Odisha CHSE +2 VOC-ITV Wireman Control Panel flashcards
Odisha CHSE +2 VOC-ITV Wireman Control Panel · Build recall with a focused review session.
33 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's law
- For a resistive circuit, voltage equals current multiplied by resistance (V = I × R). Power can be found as P = V × I = I²R = V²/R.
- Parallel resistance formula
- The reciprocal of total resistance equals the sum of the reciprocals of individual resistances. For two resistors, RT = (R1 × R2)/(R1 + R2).
- RMS value of sine
- The root-mean-square value of a sinusoidal quantity equals the peak value divided by the square root of two, about 0.707 times the peak.
- Power factor
- The cosine of the phase angle between voltage and current, equal to real power divided by apparent power. It is 1.0 for pure resistance and zero for pure reactance.
- Three-phase star relationship
- In a star-connected system the line voltage is √3 times the phase voltage, while the line current equals the phase current. Total power is √3 × VL × IL × cos φ.
- Conductor resistance formula
- Resistance equals resistivity multiplied by length divided by cross-sectional area. Doubling the length doubles resistance; doubling the area halves it.
- PVC versus XLPE insulation
- PVC is thermoplastic with a 70 °C rating and softens on overload. XLPE is thermoset with a 90 °C rating and better short-circuit withstand, so it suits hot locations.
- Conduit fill rule
- The total cross-sectional area of cables in a conduit should not exceed 40 percent of the conduit internal area, allowing heat dissipation and easy drawing of conductors.
- Standard Indian cable sizes
- Common metric conductor sizes are 1.0, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70 and 95 square millimetres. Lighting uses 1.5 and sockets 2.5.
- Crimping versus soldering
- Crimping with a matched lug and tool gives a mechanically and electrically sound joint without heat damage and is preferred in control panels over soldered terminations.
- Bimetallic lug
- A lug made for joining aluminium conductors to copper busbars, preventing galvanic corrosion at the joint. Anti-oxidant compound is applied to aluminium strands before crimping.
- Two-way switch control
- Two two-way switches connected by two strapper wires allow a lamp to be controlled from either of two positions. An intermediate switch extends control to three or more points.
- Indian phase colour code
- Three-phase conductors are red, yellow and blue; neutral is black or blue; earth is green or green-yellow. Single-phase live is red or brown.
- Loop-in lighting wiring
- Live, neutral and earth are looped from ceiling rose to ceiling rose, with the switch drop taken from each rose. Fewer concealed joints make it preferred over joint-box wiring.
- Cable derating factors
- The tabulated current rating is multiplied by correction factors for ambient temperature, grouping of circuits, and installation method to obtain the actual permissible current.
- Voltage drop limit
- Installation design keeps voltage drop within 3 percent on a final sub-circuit and 5 percent from the supply origin to the load, ensuring equipment receives adequate voltage.
- Contactor auxiliary contacts
- Small normally-open and normally-closed contacts mechanically linked to the main contactor, used in control circuits for holding, interlocking and indication at low current.
- MCB trip curves
- B curve trips at 3 to 5 times rated current for resistive loads, C curve at 5 to 10 times for general use, and D curve at 10 to 20 times for motors.
- Thermal overload relay setting
- The relay is set to the motor full-load current. Class 10 suits normal starting, while class 20 or 30 allows the longer starting times of high-inertia loads.
- Emergency stop push button
- A red mushroom-head latching button with normally-closed contacts that removes control power and stays latched until deliberately reset, preventing unexpected restart.
- DOL starter
- Direct-on-line starting applies full line voltage to the motor through a contactor and overload relay. It is simple and cheap but draws six to eight times full-load current.
- Star-delta starting principle
- The motor starts in star, reducing phase voltage to line voltage divided by √3, so starting current and torque fall to one third. It then changes to delta for run.
- No-volt protection
- A contactor drops out when supply fails and does not re-energise on restoration until the start button is pressed again, protecting people from unexpected machine restart.
- Forward-reverse interlocking
- Two contactors controlling opposite rotation are fitted with normally-closed auxiliary contacts in each other's coil circuit, so both can never energise at the same time.
- Variable frequency drive
- A drive varies both frequency and voltage applied to a motor, giving controlled acceleration, speed control and energy saving on variable-torque loads such as fans and pumps.
- Earth pit resistance
- Earthing resistance should not exceed 1 ohm for a substation and is generally kept within 5 ohms for domestic installations. It is measured with an earth tester.
- 30 mA RCD
- A residual current device that trips when earth leakage exceeds 30 milliamperes, protecting people from electric shock. It does not protect against overload or short circuit.
- Safe isolation procedure
- Identify the circuit, isolate and lock off, prove the tester on a live source, test the conductors dead, then re-prove the tester before touching anything.
- Megger insulation test voltage
- Use 500 volts DC for low-voltage circuits and 1000 volts for low-voltage cables and motors. A reading of at least 1 megohm is normally acceptable.
- Clamp meter principle
- The instrument measures current from the magnetic field around a single conductor without breaking the circuit. Clamping two conductors together cancels the reading.
- IS 732 and IS 3043
- IS 732 is the code of practice for electrical wiring installations covering design, protection and testing. IS 3043 is the code of practice for earthing.
- Permissible supply voltage variation
- Indian regulations permit low-voltage supply variation of plus or minus 6 percent, with frequency held at 50 hertz within plus or minus 3 percent.
- Panel estimation line items
- A panel estimate lists enclosure, busbars, switchgear, contactors, relays, wiring, ferrules, terminal blocks, labels, painting and testing, then adds labour, overheads, profit and GST.