PGCIL Field Engineer & DT key terms
PGCIL Field Engineer & DT · Get comfortable with the vocabulary.
- Power factor
- Related: Reactive power, Apparent power
The cosine of the angle between voltage and current in an AC circuit; it equals real power divided by apparent power and indicates how effectively current is converted into useful work.
- Reactive power
- Related: Power factor, Series compensation
The portion of AC power that oscillates between source and reactive elements without doing net work, measured in volt-amperes reactive (var) and needed to sustain magnetic fields in inductors and transformers.
- Apparent power
- Related: Power factor, Reactive power
The product of RMS voltage and RMS current in an AC circuit, expressed in volt-amperes; it is the vector sum of real power and reactive power.
- Per-unit system
- Related: Symmetrical components, Fault level
A method of expressing electrical quantities as fractions of chosen base values, so that transformers of different ratings can be handled uniformly and calculations become independent of voltage level.
- Symmetrical components
- Related: Per-unit system, Negative sequence
A technique that resolves an unbalanced three-phase set of phasors into three balanced sets called positive, negative and zero sequence, enabling fault and unbalance analysis using single-phase equivalent circuits.
- Negative sequence
- Related: Symmetrical components, Current transformer
The balanced component set whose phase rotation opposes the normal phase order; it appears during unbalanced faults or unbalanced loads and causes rotor heating and torque pulsation in machines.
- Load flow study
- Related: Voltage regulation, Per-unit system
A steady-state network calculation that determines bus voltage magnitudes and angles and the real and reactive power flows on each branch for specified generation and demand conditions.
- Equal area criterion
- Related: Critical clearing time, Swing equation
A graphical stability test in which the accelerating area of a synchronous machine's power-angle curve must be matched by an available decelerating area for the system to remain transiently stable after a disturbance.
- Critical clearing time
- Related: Equal area criterion, Distance relay
The longest fault duration for which a power system can retain synchronism after the fault is cleared; clearing faster than this value keeps the machine transiently stable.
- Swing equation
- Related: Equal area criterion, Critical clearing time
The differential equation relating rotor angular acceleration of a synchronous machine to the imbalance between mechanical input power and electrical output power, scaled by inertia constant.
- Distance relay
- Related: Current transformer, Capacitor voltage transformer, Critical clearing time
A protection relay that estimates the impedance from the relay location to a fault by dividing measured voltage by measured current, then trips when the impedance falls inside a set zone.
- Differential protection
- Related: Current transformer, Restricted earth fault protection
A scheme that compares currents entering and leaving a protected zone and trips when their difference exceeds a threshold, giving fast, selective protection for transformers, generators and busbars.
- Restricted earth fault protection
- Related: Differential protection, Current transformer
A sensitive earth-fault scheme in which a core-balance or neutral current transformer measures only the residual current inside a defined zone, so faults outside the zone do not operate it.
- Current transformer
- Related: Capacitor voltage transformer, Distance relay, Negative sequence
An instrument transformer that reproduces a large primary current as a proportional, phase-related smaller secondary current for measurement and protection relays, while isolating the secondary circuit from high voltage.
- Capacitor voltage transformer
- Related: Current transformer, Distance relay
A voltage measuring device that uses a capacitive divider, often with a carrier-access unit, to produce a low secondary voltage for metering and protection and to couple power-line carrier signals.
- Circuit breaker
- Related: Isolator, Auto-reclosing
A switching device capable of making, carrying and interrupting fault currents, with an arc-quenching medium such as SF6, vacuum or air, and a mechanism that reseals the circuit after interruption.
- Isolator
- Related: Circuit breaker, Interlock
A mechanical switching device that provides a visible isolating gap for safe maintenance but has no rated fault-interrupting capability, so it must be operated only after the circuit breaker has cleared current.
- Auto-reclosing
- Related: Circuit breaker, Distance relay
An automatic scheme that re-closes a circuit breaker after a trip to restore service following transient faults, often with single-pole or three-pole operation and a dead time before reclosure.
- Interlock
- Related: Isolator, Circuit breaker
A logic arrangement that prevents unsafe sequences of switching or operation, for example blocking an isolator from opening while its associated circuit breaker is still carrying load current.
- Insulation coordination
- Related: Surge arrester, Basic impulse insulation level
The selection of insulation withstand levels and protective device characteristics so that insulation is protected against overvoltages while cost and clearance are kept reasonable.
- Basic impulse insulation level
- Related: Insulation coordination, Surge arrester
The standard lightning-impulse withstand voltage that equipment insulation must tolerate, used as a reference for coordinating insulation and protective margins across a system voltage class.
- Surge arrester
- Related: Insulation coordination, Basic impulse insulation level
A protective device that presents high impedance at normal voltage but becomes conducting during overvoltage, diverting surge current to earth and then resealing to protect insulation.
- Corona
- Related: Bundle conductor, Skin effect
Ionization of air around a conductor when the surface electric field exceeds the breakdown strength of air, causing power loss, audible noise, radio interference and possible insulation damage.
- Bundle conductor
- Related: Corona, Series compensation
Two or more sub-conductors per phase spaced by small spacers, which reduces corona and inductive reactance while increasing the effective diameter and current-carrying capability of the phase.
- Series compensation
- Related: Reactive power, Bundle conductor
Insertion of capacitors in series with a transmission line to cancel part of its inductive reactance, raising power transfer capability and improving voltage profile, with protection against sub-synchronous effects.
- Ferranti effect
- Related: Voltage regulation, Shunt reactor
The rise of receiving-end voltage above sending-end voltage on a lightly loaded or open long AC line, caused by the line's capacitive charging current flowing through its series inductance.
- Shunt reactor
- Related: Ferranti effect, Reactive power
An inductor connected from line or bus to earth to absorb capacitive reactive power, limiting overvoltage on light load and long lines and aiding voltage control.
- Skin effect
- Related: Proximity effect, Corona
The tendency of alternating current to concentrate near the surface of a conductor at higher frequencies, which raises effective resistance and reduces usable cross-section.
- Proximity effect
- Related: Skin effect
The redistribution of alternating current in a conductor caused by the magnetic field of nearby current-carrying conductors, increasing effective resistance in windings and cables.
- Voltage regulation
- Related: Load flow study, Ferranti effect
The change in terminal voltage of a machine or transformer between no load and full load at a stated power factor, usually expressed as a percentage of rated voltage.
- Slip
- Related: V/f control, Voltage regulation
The difference between synchronous speed and actual rotor speed of an induction machine, expressed as a fraction of synchronous speed; it determines rotor frequency and developed torque.
- V/f control
- Related: Slip, Pulse-width modulation
A variable-speed drive technique for induction motors that keeps the voltage-to-frequency ratio nearly constant so that magnetic flux and hence torque capability remain approximately unchanged as speed varies.
- Pulse-width modulation
- Related: V/f control, Total harmonic distortion
A switching method that synthesizes a variable-voltage, variable-frequency waveform by rapidly chopping a DC supply and varying the on-time of pulses, shifting harmonics to higher frequencies.
- Total harmonic distortion
- Related: Pulse-width modulation, Active filter
The ratio, usually expressed as a percentage, of the RMS value of all harmonic components to the RMS value of the fundamental component of a voltage or current waveform.
- Active filter
- Related: Total harmonic distortion, Reactive power
A power-electronic converter that injects compensating currents or voltages to cancel harmonics and correct reactive power, adapting in real time to changing load conditions.
- SCADA
- Related: Interlock, Current transformer
Supervisory control and data acquisition: a system of remote terminal units, communication links and a master station that lets operators monitor and control substation and plant equipment from a control centre.
- Fault level
- Related: Per-unit system, Circuit breaker
The maximum prospective short-circuit current or apparent power that a network can deliver at a given point, used to select switchgear ratings and check protection settings.