Quick reference

Fundamentals of Electricity and DC Circuits

  • Ohm's law: V = IR; power P = VI = I²R = V²/R. Units: volt, ampere, ohm, watt.

  • Series circuit: same current through all elements; R_total = R₁ + R₂ + …; voltage divides in ratio of resistances.

  • Parallel circuit: same voltage across all branches; 1/R_total = 1/R₁ + 1/R₂ + …; current divides inversely with resistance.

  • Resistance of a conductor: R = ρL/A; ρ in Ω·m, L in m, A in m². Longer or thinner wire gives higher resistance.

  • Temperature coefficient: R_t = R₀(1 + αΔt); metals have positive α, carbon and electrolytes negative.

  • Kirchhoff's laws: KCL - algebraic sum of currents at a node is zero; KVL - algebraic sum of emfs and drops round a loop is zero.

  • Energy: W = Pt; 1 kWh (one unit) = 3.6 × 10⁶ J. Energy in kWh = watts × hours ÷ 1000.

  • Cells: emf E, internal resistance r; terminal voltage V = E − Ir on discharge. Series connection raises emf, parallel raises current capacity.

Quick reference

Electromagnetism and Magnetic Circuits

  • Magnetic flux Φ in weber (Wb); flux density B = Φ/A in tesla (Wb/m²).

  • Magnetomotive force mmf = NI (ampere-turns); magnetising force H = NI/l in A/m.

  • Reluctance S = l/(μ₀μ_r A); magnetic Ohm's law: Φ = mmf/S.

  • Force on a current-carrying conductor: F = BIl sin θ; direction by Fleming's left-hand rule.

  • Faraday's law: e = −N dΦ/dt; Lenz's law fixes the direction opposing the change producing it.

  • Self-induced emf e = −L di/dt; energy stored in an inductor W = ½LI².

  • B–H curve: initial and maximum permeability; saturation limits flux for a given mmf; hysteresis loss ∝ frequency × area of loop.

  • Series magnetic circuit: total reluctance is the sum of the parts; air gaps dominate because μ_r of air is 1.

Quick reference

AC Fundamentals and Single-Phase Circuits

  • RMS = peak/√2 = 0.707 × peak; average of a full sine = 0; form factor 1.11, peak factor 1.414.

  • Frequency f = 1/T; angular frequency ω = 2πf; a 50 Hz supply has 100 pulses per second in a full-wave rectifier.

  • Pure R: current in phase with voltage. Pure L: current lags voltage by 90°. Pure C: current leads by 90°.

  • Reactances: X_L = 2πfL (rises with f); X_C = 1/(2πfC) (falls with f).

  • Impedance Z = √(R² + (X_L − X_C)²); phase angle tan φ = (X_L − X_C)/R.

  • Power: P = VI cos φ (watt), Q = VI sin φ (var), S = VI (VA); power factor = cos φ = R/Z.

  • Series resonance: X_L = X_C, Z = R minimum, current maximum, f_r = 1/(2π√(LC)).

  • Single-phase power factor improvement uses a parallel capacitor: I_C = P(tan φ₁ − tan φ₂)/V.

Quick reference

Three-Phase Systems and Transformers

  • Star: V_L = √3 V_ph, I_L = I_ph. Delta: V_L = V_ph, I_L = √3 I_ph.

  • Three-phase power P = √3 V_L I_L cos φ; for balanced star or delta the same formula applies.

  • Phase sequence and 120° displacement give constant total power in a balanced three-phase load.

  • Transformer emf equation: E = 4.44 f N Φ_m; voltage ratio V₂/V₁ = N₂/N₁ = I₁/I₂.

  • Ideal transformer: input VA equals output VA; core loss is constant, copper loss varies as I².

  • Losses: hysteresis and eddy-current (core) losses plus I²R (copper) losses; efficiency is maximum when copper loss equals core loss.

  • Open-circuit test gives core loss; short-circuit test gives full-load copper loss and equivalent impedance.

  • An autotransformer shares one winding; a current transformer steps current down for measurement and must never be open-circuited on the secondary.

Quick reference

DC Machines and AC Rotating Machines

  • DC generator emf: E_g = ΦZN P/(60A); for a DC motor back emf E_b = V − I_a R_a.

  • Motor torque T ∝ Φ I_a; speed N ∝ (V − I_a R_a)/Φ, so a shunt motor is nearly constant-speed.

  • A DC series motor must never be started unloaded; it develops high torque at low speed.

  • Three-phase induction motor: synchronous speed N_s = 120f/P; slip s = (N_s − N)/N_s; rotor frequency = sf.

  • Induction motor is self-starting, has no electrical connection to the rotor (squirrel cage), and runs below synchronous speed.

  • Synchronous motor runs at exactly N_s and can supply leading reactive power (used for power-factor correction).

  • Single-phase induction motors are not self-starting in principle; capacitor and shaded-pole types create a rotating field.

  • Alternator frequency f = PN/120; emf per phase E = 4.44 f Φ T k_d k_p.

Quick reference

Electrical Wiring, Installation and Protection

  • Indian wiring colours: phase red/yellow/blue, neutral black, earth green (or green-yellow).

  • Copper has lower resistivity than aluminium, so a smaller copper conductor carries the same current.

  • Fuse rating rule: fuse current slightly above normal load current but below the cable's current rating.

  • MCB trips on overload (thermal) and short circuit (magnetic); ELCB/RCCB trips on earth leakage, typically 30 mA for personnel protection.

  • Earthing limits touch voltage; earth resistance should be low (commonly ≤ 1 Ω for substations, a few ohms for domestic).

  • Two-way switching uses two two-way switches; the intermediate (three-way) switch is added for three control points.

  • Wire gauge (SWG) increases as the number decreases; a lower SWG number means a thicker wire.

  • Conduit, casing-capping and cleat wiring are chosen by location: conduit for concealed and damp areas, cleat for temporary open runs.

Quick reference

Electrical Measuring Instruments and Tariffs

  • Ammeter is connected in series and has very low resistance; voltmeter in parallel with very high resistance.

  • PMMC instrument: deflecting torque T = NABI, reads average value, used with rectifier for AC.

  • Moving-iron instrument reads RMS, is robust, and suits both AC and DC.

  • Induction type energy meter: deflecting torque ∝ power; creep prevented by a brake magnet and shading.

  • Wattmeter has a current coil (series) and a pressure coil (parallel); reading is VI cos φ.

  • Meter constant is revolutions per kWh; energy = revolutions ÷ meter constant.

  • Tariff: two-part tariff = fixed charge + running charge per unit; power factor penalty applies below a set cos φ.

  • Energy = power × time; a 1000 W load for 2 hours consumes 2 units (kWh).

Quick reference

Safety, Energy Conservation and Applied Practice

  • First aid for electric shock: switch off the supply, use dry insulating material to separate the victim, then start artificial respiration if breathing has stopped.

  • Never use water on an electrical fire; use CO₂ or dry-powder extinguishers.

  • Earth-leakage protection of 30 mA is the usual threshold for protection of persons against fatal shock.

  • Energy conservation: replace incandescent lamps with LED, use electronic chokes, and improve power factor to cut line current.

  • Illumination: luminous flux in lumen, illuminance in lux (lumen per m²); LED gives more lumen per watt than incandescent.

  • Load estimation: total connected load in watts ÷ 1000 gives kW; diversity factor reduces the maximum demand used for billing.

  • A star-delta starter reduces starting current to one-third of the direct-on-line value.

  • Periodic inspection checks insulation resistance (megger), earth continuity and correct fuse/MCB ratings.