SOLAS Plumbing study materials
SOLAS Plumbing study resources

SOLAS Plumbing cheat sheet

SOLAS Plumbing · Keep the key ideas within reach.

Quick reference

Health, Safety and Welfare on Plumbing Sites

  • Hierarchy of control, most to least effective: eliminate, substitute, engineering controls, administrative controls, PPE. PPE is the last line of defence and never a substitute for removing the hazard.

  • COSHH requires a current safety data sheet and a documented risk assessment before any hazardous substance (flux, solvent cement, descaler, lead solder, two-pack sealant) is used or stored on site.

  • Confined-space entry (tanks, pits, sewers, plant rooms with restricted egress) requires a permit, atmospheric testing for oxygen (19.5-23.5% v/v), flammable and toxic gas, a rescue plan and a top-man.

  • Manual handling assessment uses the guideline figures: load close to the body, avoid twisting, keep lifts below shoulder height, and treat loads over 25 kg as requiring a team lift or mechanical aid.

  • Working at height hierarchy: avoid work at height, prevent falls using a suitable platform, then mitigate the distance and consequences of a fall. Ladders are for low-risk, short-duration work only.

  • Hot work (soldering, brazing, grinding) requires a hot-work permit, a fire watch during and for at least 60 minutes after work, and removal of combustibles within the immediate area.

  • Electrical safety on site: 110 V centre-tapped-to-earth reduced low voltage for portable tools, RCD protection at 30 mA, and PAT testing records available for inspection.

  • Legionella risk from aerosols means showers, cooling towers, spa pools and stagnant pipework are assessed under the site's water safety plan; report any positive result immediately.

Quick reference

Plumbing Science

  • Pressure at a depth: p = rho x g x h. Water at 1 m depth gives about 9.81 kPa, so roughly 10 m head equals 1 bar (100 kPa).

  • Flow rate through an orifice or terminal fitting: Q = v x A. Doubling the pipe diameter quadruples the cross-sectional area and so quadruples flow at the same velocity.

  • Bernoulli's equation: p1 + 0.5 rho v1^2 + rho g h1 = p2 + 0.5 rho v2^2 + rho g h2, plus friction losses. Higher velocity means lower static pressure at that point.

  • Darcy-Weisbach head loss: hf = f (L/D)(v^2/2g). Friction loss rises with length and with the square of velocity, so oversized flow in undersized pipe is the common fault.

  • Thermal expansion of water: about 4% volume increase from 10 to 100 degrees C; sealed systems need an expansion vessel or a relief valve to accommodate it.

  • Specific heat capacity of water is 4.18 kJ/kg.K. Heating 1 kg of water by 1 K takes 4.18 kJ, so energy = mass x 4.18 x temperature rise.

  • Sensible heat and latent heat: raising water from 0 to 100 degrees C takes 419 kJ/kg, and changing 100 degree water to steam at the same temperature takes a further 2257 kJ/kg.

  • Water hammer is caused by sudden velocity change; mitigation is slow-closing valves, correctly sized pipe, air vessels or surge arrestors, and adequate pipe clipping.

Quick reference

Materials and Pipework Systems

  • Copper tube is graded by wall thickness: R250 (light), R220 (medium), R200 (heavy). Table X (R250) suits surface-run domestic work; buried or high-pressure work needs heavier grades.

  • Copper to copper joints are made with lead-free solder and a flux matched to the filler; a nitrogen purge prevents internal oxide scale on medical and high-purity work.

  • Plastic pipe pressure ratings fall with temperature. A pipe rated PN10 at 20 degrees C is derated at 60-70 degrees C, so check the manufacturer's pressure-temperature table before use on hot water.

  • PEX and PEX-Al-PEX are joined with press or compression fittings specific to the system; mixing barrier and non-barrier pipe in a heating circuit causes oxygen ingress and corrosion.

  • Push-fit plastic systems rely on an O-ring seal and a grab ring; the pipe must be cut square, deburred, marked to insertion depth and secured with the correct insert for the pipe type.

  • Galvanised steel must not follow copper in the direction of flow, because copper ions accelerate galvanic corrosion of the zinc; use a dielectric union at any transition.

  • Dissimilar metals need isolation: brass and copper are close on the galvanic series and acceptable, but steel with copper or stainless with carbon steel needs a dielectric coupling.

  • Pipe support spacing depends on material and temperature: plastic pipe needs more clips than copper because its stiffness falls and expansion is greater; follow the manufacturer's spacing table.

Quick reference

Water Supply, Storage and Distribution

  • Category 5 fluid risk (faecal, animal or human waste) requires an air gap (type AA or AB); reduced-pressure zone valves (type BA) are the minimum for category 4.

  • Cold water storage cistern sizing: allow at least 100-200 litres per dwelling and 45 litres per occupant per day as a working figure; the cistern must hold a minimum 24-hour supply where the mains can be interrupted.

  • Cistern installation rules: a screened warning pipe, a lid, an insect screen, a raised base, insulation, and a minimum 150 mm air gap between the float-operated valve outlet and the spillover level.

  • The water bylaws/regulations require a minimum 15 mm service pipe for a single dwelling and a maximum length of 30 m for a 15 mm pipe from the communication pipe to the stop valve without a pressure check.

  • Static pressure in a building is set by the height of the highest outlet above the supply; a break tank and booster set are needed when the mains cannot deliver the required pressure and flow.

  • Balanced cold and hot supplies to a mixer tap or shower prevent pressure fluctuation and temperature swing; unbalanced supplies cause the blended temperature to drift.

  • Pipe sizing uses the loading-unit method: each outlet has a loading unit, the total is converted to a design flow, and the pipe is sized so velocity stays below about 1.5 m/s in cold and 1.0 m/s in hot services.

  • Water meters and stop valves must be accessible, and the internal stop valve must be fitted immediately after the rising main enters the building, with a drain cock on the lowest point.

Quick reference

Sanitary Appliances

  • WC flush volumes: 6/4 litre dual flush is the common maximum for new installations; reduced flush must not exceed two-thirds of the full flush.

  • Trap seal depth must be 75 mm for WC pans and 38-75 mm for other appliances; a seal below 38 mm risks sewer gas ingress and above 75 mm risks self-siphoning.

  • A branch discharging into a stack must be within 450 mm of the trap outlet (or the trap must be ventilated) to avoid induced siphonage on the appliance.

  • Washbasin and sink taps are fitted with an air gap or a check valve on any flexible hose connection; a hand-held shower on a flexible hose is a category 5 risk and needs backflow protection.

  • Bath and shower mixers must limit hot water delivery to 48 degrees C at the outlet for domestic baths and 41 degrees C for showers in healthcare and vulnerable settings.

  • Accessible WC compartments require a minimum 800 mm clear transfer space beside the pan, grab rails, and a 480 mm high seat in an accessible/ambulant cubicle.

  • Unvented hot water cylinders and combination boilers must have a temperature and pressure relief valve piped to a safe discharge point, not to a gully inside the building.

  • Sanitary appliance waste pipes must fall at 18-90 mm per metre for 32-50 mm pipe and 22 mm per metre for a 110 mm branch to maintain self-cleansing velocity.

Quick reference

Drainage and Above-Ground Discharge

  • Self-cleansing velocity in drains is about 0.7 m/s at design flow; below this solids settle, above about 3 m/s scour of the pipe wall occurs.

  • Soil and waste stack sizing: a 100 mm stack serves up to about 20 WC pans on a domestic system; a 75 mm stack serves up to 6; a 50 mm stack serves up to 2.

  • Stack ventilation: a vent pipe must rise at least 900 mm above the highest branch and terminate at least 900 mm above any opening window or 3 m horizontally from it.

  • A stub stack is permitted where the stack carries no more than 6 WC pans and the lowest branch is within 6 m of the drain invert; otherwise a full vent is needed.

  • Drain gradients in the regulations: 1 in 40 to 1 in 80 for 100 mm pipe, 1 in 40 to 1 in 110 for 150 mm pipe; flatter than 1 in 110 causes solids deposition.

  • Inspection chambers are required at every change of direction, at junctions of drains, and at intervals of no more than 45 m on a straight run.

  • A gully trap must be fitted with a sealed grating and its seal must be at least 75 mm deep; rainwater and surface water must not discharge into the foul drain.

  • Air admittance valves admit air to balance pressure but do not vent foul air; they must be fitted above the flood level of the highest appliance and be accessible for maintenance.

Quick reference

Heating, Hot Water and Renewable Systems

  • Boiler sizing uses the heat loss of the building, not the radiator count; a room-by-room heat loss calculation is the basis for radiator sizing and flow temperature choice.

  • Radiator output falls as the mean water temperature falls: a radiator rated at 75/65/20 degrees C (delta T 50) delivers about 75% of that output at 55/45/20 (delta T 30).

  • Weather compensation lowers the flow temperature as the outside temperature rises, improving condensing boiler efficiency and reducing cycling; the boiler must condense below about 55 degrees C return.

  • A heat pump needs a low flow temperature (35-45 degrees C) and a well-insulated building; the seasonal performance factor depends on the temperature lift, so oversized emitters matter.

  • Unvented cylinders need a 3 bar pressure reducing valve, a 6 bar expansion relief valve, a 7 bar temperature and pressure relief valve, and an expansion vessel sized to the cylinder volume.

  • Solar thermal and heat pump cylinders need a larger coil or a plate heat exchanger to transfer heat at low flow temperatures; a standard indirect coil is often inadequate.

  • Legionella control in hot water: store at 60 degrees C or above, distribute at 50 degrees C or above, and deliver at the outlet within 1 minute at 55 degrees C (healthcare) or 50 degrees C (other premises).

  • Underfloor heating manifolds need a mixing valve or a separate low-temperature circuit, a flow meter per loop, and actuators controlled by room thermostats or zone valves.

Quick reference

Water Treatment, Legionella Control and Backflow Protection

  • Backflow protection is selected by fluid category: category 1 wholesome water, 2 slight health hazard, 3 moderate, 4 significant, 5 severe. The protection device must match the highest category downstream.

  • Air gap (type AA/AB) is the only protection for category 5. Type BA (reduced pressure zone) suits category 4. Type CA (double check valve) suits category 3. Type EA/EB (single check) suits category 2.

  • Legionella bacteria multiply between 20 and 45 degrees C, with the highest growth around 37 degrees C; above 60 degrees C they die within minutes, and below 20 degrees C they are dormant.

  • A water safety plan or legionella risk assessment is required for every premises with a water system; it must be reviewed at least every 2 years or when the system changes.

  • Sentinel outlets are the nearest and furthest from the supply, plus any low-use outlet; they are the first to be sampled and the first to be flushed during a control programme.

  • Water softeners use ion exchange to swap calcium and magnesium for sodium; they reduce scale but raise sodium content, so softened water must not be used for drinking or infant formula unless a hard-water tap is provided.

  • Chemical dosing for closed heating systems uses inhibitor at the manufacturer's concentration, typically checked by a test kit for pH (8-10), inhibitor level, and chloride; a corrosion coupon or test kit confirms the result.

  • TMV (thermostatic mixing valve) type 3 is used for vulnerable persons and must be fitted with a means of temperature verification and a failsafe to shut off hot water on cold failure.

Quick reference

Installation Practice, Commissioning and Handover

  • Pressure testing of pipework: test at 1.5 times the design pressure or the manufacturer's figure, hold for at least 1 hour for plastic and 30 minutes for metal, with a visible gauge and a recorded result.

  • Flushing and chlorination of new mains and storage: chlorinate to 50 mg/l free chlorine for 1 hour contact, then flush until the residual falls below the wholesome water limit.

  • Commissioning a heating system: fill, vent, cold-flush, dose with inhibitor, set the bypass, balance the radiators to a 10-11 degrees C differential, and record the boiler combustion readings.

  • Handover documentation must include the benchmark/commissioning checklist, as-installed drawings, O&M manuals, guarantee certificates, and the user instructions for controls.

  • Gas work handover requires the benchmark log, a warning notice where a defect is found, and a gas safety record for rented property; only a Gas Safe registered engineer may work on gas.

  • Electrical work on boilers and controls must comply with Part P; minor works and new circuits need certification, and the boiler must be on a fused spur with a 3 A fuse.

  • Pipe insulation thickness is set by the pipe diameter and location; a 15 mm domestic hot pipe needs at least 9 mm in a heated space and 13-25 mm in unheated or cold spaces to avoid condensation and freezing.

  • Labelling of pipework is required for isolation valves, drain cocks, and pipes carrying water for non-potable uses; the label must state the fluid and the hazard.

Quick reference

Maintenance, Fault Diagnosis and Repair

  • A combi boiler losing pressure repeatedly usually has a failed expansion vessel, a leaking pressure relief valve, or a system leak; isolate the boiler to distinguish a vessel fault from a system leak.

  • No hot water from a combi with heating working points to a stuck diverter valve, a faulty flow sensor, or a blocked plate heat exchanger; check the flow switch signal before replacing parts.

  • Radiators cold at the top indicate air, cold at the bottom indicate sludge; a cold radiator at the top with a hot flow pipe suggests a balancing or pump problem.

  • A WC that runs continuously usually has a worn inlet valve washer, a mis-set float, or a faulty fill valve; a WC that leaks at the base has a failed pan connector or a cracked pan.

  • A trap that gurgles or empties indicates induced siphonage or a blocked vent; check the branch distance to the stack and the vent terminal before altering the trap.

  • A water meter turning with all outlets closed indicates a leak on the supply; isolate sections in turn to localise it, and check the ball valve in the cistern first.

  • Frost damage: a frozen pipe must be thawed from the outlet end towards the supply with warm air or a hot pack, never with an open flame, and the pipe must be checked for splits before restoring pressure.

  • A boiler lockout with a fault code should be read against the manufacturer's fault table before resetting; repeated resets without diagnosis can flood the combustion chamber with unburnt gas.