Thevenin's theorem
Any linear two-terminal network can be replaced by a single voltage source V_th in series with R_th, where V_th is the open-circuit voltage and R_th the equivalent resistance with sources de-energized.
Maximum power transfer
A load receives maximum power when its resistance equals the Thevenin resistance of the source network. At that point the source delivers only 50 percent efficiency.
Series resonance condition
In a series RLC circuit, resonance occurs at f = 1/(2π√(LC)). At this frequency inductive and capacitive reactances cancel, impedance is minimum and current is maximum.
Power factor correction
Capacitor kVAR needed to raise power factor from cos φ₁ to cos φ₂ equals P multiplied by (tan φ₁ minus tan φ₂), where P is the active power in kW.
Per-unit impedance base
Z_base equals V_base squared divided by S_base. Converting actual ohms to per-unit simplifies transformer networks because per-unit impedances stay unchanged across voltage levels.
Symmetrical components
Any unbalanced three-phase set is resolved into positive, negative and zero sequence sets. The operator a equals 1 at 120 degrees, and a² equals 1 at 240 degrees.
Surge impedance loading
SIL equals V_L squared divided by the surge impedance √(L/C). At SIL the line delivers natural power with flat voltage profile and no reactive compensation.
Equal-area criterion
Transient stability is maintained when the accelerating area equals the maximum possible decelerating area. The method applies to a single machine against an infinite bus.
Distance relay zones
Zone 1 covers about 80 percent of the protected line with no intentional delay. Zone 2 reaches about 120 percent with a delay, and Zone 3 provides remote backup.
Mho relay characteristic
The mho relay has a circular characteristic passing through the origin, making it inherently directional. It is widely used for long transmission line protection.
Buchholz relay function
A gas-operated relay fitted in the pipe between transformer tank and conservator. It detects incipient faults by gas accumulation and severe faults by oil surge.
Restricted earth fault protection
A differential scheme using a core-balance CT on the transformer neutral. It detects ground faults in the winding that produce current below normal overcurrent settings.
Three-phase controlled rectifier
Average output of a fully controlled three-phase bridge is 1.35 times line voltage times cos alpha, where alpha is the firing angle measured from natural commutation.
Buck converter voltage ratio
In continuous conduction, output voltage equals duty cycle D multiplied by input voltage. The inductor current ripple depends on switching frequency and inductance value.
V/f control principle
Keeping voltage proportional to frequency maintains constant air-gap flux in an induction motor. This gives nearly constant torque capability below rated base speed.
Thyristor latching current
The minimum anode current needed to keep a thyristor conducting immediately after the gate pulse is removed. It is higher than the holding current value.
Transformer EMF equation
RMS induced EMF equals 4.44 times frequency times turns times peak flux. Voltage per turn is identical on primary and secondary windings of the same core.
Maximum efficiency load
A transformer reaches maximum efficiency when copper loss equals iron loss. The load fraction at that point equals the square root of iron loss over full-load copper loss.
Slip at maximum torque
For an induction motor, slip at maximum torque equals rotor resistance divided by rotor standstill reactance. Maximum torque itself does not depend on rotor resistance.
Synchronous speed formula
Synchronous speed in rpm equals 120 times supply frequency divided by the number of poles. A four-pole machine on 50 Hz runs at 1500 rpm.
Ferranti effect
On a lightly loaded long transmission line, receiving-end voltage exceeds sending-end voltage because charging current through line inductance raises the voltage. Shunt reactors compensate.
ABCD constants
A two-port transmission network is described by sending voltage equals AV_r plus BI_r and sending current equals CV_r plus DI_r. For a symmetrical network AD minus BC equals one.
Voltage regulation
The rise in receiving-end voltage, expressed as a percentage of full-load value, when full load is removed while sending-end voltage remains constant.
Sag formula
For level supports with uniformly distributed load, sag equals weight per unit length times span squared divided by eight times tension. Sag rises with span squared.
Wheatstone bridge balance
The bridge is balanced when the ratio of two adjacent arms equals the ratio of the remaining two arms. At balance no current flows through the galvanometer.
PMMC instrument response
A permanent-magnet moving-coil meter responds to the average value of current and is inherently a DC instrument. A rectifier extends it to AC measurement.
PID controller actions
Proportional action responds to present error, integral action eliminates steady-state offset, and derivative action anticipates error trend to reduce overshoot.
Strain gauge gauge factor
Gauge factor equals the fractional change in resistance divided by the fractional change in length. Metal foil gauges typically have a factor near two.
Successive percentage change
Two successive changes of a percent and b percent produce a net change of a plus b plus ab divided by 100 percent. A rise then equal fall never returns to the original value.
Syllogism validity rule
A conclusion follows only if it is true in every possible Venn diagram consistent with the premises. A single counterexample diagram makes it invalid.
Active to passive voice
The object becomes the subject, the verb becomes a form of be plus past participle, and the original subject follows 'by' or is omitted when unimportant.
Load despatch centres
The National Load Despatch Centre coordinates national grid operation in India, while regional load despatch centres manage their regions under its overall supervision.