg limits (liquid limit, plastic limit, plasticity index) define the plastic behavior of fine-grained soils; PI = LL - PL.

  • Soil color, especially mottling, indicates drainage conditions; gray or bluish-gray colors with redoximorphic features suggest prolonged saturation.

  • Soil structure describes the arrangement of soil particles into aggregates (e.g., granular, blocky, prismatic) and affects permeability and root penetration.

  • The AASHTO soil classification system groups soils into A-1 through A-8 based on particle size, plasticity, and group index for highway subgrade evaluation.

  • Field identification of soil includes the ribbon test for clay content, the dilatancy test for silt, and the dry strength test.

  • Organic soils (peat, muck) are highly compressible and unsuitable for structural fill; they are identified by dark color, low density, and organic odor.

Quick reference

Soil Compaction and Field Testing

  • Standard Proctor (ASTM D698) uses a 5.5-lb hammer dropped 12 inches in 3 layers; Modified Proctor (ASTM D1557) uses a 10-lb hammer dropped 18 inches in 5 layers.

  • Maximum dry density and optimum moisture content are determined from a compaction curve; field density must be at least 95% of maximum dry density for most fills.

  • Field density testing methods include the sand cone (ASTM D1556), rubber balloon (ASTM D2167), and nuclear gauge (ASTM D6938).

  • The sand cone method requires calibrating the sand bulk density and determining the volume of the test hole.

  • Nuclear gauge testing measures wet density and moisture content; it must be calibrated and operated by a trained technician with proper licensing.

  • Compaction specifications often require a certain percentage of maximum dry density (e.g., 95%) and a moisture content within ±2% of optimum.

  • Test frequency is typically one test per lift per specified area (e.g., every 2,500 square feet) or as directed by the geotechnical engineer.

  • Acceptance criteria for compaction are based on the specified relative compaction and moisture range; failing tests require rework and retesting.

Quick reference

Code Administration

  • The inspector must verify that all required permits are obtained before construction begins and that the approved plans are on site.

  • Code administration includes maintaining records of inspections, test results, and correspondence for each project.

  • Stop-work orders may be issued when work is proceeding without a permit or when violations pose a threat to public safety.

  • Inspectors have the authority to enter premises at reasonable times to inspect and to require correction of code violations.

  • Appeals of inspection decisions are typically heard by a local board of appeals within a specified timeframe.

  • The code official may require special inspections by a qualified third party for certain elements (e.g., soil compaction, foundation excavation).

  • Penalties for code violations may include fines, revocation of permits, or legal action; the inspector documents violations and follows up.

  • Code administration requires knowledge of local amendments and the adopted edition of the International Code Council (ICC) family of codes.

Quick reference

Inspection and Reporting

  • Inspection reports must include date, time, project identification, inspector name, weather conditions, and specific observations with locations.

  • Photographs should be dated and referenced in the report to document conditions such as soil strata, compaction equipment, and test locations.

  • Nonconformance reports must clearly state the code or specification requirement, the observed condition, and the required corrective action.

  • Inspectors should verify that materials (e.g., backfill, geotextile) meet approved submittals before installation.

  • Field tests must be recorded with test method, location, results, and pass/fail determination; retests are required for failed tests.

  • Daily reports should note any deviations from approved plans and whether they were approved by the designer or code official.

  • Final inspection reports summarize all inspections, test results, and confirm that the work complies with the approved plans and code.

  • Reports must be retained for the period specified by the jurisdiction and made available for review upon request.