OFTEC Solid Fuel study materials
OFTEC Solid Fuel study resources

OFTEC Solid Fuel cheat sheet

OFTEC Solid Fuel · Keep the key ideas within reach.

Quick reference

Oil Heating Installation and Maintenance

  • Complete combustion of kerosene requires roughly 12.5 kg of air per kg of fuel; CO2 in flue gas near 12% indicates good excess-air control.

  • Smoke number is read against the pump's reference scale: 0-1 is clean, 2 acceptable, 3+ indicates poor atomisation or wrong air setting.

  • Nozzle flow rate varies with pressure by the square-root law: doubling pressure multiplies flow by about 1.41.

  • Standard nozzle rating pressure is 100 psi (7 bar); flow markings (e.g. 0.60) are US gallons per hour at that pressure.

  • Flue gas temperature should typically exceed boiler return temperature by 20-40 C for a condensing boiler to be in condensing mode.

  • Oil line vacuum should not exceed about 0.4 bar (roughly 12 in Hg); higher vacuum signals a blocked filter, kinked line or faulty foot valve.

  • Fire-valve and photocell (cad cell) resistance: a clean flame gives low resistance (typically under 1-2 kOhm); high resistance means weak flame or dirty cell.

  • Tigerloop/one-pipe lift systems are used where the tank is below the burner; two-pipe gravity systems are used where the tank is above the burner.

Quick reference

Solid Fuel Heating Installation and Maintenance

  • Solid fuel appliances require a permanent, unobstructed combustion air supply; a ventilator sized to the appliance's rated input is mandatory.

  • Chimney draught is driven by temperature difference: hotter flue gases give more draught, so a cold flue is a common cause of poor performance.

  • A flue serving a solid fuel appliance should terminate above the roof line and clear adjacent openings in accordance with building regulations.

  • Wood fuel moisture content should be around 20% or lower; wet wood causes tar/creosote deposition and reduced net efficiency.

  • Anthracite and other smokeless fuels are required in smoke control areas; bituminous coal is generally prohibited there.

  • A gravity-fed solid fuel system must include an open vent and a cold feed; a closed, unvented arrangement on a solid fuel boiler is unsafe.

  • Regular servicing includes sweeping the flue, checking baffles, seals, door gaskets and the draught stabiliser.

  • Over-firing (excessive primary air) shortens appliance life; under-firing causes incomplete combustion and soot.

Quick reference

Electrical Work Associated with Heating Equipment

  • Final circuits in domestic premises are protected by 30 mA RCDs; a 6 A MCB typically protects a 1.0-1.5 mm2 lighting/control circuit.

  • Cable current-carrying capacity must be derated for grouping, ambient temperature and thermal insulation (BS 7671 factors).

  • A boiler's switched live (SL) terminal is fed from the room/programmer controls; permanent live (PL) provides power for pump overrun and frost protection.

  • Earth loop impedance must be low enough for the protective device to disconnect within the required time at the stated fault current.

  • SELV controls (e.g. 24 V or 0-10 V) must be kept separate from mains wiring; separation barriers and correct cable colours apply.

  • Functional switching and isolation: each appliance needs a means of isolation, and a double-pole switch is used for maintenance isolation.

  • Motorised valves are typically 3-port (mid-position) or 2-port (zone); a 3-port valve has a mid-position that supplies both heating and hot water.

  • Bonding of metallic pipework is required where it is an extraneous conductive part; supplementary bonding may be needed in bathrooms.

Quick reference

Renewable Heating Technologies

  • Heat pump COP = heat output (kW) / electrical input (kW); seasonal performance factor (SPF) is the same ratio over a whole season.

  • Carnot efficiency sets the theoretical maximum COP: COP_max = T_hot / (T_hot - T_cold) with temperatures in kelvin.

  • Lower flow temperatures (e.g. 35-45 C) improve heat pump COP; underfloor heating suits this better than high-temperature radiators.

  • A heat pump's heat output must be sized to the building's heat loss at design external temperature, not to the existing boiler rating.

  • Ground-source collectors need adequate ground area; boreholes are used where land is limited, and loop length depends on ground thermal conductivity.

  • Solar thermal yield depends on collector area, orientation and tilt; a south-facing tilt of about 30-45 degrees in the UK is typical.

  • Biomass boilers require fuel storage, delivery access and flue arrangements; efficiency is rated on a gross or net calorific value basis.

  • Thermal stores decouple heat generation from demand and are often required with heat pumps and biomass to buffer output.