Israel Electrician Licensing Exam: Earthing, Bonding, and Protection Against Electric Shock

Israel Electrician Licensing Exam · Work through your exam, one topic at a time.

All guide sections

Earthing, Bonding, and Protection Against Electric Shock

Earthing, bonding and protection against electric shock is where the most marks are lost, because the answer depends on the declared earthing system (TN-S, TN-C-S, TT, IT) and on whether faults are cleared by overcurrent devices or by residual current devices.

Core rules

  • Exposed conductive parts are connected to the protective conductor (PE); extraneous conductive parts are connected by main protective bonding to the main earthing terminal. Water, gas, structural steel and lightning protection all terminate at the bonding bar.
  • Automatic disconnection requires Zs ≤ U0/Ia, where Ia is the current that operates the device within the stated time (5×In for a B MCB, 10×In for a C MCB, IΔn for an RCD).
  • The touch-voltage limit is 50 V AC under normal conditions.
  • In TN-C-S the PEN is earthed at the origin and split into PE and N; downstream, PE and N must never be recombined.
  • In TT the installation has its own electrode and RA ≤ 50/IΔn.

Worked example

A 16 A B-curve MCB protects a socket circuit. Ia = 5 × 16 = 80 A, so maximum Zs = 230/80 = 2.88 Ω. A measured Zs of 1.9 Ω confirms disconnection. If the measurement were 3.4 Ω the circuit fails; you must improve the earth path or add a 30 mA RCD, for which RA ≤ 50/0.03 = 1667 Ω.

Traps

  • Assuming an RCD removes the need for a sound earth connection.
  • Losing the PEN and diagnosing it as a simple neutral fault.
  • Using a metallic water pipe as the only earth electrode.
  • Omitting supplementary bonding in bathrooms and around metallic services.