Ohm's law
For a resistive circuit, voltage equals current multiplied by resistance (V = I × R). This relationship allows any one quantity to be calculated when the other two are known.
Power formula
Electrical power equals voltage multiplied by current (P = V × I), and can also be written as I²R or V²/R. Power is measured in watts.
Three-phase power
For a balanced three-phase load, power equals √3 times line voltage times line current times power factor. The √3 factor arises from the 120-degree phase displacement.
Star connection
In a star-connected three-phase system, line voltage is √3 times phase voltage and line current equals phase current. A 400 V line supply gives 230 V per phase.
Capacitive reactance
Capacitive reactance equals 1 divided by (2π times frequency times capacitance). It falls as frequency rises, so a capacitor opposes low-frequency signals more than high-frequency ones.
Transformer ratio
The voltage ratio equals the turns ratio, and current ratio is the inverse. An ideal transformer conserves apparent power, so a voltage step-down produces a current step-up.
Insulation resistance test
Apply 500 V DC to a de-energised circuit with loads disconnected. A 230 V final circuit must read at least 1 MΩ to confirm the insulation is sound.
Earth loop impedance
Zs is the total resistance of the earth fault path, measured live. It must be low enough for the protective device to disconnect within the required time.
RCD trip test
A 30 mA RCD must trip within 300 ms at rated residual current and must not trip at 15 mA. The test button is a mechanical check only.
Ring continuity test
End-to-end resistance readings r1, rn and r2 are taken, then cross-connected. The highest socket readings should be about (r1+rn)/4 and (r1+r2)/4.
Lock-off procedure
Isolate the supply, prove dead with a voltage indicator checked on a known live source, apply a lock and warning notice, and keep the key with the worker.
Periodic inspection
An electrical installation condition report records the extent of sampling and the interval to the next inspection, which depends on the installation type and use.
Design current Ib
Ib is the current the circuit is expected to carry in normal use. The protective device rating In must be at least Ib, and cable capacity Iz at least In.
Voltage drop limits
Voltage drop must not exceed 3% of nominal voltage for lighting and 5% for other circuits on a public low-voltage supply. Calculate mV/A/m × Ib × length ÷ 1000.
Correction factors
Cable current-carrying capacity is adjusted by factors for ambient temperature (Ca), grouping (Cg), thermal insulation (Ci) and BS 3036 fuses (Cf).
Ring final circuit
A 32 A protected ring uses 2.5 mm² line and neutral conductors with a 1.5 mm² circuit protective conductor. The ring shares load between two paths.
TN-C-S earthing
In a TN-C-S (PME) system, the neutral and earth are combined in the supply and separated at the origin. The earth path relies on the supply neutral.
TT earthing system
A TT system uses a local earth electrode rather than a supply earth. Earth fault loop impedance is high, so a 30 mA RCD is normally required.
Segregation of circuits
Band I (SELV), band II (low voltage) and band III (telecoms) circuits are kept apart by separate compartments, barriers or spacing to prevent contact and interference.
BS 7671 status
The IET Wiring Regulations is the UK national standard for electrical installations. It is not a statute, but compliance is used as evidence of reasonable care.
Disconnection times
For a 230 V final circuit not exceeding 32 A, automatic disconnection must occur within 0.4 s. Distribution circuits are permitted 5 s.
Basic protection
Basic protection prevents contact with live parts in normal conditions, using insulation, barriers or enclosures. Fault protection deals with contact under fault conditions.
Bathroom zones
Zones 0, 1 and 2 define proximity to a bath or shower and restrict the equipment permitted in each. Supplementary bonding and 30 mA RCD protection are typically required.
Minor works certificate
A minor works certificate covers additions or alterations that do not include a new circuit. New circuits or consumer unit replacements need an electrical installation certificate.
Silicon diode drop
A forward-biased silicon diode conducts above about 0.7 V and blocks in reverse. The reverse breakdown voltage of the device must not be exceeded.
Bridge rectifier
A full-wave bridge rectifier produces two output pulses per input cycle, so ripple frequency is twice the supply frequency. A half-wave rectifier produces one.
Zener diode
A Zener diode operates in reverse breakdown to give a stable reference voltage. A series resistor limits the current through the Zener.
Thyristor latching
A thyristor turns on when a gate pulse arrives with the anode positive. It turns off only when anode current falls below the holding current.
PLC scan cycle
A PLC reads inputs, executes the program and updates outputs in a repeating scan. The scan time sets the response of the control system.
PV cell voltage
A photovoltaic cell produces about 0.5 to 0.6 V in open circuit. Cells in series raise voltage; cells in parallel raise current. Arrays are rated in kWp.
Anti-islanding
A grid-tied inverter must disconnect automatically when the grid supply is lost. This prevents the inverter from energising the network while workers expect it dead.
MPPT
Maximum power point tracking adjusts the array operating voltage to extract maximum power as irradiance and temperature change throughout the day.
Wind power cube law
Wind turbine power is proportional to the cube of wind speed and to the swept area. A small rise in wind speed produces a large rise in power.