- RGII registration requirement
- Gas work in Ireland must be carried out by an installer registered with the Register of Gas Installers of Ireland holding the correct scope, including non-domestic natural gas or LPG categories.
- I.S. 820 scope
- The Irish standard for non-domestic gas installations, covering design, installation, commissioning, testing and documentation for commercial and industrial gas systems.
- Gas Safety Act 2012
- Irish legislation establishing the regulatory framework for gas safety, including the registration of gas installers and enforcement powers relating to gas works.
- Warning notice purpose
- A written notice attached where an immediate danger exists, stating the defect and action taken, with the supply isolated and the responsible person and RGII informed.
- Natural gas relative density
- Approximately 0.6, so natural gas is lighter than air, rises, and accumulates at high level, driving high-level ventilation and detector placement.
- LPG vapour relative density
- Approximately 1.5 to 2.0, so LPG vapour is heavier than air and collects in low areas, pits, ducts and basements, requiring low-level ventilation and detection.
- Stoichiometric air requirement
- The exact air volume needed for complete combustion: about 9.5 m³ air per m³ methane and about 23.8 m³ per m³ propane vapour.
- Flammable limits of methane
- Methane is flammable in air at roughly 5% to 15% by volume; LPG has a wider, lower range, increasing explosion risk in confined spaces.
- Equivalent pipe length method
- Sizing method adding measured pipe run to equivalent lengths of fittings, then selecting diameter from gas rate and allowable pressure drop tables.
- Low-pressure design pressure drop
- For low-pressure natural gas, pipework is commonly sized to a total pressure drop of about 1 mbar from meter outlet to appliance inlet.
- Gas isolation valve location
- An accessible isolation valve is required at the meter or regulator outlet and at each appliance or zone, with emergency controls clearly marked.
- Medium-pressure regime
- A supply pressure between about 75 mbar and 2 bar, often used on non-domestic sites with a site regulator, requiring different design and testing rules.
- Type C appliance flueing
- A room-sealed, balanced-flue appliance drawing combustion air from outside and discharging flue products outside, so room combustion-air openings are generally not needed.
- Safety shut-off valve function
- A valve that closes automatically on flame failure or unsafe condition, proved closed before light-up and on shutdown, preventing unburnt gas entering the combustion chamber.
- Burner pre-purge purpose
- A period of forced air flow through the combustion chamber before ignition to remove any accumulated flammable gas and prevent explosion on light-up.
- Appliance data plate values
- Declared gas family, nominal heat input, gas rate, burner pressure and injector size that commissioning must match and record.
- Combustion air versus dilution air
- Two separate ventilation requirements: air for burning the gas, and air to dilute flue products for open-flue appliances; the larger governs opening size.
- Louvre free area
- The actual unobstructed area of a ventilation opening after allowing for grille or louvre blockage, which must be used in ventilation calculations.
- Ventilation interlock
- A proven airflow device that prevents burner firing unless mechanical ventilation is running, shutting the burner down safely if airflow fails.
- LPG basement ventilation
- Below-ground rooms using LPG require low-level ventilation and mechanical extract at low level, interlocked with gas detection and firing controls.
- CO/CO₂ ratio
- An indicator of incomplete combustion calculated from flue gas analysis; around 0.004 or below is normal for natural gas, with higher values requiring investigation.
- Flue draught measurement
- Measurement of the pressure pulling flue products from the appliance, taken with the appliance and other appliances running under worst-case conditions.
- Spillage test
- A test confirming open-flue appliances clear combustion products under worst-case conditions, such as closed doors and windows with extract fans running.
- Excess air from O₂ reading
- Flue oxygen of about 3% to 6% for natural gas indicates correct excess air; very low O₂ risks carbon monoxide, very high O₂ wastes heat.
- Tightness test medium
- Air or inert gas is used for strength and tightness testing; oxygen and flammable gas must never be used as the test medium.
- Purging pipework
- Removing air before gas is introduced, or removing gas before opening pipework, with calculated purge volumes discharged to a safe, ignition-free location.
- Commissioning sequence
- Tightness test, purge, set pressures and gas rate, combustion analysis, confirm ventilation and flueing, test safety controls, then record all results.
- Decommissioning steps
- Isolate and lock off supply, purge the section, cap or plug pipework, make appliances safe, label the installation, and update records and the client.
- LPG detector placement
- Because LPG vapour is heavier than air, detectors are mounted low, typically 150 to 300 mm above floor level near potential leak points.
- Gas detection alarm stages
- Typically a pre-alarm near 10% of the lower flammable limit and an alarm near 20%, with the alarm stage isolating gas and shutting down burners.
- Gas escape emergency actions
- Eliminate ignition sources, isolate at the emergency control valve, ventilate, evacuate, and call the gas network emergency service and fire service.
- Non-domestic handover pack
- A record containing pipework details, tightness and purge results, appliance settings, combustion readings, ventilation and flueing details, and certificates.