- Tonn of refrigeration
- A unit of cooling capacity equal to 3.517 kW or 210 kJ/min, defined as the heat absorbed to melt one short ton (907 kg) of ice in 24 hours.
- COP of refrigerator
- Coefficient of performance = refrigerating effect divided by compressor work input. For a Carnot cycle, COP = T_L / (T_H − T_L) with temperatures in kelvin.
- Relative humidity
- The ratio of the actual partial pressure of water vapour in air to the saturation pressure at the same dry-bulb temperature, expressed as a percentage.
- Dew point temperature
- The temperature at which air becomes saturated (RH = 100%) and water vapour begins to condense; cooling below dew point causes dehumidification.
- Sensible vs latent heat
- Sensible heat changes temperature without changing state (Q = m·c·ΔT); latent heat changes state at constant temperature (Q = m·h_fg).
- R-410A composition
- A near-azeotropic blend of 50% R-32 and 50% R-125 by mass, with zero ODP, GWP about 2088, and operating pressures roughly 1.6 times those of R-22.
- ODP definition
- Ozone Depletion Potential, a relative measure of how much a substance destroys stratospheric ozone, with CFC-11 assigned the reference value of 1.0.
- GWP definition
- Global Warming Potential, a relative measure of the heat trapped by a greenhouse gas over 100 years compared with carbon dioxide, which is assigned a value of 1.0.
- R-22 phase-out
- R-22 is an HCFC with ODP about 0.055; it is being phased out under the Montreal Protocol and is replaced by R-32, R-410A, or R-290 in new equipment.
- POE oil
- Polyolester synthetic lubricating oil, mandatory with HFC refrigerants such as R-134a and R-410A; it is hygroscopic and must be kept sealed from air.
- Montreal Protocol
- The 1987 international treaty that phases out ozone-depleting substances such as CFCs and HCFCs; its 2016 Kigali Amendment adds an HFC phase-down for climate protection.
- Phosgene formation
- A toxic gas produced when CFC or HCFC refrigerant contacts an open flame; therefore flame leak detectors must never be used on such systems.
- Frostbite first aid
- Refrigerant contact causes frostbite; flush the affected skin with lukewarm water, not hot water, cover loosely, and seek medical attention.
- TXV function
- A thermostatic expansion valve modulates refrigerant flow to maintain a constant evaporator superheat, typically 5–8 K, using bulb, evaporator, and spring pressures.
- Capillary tube
- A fixed-restriction expansion device made of a long small-bore tube, used in small window and split air conditioners; it cannot adjust to load changes.
- Filter-drier
- A device in the liquid line containing desiccant and a screen that removes moisture and solid particles, protecting the expansion device and compressor from blockage and corrosion.
- Four-way reversing valve
- A solenoid valve in a heat pump that reverses refrigerant flow direction, switching the system between cooling and heating modes by swapping evaporator and condenser roles.
- Split AC indoor height
- The indoor unit is mounted 2.3–2.5 m above the floor, with at least 15 cm clearance from the ceiling and side walls for proper air circulation.
- Evacuation level
- A deep vacuum of 500 microns (0.67 mbar) or lower must be reached and held for 10 minutes to confirm the system is dry and leak-free.
- Nitrogen pressure test
- A tightness test using dry nitrogen at 350–550 psi (24–38 bar) held for 24 hours; any pressure drop indicates a leak that must be repaired.
- Flare nut torque
- Standard tightening torques for flare joints: about 15–18 N·m for 1/4 inch, 35–40 N·m for 3/8 inch, and 50–55 N·m for 1/2 inch.
- Superheat diagnosis
- Superheat = suction temperature minus evaporating temperature. High superheat with low suction pressure indicates undercharge or a restriction; low superheat indicates overcharge.
- Dirty condenser symptom
- A dirty condenser raises discharge pressure and running current, raises suction pressure slightly, and reduces cooling capacity; clean the coil to restore performance.
- Compressor winding test
- Measure resistance between C–R, C–S, and R–S with a multimeter; C–R plus C–S should equal R–S. Infinite or zero readings indicate a faulty winding.
- Capacitor replacement rule
- After safely discharging, measure capacitance with a meter; replace the capacitor if the reading is more than 10% below the rated microfarad value.
- PSC motor
- Permanent split capacitor motor, the standard fan and small compressor motor in split air conditioners; it uses a run capacitor but no start capacitor.
- Inverter AC control
- An inverter air conditioner varies compressor speed using an IPM module and variable-frequency drive; check DC bus voltage and fault codes before replacing the PCB.
- NTC thermistor
- A negative-temperature-coefficient sensor whose resistance falls as temperature rises; a typical room thermistor reads about 10 kΩ at 25 °C.
- Micron gauge
- A vacuum instrument that measures absolute pressure in microns; it is essential to confirm deep vacuum because a manifold gauge cannot resolve low pressures.
- Megger test
- An insulation resistance test at 500 V DC between compressor winding and earth; a reading of at least 1 MΩ indicates acceptable insulation.
- Manifold gauge colours
- Blue hose connects to the low-pressure side, red to the high-pressure side, and yellow to the vacuum pump or charging cylinder.
- LOTO procedure
- Lock-out/tag-out: isolate the electrical supply, lock the breaker, attach a warning tag, and verify with a tester before beginning any service work.
- Class C fire
- A fire involving live electrical equipment; extinguish with CO2 or dry powder, never with water or foam, and isolate the supply first.