Commissioning a Stove Flue in a Thatched Property
You are installing a solid fuel stove in a single-storey cottage with a thatched roof. The existing masonry chimney passes through the thatch and terminates with a pot. The stove is to be fitted into an existing fireplace opening with a register plate and a flexible liner. The customer wants the highest heat output possible and asks you to remove the damper and leave the liner uninsulated to save cost. The chimney is on the leeward side of the roof and the thatch is within the required distance of the chimney. You are responsible for commissioning and handover.
1. Identify the safety issues with the customer's requests and state what you would insist on.
Read the worked answer
Removing the damper and leaving the liner uninsulated are both unsafe or non-compliant in this situation:
- Thatch fire risk - a chimney passing through thatch must be at the correct distance and the thatch protected; an uninsulated liner raises flue gas temperatures and heat transfer to the thatch, increasing fire risk. Insulation of the liner is important for performance and safety.
- Damper removal - the damper helps control combustion and draught; removing it removes a control and can allow excessive heat and poor combustion control.
- Chimney distance to thatch - must comply with the required separation; if the chimney is within the required distance, additional protection is needed and the installation must be assessed by a competent person.
- Liner suitability - a flexible liner must be correctly sized, insulated where required, and suitable for solid fuel.
Insist on: an insulated liner of correct size and grade, retention of combustion control, correct register plate and sealing, and compliance with the required chimney/thatch separation and any protection measures. Do not proceed if these cannot be met.
2. Describe the commissioning and handover steps you would carry out.
Read the worked answer
- Visual inspection of the flue route, liner, register plate, seals and terminal.
- Smoke test to confirm the flue draws and there is no leakage into the room.
- Flue draught measurement and comparison with the appliance manufacturer's requirements.
- Combustion/CO check where applicable and confirmation that no smoke or CO spills into the room.
- Check ventilation for combustion air is adequate and unobstructed.
- Check clearances to combustibles and that the hearth and fireplace opening are suitable.
- Operate the appliance through its range and confirm controls work.
- Handover - explain fuel, burning-in, control use, sweeping frequency, thatch-specific precautions, and provide the manufacturer's instructions and a record of commissioning. Advise on chimney sweeping and any thatch insurance requirements.