Israel Electrician Licensing Exam flashcards
Israel Electrician Licensing Exam · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's law
- For a resistive circuit, voltage equals current multiplied by resistance (U = I × R). Power equals voltage times current, also I²R or U²/R.
- Three-phase power formula
- For a balanced three-phase load, active power equals √3 times line voltage times line current times power factor. Reactive power uses sine of the phase angle instead.
- Inductive reactance
- Opposition to alternating current from inductance, calculated as two pi times frequency times inductance. It rises with frequency, so higher harmonics see greater impedance.
- Power factor
- Ratio of active power to apparent power, equal to cosine of the phase angle between voltage and current. Low values increase current for the same useful power.
- Kirchhoff's current law
- The algebraic sum of currents entering and leaving any node in a circuit equals zero. It expresses conservation of charge at a junction.
- Design current inequality
- The circuit design current must not exceed the device rating, which must not exceed the cable capacity. This ordering ensures the cable is protected from overload.
- Voltage drop allowance
- Final circuits are commonly limited to about three percent drop, and the whole installation to about five percent from origin. Confirm values in SI 100.
- Adiabatic short-circuit check
- The cable withstands a fault if k squared times cross-section squared is at least the fault current squared times clearing time. k depends on conductor and insulation.
- Protective conductor sizing rule
- The protective conductor matches the phase conductor up to 16 square millimetres, is 16 square millimetres up to 35, and half the phase size above that.
- Cable correction factors
- Tabulated current capacity must be multiplied by factors below one for ambient temperature, grouping, thermal insulation and installation method before comparing with the design current.
- MCB trip types
- Type B trips at three to five times rated current, type C at five to ten, and type D at ten to twenty. The type is chosen to tolerate expected inrush current.
- RCD versus RCBO
- An RCD detects residual current only and needs separate overcurrent protection. An RCBO combines residual current and overcurrent protection in a single device.
- RCD 30 mA protection
- A 30 milliampere residual current device provides additional protection against electric shock and is required for socket circuits and wet locations under SI 100.
- TN-S earthing system
- The supply provides separate neutral and protective conductors all the way from the source. Earth fault current returns through the metallic protective conductor.
- TT system disconnection
- The installation has its own earth electrode independent of the supply neutral. Disconnection relies on an RCD, with electrode resistance not exceeding 50 volts divided by trip current.
- Earth-fault loop impedance
- The total impedance of the fault path. It must be low enough that the protective device trips within the required disconnection time at the nominal voltage.
- Main equipotential bonding
- Connection of incoming metallic water, gas and structural services to the main earthing terminal at the origin, keeping all accessible metal at similar potential.
- Five safety rules
- Disconnect the supply, secure against reconnection, verify absence of voltage, earth and short-circuit, and protect adjacent live parts before beginning work.
- Ventricular fibrillation threshold
- Currents above roughly 30 milliamperes through the body can cause ventricular fibrillation. This is why 30 milliampere RCDs are used for additional protection.
- First aid for electric shock
- Isolate the supply safely, call emergency services, check breathing and pulse, begin CPR if trained, and use an automated external defibrillator if available.
- Lockout tagout
- Each worker applies a personal lock and tag to the isolation point. Only the person who applied a lock removes it, following the documented procedure.
- SI 100 scope
- The Israeli national electrical code governing low-voltage installation requirements, including protection, earthing, cable selection and inspection obligations for electricians.
- SI 900 scope
- The Israeli standard covering electrical installations in residential buildings, setting requirements for dwelling circuits, socket outlets and protective measures.
- Israeli supply characteristics
- Low-voltage supply is 230 volts phase to neutral and 400 volts phase to phase at 50 hertz, with a combined neutral-earth arrangement at the origin.
- Electrician licensing classes
- Israeli law defines licence classes such as practical electrician, electrician and electrical engineer, each permitting different scopes of installation work and supervision.
- Insulation resistance test
- A DC test voltage, typically 500 volts, is applied between conductors and earth. A healthy low-voltage installation reads at least one megohm.
- Continuity testing
- A low-resistance ohmmeter verifies protective conductors and ring circuits. Test leads are nulled first so their resistance does not distort the reading.
- RCD trip time test
- A calibrated tester applies residual current at rated and five times rated sensitivity, recording trip times to confirm the device operates within specified limits.
- Polarity check
- Verification that the line conductor is switched and connected to the correct socket terminal. Reversed polarity is a common and dangerous installation fault.
- Synchronous speed
- The speed of the rotating magnetic field, equal to 120 times frequency divided by the number of poles. A four-pole motor on 50 hertz runs at 1500 rpm.
- Induction motor slip
- The fractional difference between synchronous speed and actual rotor speed. Slip increases with load and is necessary for torque production.
- Star-delta starting
- A starting method that reduces starting current and torque to one third of direct-on-line values. It suits loads that can accelerate with reduced torque.