Haryana BSEH Secondary NSQF Power: Generation, Transmission and Distribution Basics

Haryana BSEH Secondary NSQF Power · Work through your exam, one topic at a time.

All guide sections

Generation, Transmission and Distribution Basics

What the domain tests

Generation, Transmission and Distribution Basics tests the path from fuel or renewable source to the consumer, the reason for high-voltage transmission, and the meaning of feeder, distributor, load factor and diversity.

Core rules

  • Generation: thermal, hydro, nuclear, solar and wind produce electrical energy; a generator typically produces at 11–25 kV.
  • Step-up transformers raise voltage for transmission; high voltage reduces current for the same power, cutting I²R losses. Transmission voltages in India include 132, 220, 400 and 765 kV.
  • Distribution steps down through substations to 33/11 kV, then 400/230 V for consumers. Primary distribution feeds distribution transformers; secondary distribution feeds service connections.
  • Load factor = average load / maximum demand. Diversity factor recognises that not all consumers peak at once.
  • A feeder supplies a distribution area; a distributor is tapped along its length for consumer connections.

Worked example

A 100 MW plant runs at 80% load factor for one day. Average load = 100 × 0.8 = 80 MW. Energy = 80 MW × 24 h = 1,920 MWh. If the same power were sent at 220 kV instead of 11 kV, the current would be 20 times lower, so line losses (I²R) would fall dramatically for the same conductor resistance.

Traps

Do not say high voltage reduces power; it reduces current and losses for the same power. Do not call a distribution transformer a generator step-up transformer. Do not calculate energy by multiplying maximum demand by time unless the load is actually at maximum throughout.