Plumbing permit required
A permit from the authority having jurisdiction must be obtained before installing, altering, or repairing a plumbing system; ordinary minor repairs are typically exempt.
Rough-in inspection
The rough-in inspection is requested after all piping is installed and tested but before any piping is concealed by framing, drywall, or concrete.
Licensed contractor requirement
Plumbing work must be performed by a licensed plumbing contractor, a licensed journeyman, or an apprentice under the direct supervision of a licensed journeyman.
Drainage fixture unit
One drainage fixture unit represents one cubic foot per minute, or about 7.5 gallons per minute, of flow discharged by a plumbing fixture.
Building drain definition
The lowest piping of a building drainage system, receiving waste from inside the building and extending 30 inches beyond the exterior wall where it becomes the building sewer.
Water supply fixture unit
One water supply fixture unit equals one gallon per minute of water demand and serves as the basis for sizing water distribution piping.
Flushometer water closet demand
A flushometer-valve water closet is rated 10 water supply fixture units, while a tank-type water closet is rated 2.5 water supply fixture units.
Minimum fixture residual pressure
A water distribution system must deliver at least 15 psi of residual pressure at fixtures while they are flowing at peak demand.
Water piping test requirement
Water distribution piping is tested with water at working pressure, but not less than 100 psi, for 15 minutes with no loss of pressure.
Horizontal drain slope
Drainage pipe 2 1/2 inches and smaller must slope at least 1/4 inch per foot, while pipe 3 inches and larger slopes at least 1/8 inch per foot.
Cleanout spacing rule
Cleanouts are required at the base of each stack, at the building drain, and at intervals not exceeding 100 feet along horizontal drainage piping.
Drain size reduction
Drainage piping may never be reduced in size in the direction of flow at any point from the fixture to the building sewer.
Lavatory fixture units
A lavatory is rated 1 drainage fixture unit, a value used in code tables to size fixture branches, stacks, and building drains.
Vent terminal height
A vent must extend at least 6 inches above the roof surface and terminate away from windows, doors, and outdoor air intakes.
Vent minimum diameter
No vent pipe may be smaller than 1 1/4 inches in diameter, and vent size may not be reduced in the direction of flow.
Trap vent requirement
Each trap must be protected against siphonage by a vent connected to open air, unless an approved special venting method is used.
Trap seal depth
A trap must hold a liquid seal at least 2 inches deep and not more than 4 inches deep to resist the passage of sewer gas.
Grease interceptor sizing
A grease interceptor serving food service fixtures is sized by fixture flow in gallons per minute and must remain accessible for cleaning.
Prohibited S-trap
S-traps and bell traps are prohibited because their shape promotes siphonage of the trap seal and makes the trap prone to clogging.
Water closet flush volume
Water closets installed in a plumbing system must not exceed 1.6 gallons per flush under federal water efficiency standards adopted by Indiana.
Showerhead flow rate
A showerhead may not discharge more than 2.5 gallons per minute when tested at 80 psi of flowing pressure.
Lavatory faucet flow rate
Lavatory and kitchen faucets are limited to a maximum flow of 2.2 gallons per minute at 60 psi under federal efficiency standards.
T&P relief valve setting
The temperature and pressure relief valve on a water heater is set to open at 210 degrees Fahrenheit or 150 psi, whichever occurs first.
Relief discharge pipe
The relief valve discharge pipe must be full size, contain no valves or threads, and terminate within 6 inches of the floor or outdoors.
Thermal expansion tank
A closed potable water system with a check valve or backflow preventer requires a thermal expansion tank to control pressure rise from heated water.
Storm and sanitary separation
Storm drainage from roofs, yards, and paved areas must be piped separately and may never be connected to a sanitary sewer.
Roof drain sizing basis
Roof drain and leader sizes are selected using the roof area drained and the design rainfall intensity in inches per hour for the site.
Storm drain disposal point
Storm drainage must discharge to an approved outlet such as a storm sewer, dry well, or natural watercourse, never to a sanitary line.
Air gap definition
An air gap is the unobstructed vertical distance through free air between a potable water outlet and the flood level rim of the receptacle it serves.
Reduced pressure zone assembly
A reduced pressure zone assembly protects potable water against both backpressure and backsiphonage and is required for high hazard cross connections.
Backflow assembly testing
Testable backflow prevention assemblies must be tested at installation and at least annually by a certified backflow prevention assembly tester.
Hose bibb vacuum breaker
A hose bibb requires an atmospheric or hose-connection vacuum breaker so that a submerged hose cannot siphon contaminants into the water supply.