Authorized Gas Tester (AGT) flashcards
Authorized Gas Tester (AGT) · Build recall with a focused review session.
33 cards. Read the term and the definition here. The deck at the top of this page is optional.
- LEL and UEL
- The lower and upper explosive limits are the gas concentrations in air, in % v/v, between which the mixture can ignite; outside that range it is too lean or too rich to burn.
- Flash point
- The lowest temperature at which a liquid releases enough vapour to form an ignitable mixture near its surface; liquids below 23 °C are conventionally highly flammable.
- Auto-ignition temperature
- The temperature at which a flammable vapour-air mixture ignites without an external ignition source, so hot surfaces above this value can start a fire.
- Vapour density relative to air
- The ratio of a gas or vapour's molar mass to air (about 29); values above 1 mean it tends to settle in low points, values below 1 mean it rises.
- Olfactory fatigue
- Loss of the sense of smell after exposure to a gas such as hydrogen sulfide; odour is therefore never a valid method of detecting or judging gas concentration.
- Vapour pressure
- The pressure exerted by a vapour above its liquid; it rises with temperature, so warming a liquid can move its vapour concentration into the flammable range.
- Permit to work
- A formal written authorization for a defined task, location and time; it becomes invalid when conditions change, the validity period expires, or the task or personnel differ.
- Authorized gas tester
- The competent person who tests the atmosphere, interprets the readings against acceptance criteria, and records the results; they are accountable for the validity of those readings.
- Stand-by person duties
- The attendant remains outside the space, maintains communication, accounts for entrants, and initiates rescue; they do not enter unless trained, equipped and authorized.
- Entry supervisor authority
- The person who authorizes entry, issues and cancels the permit, confirms controls are in place, and has authority to stop work when conditions change.
- Isolation before entry
- Blanking, spading, disconnecting or locking off all lines and energy sources; a closed valve alone is not isolation and does not protect entrants.
- Hierarchy of control
- Controls ranked from eliminate and substitute, through engineering (isolation, ventilation), to administrative (permit, procedure), with PPE as the last line of defence.
- Ventilation as a control
- Forced air dilution lowers gas concentration but does not remove the source; continuous monitoring is still required because emission can continue during occupancy.
- Permit cancellation
- A positive act confirming all personnel have exited, the space is secured, and the permit is closed and retained for records; it is not simply letting the permit expire.
- Catalytic bead sensor
- A flammable gas sensor that measures heat of combustion on a heated bead; it reads in % LEL, needs oxygen, and is poisoned by silicones, lead and sulfides.
- Infrared sensor
- A gas sensor measuring light absorption at a characteristic wavelength; it is specific to a gas group, needs no oxygen, and resists poisoning but can be blinded by dirt or condensation.
- Electrochemical sensor
- A toxic gas or oxygen sensor generating a current proportional to concentration; it has a limited life, is temperature-sensitive, and can show cross-sensitivity to other gases.
- Photoionization detector
- A total VOC instrument using a UV lamp; the reading depends on the compound's ionization energy and the lamp energy, so a response factor is needed to interpret it.
- Response factor
- A correction applied when an instrument calibrated on one gas (usually methane) is used to measure another gas, because sensor sensitivity differs between gases.
- Bump test
- A brief exposure to gas above the alarm set point confirming the sensor responds and the alarm operates; it does not adjust the reading and is not a calibration.
- Calibration
- Adjusting the instrument reading to match a certified gas standard of known concentration, with the result recorded; it establishes accuracy, unlike a bump test.
- Zero setting
- Setting the instrument baseline in clean air or with zero gas; setting zero in a contaminated atmosphere biases every subsequent reading taken with that instrument.
- Calibration gas validity
- Certified gas must be within its expiry date, matched to the sensor's target gas, and supplied through leak-free tubing; a depleted cylinder can give a false pass.
- Multi-level sampling
- Testing at top, middle and bottom of the space because gases stratify by relative density; a single point sample can miss a pocket of heavier or lighter gas.
- Test order: oxygen first
- Oxygen is tested before flammables because a catalytic LEL sensor's reading depends on oxygen; an oxygen-deficient sample can give a falsely low reading.
- Typical entry acceptance criteria
- Commonly oxygen 19.5-23.5%, flammable gas below 10% LEL, and toxics below the occupational exposure limit, as set by the site procedure and applicable standard.
- Continuous monitoring
- Monitoring during occupancy with alarms set at acceptance thresholds; a pre-entry test is valid only for the conditions at the time it was taken.
- Hot work permit
- A separate authorization for welding, cutting, grinding or any spark or flame source; where a confined space is also involved, both permits must be valid and cross-referenced.
- Hot work alarm threshold
- A commonly used stop-work threshold is 10% LEL; if the reading reaches it, stop work, withdraw, ventilate and re-test before resuming.
- Oxygen deficiency threshold
- Generally below 19.5% oxygen by volume; judgment and coordination fail before the victim is aware, and below 10% consciousness is lost rapidly.
- Oxygen enrichment threshold
- Generally above 23.5% oxygen by volume; materials burn vigorously and a spark can cause a serious fire, so the source must be found and isolated.
- Rescue plan requirement
- A space-specific, rehearsed plan with equipment at the entry point and a trained team available before entry; a generic untested plan is not adequate.
- Attendant rescue restriction
- The attendant must not enter to rescue an unconscious entrant without breathing apparatus and training; most confined space fatalities involve would-be rescuers.