Punjab PSEB Sr. Sec. NSQF Electronics (Solar Panel Installation Technician) flashcards
Punjab PSEB Sr. Sec. NSQF Electronics (Solar Panel Installation Technician) · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Standard Test Conditions
- Reference conditions for PV ratings: 1000 W/m² irradiance, 25 °C cell temperature, and AM 1.5 spectrum. Nameplate power, voltage and current are quoted at STC.
- Fill factor
- Ratio of maximum power to the product of open-circuit voltage and short-circuit current: FF = (Impp × Vmpp) / (Isc × Voc). Higher fill factor means a squarer, better I-V curve.
- Open-circuit voltage
- Voltage across a module terminals with no load connected, measured in volts. It rises slightly in cold weather and falls as cell temperature increases.
- Short-circuit current
- Current that flows when module terminals are connected through a near-zero resistance. It scales almost linearly with irradiance and is used to check string health.
- Photovoltaic effect
- Generation of voltage and current when light strikes a semiconductor junction. Photons create electron-hole pairs that the built-in electric field separates.
- Peak sun hours
- Number of hours per day at 1000 W/m² equivalent irradiance. Daily energy yield is roughly array kWp times peak sun hours times performance ratio.
- Monocrystalline module
- Module made from single-crystal silicon cells, usually black and uniform. Efficiency is typically 18-23 %, giving the highest power per square metre.
- Polycrystalline module
- Module made from multi-crystalline silicon with visible grain boundaries and a bluish look. Efficiency is typically 15-18 %, with lower cost than monocrystalline.
- Thin-film module
- Module using CdTe, CIGS or amorphous silicon layers. Efficiency is lower (6-13 %) but it is flexible, lightweight and performs relatively better in high heat and low light.
- Bypass diode
- Diode connected across a group of cells in the junction box. It provides an alternate current path when cells are shaded, limiting hot-spot heating and power loss.
- Potential-induced degradation
- PID is a voltage-driven module degradation that reduces power, often from leakage currents between cells and frame. It appears as shunting and can be tested by flash test.
- Maximum series fuse rating
- Datasheet value giving the largest fuse permitted in series with a module or string. String fuses must not exceed this rating to protect the module.
- Load assessment
- Inventory of every appliance with wattage, daily hours and quantity. Daily energy in Wh equals the sum of watts times hours times quantity.
- Optimum tilt angle
- Angle of the array from horizontal that maximises annual yield, roughly equal to site latitude. Adjusting latitude minus 10-15° favours summer generation.
- Shading analysis
- Study of shadows on the array through the day and year, especially 9:00-15:00. It identifies obstructions and sets row spacing or module repositioning.
- Depth of discharge
- Fraction of battery capacity that may be withdrawn before recharging. Lead-acid is usually limited to 50 %, while LFP batteries allow 80-90 %.
- Voltage drop
- Loss of voltage along a cable due to resistance. For a two-wire DC run, Vdrop = 2 × L × I × ρ / A; keep DC drop within 3 %.
- Mid-clamp
- Mounting clamp that grips the frames of two adjacent modules and fixes them to the rail. It is torqued to the manufacturer specification, commonly 16-20 N·m.
- Wind uplift load
- Upward force on the array caused by wind passing over it. Design pressure uses p = 0.6 × Vz², with higher values at roof edges and corners.
- Module handling rule
- Carry modules upright with two persons, never stand or place tools on the glass, and store on edge on a padded surface to avoid micro-cracks.
- MC4 connector
- Locking DC connector used for module and string wiring. Only mate identical types, crimp with the correct tool, and never disconnect under load.
- String fuse
- Fuse placed in series with each string in the combiner box. It protects the module and cabling from reverse currents and must not exceed the module maximum series fuse rating.
- Earthing and bonding
- Connection of module frames, structure, inverter and enclosures to a common earth electrode. Earth continuity resistance is typically kept below 1 Ω.
- Surge protective device
- Device that diverts lightning or switching surges to earth. Type 2 DC SPDs are fitted on the DC side and Type 2 AC SPDs on the AC side.
- Anti-islanding
- Grid-tied inverter function that stops export within a set time when the grid fails. It protects utility workers and is tested during commissioning per IEC 62116.
- MPPT charge controller
- Controller that continuously adjusts operating voltage to the array maximum power point. Efficiency is typically 93-98 %, higher than PWM controllers.
- Hybrid inverter
- Inverter that works with the grid and a battery bank, supporting self-consumption, export and backup. Sizing must check MPPT count and battery voltage compatibility.
- Insulation resistance test
- Measurement of resistance between DC conductors and earth using a megger at 500-1000 V. A reading below about 1 MΩ indicates cable damage or moisture.
- Clamp meter current check
- Measurement of DC current in each string under load. Comparing strings after correcting for irradiance reveals a dead string, mismatch or partial shading.
- Performance ratio
- Ratio of actual energy yield to theoretical yield at STC for the same irradiance. Typical values are 0.70-0.85; below 0.70 signals a problem.
- Lockout/tagout
- Safety procedure that isolates AC and DC supplies, applies a personal lock and tag, and verifies zero voltage before work. Only the applier removes the lock.
- Battery and e-waste disposal
- Used modules, inverters and batteries must go to authorised recyclers under the E-Waste and Battery Waste Management Rules. Burning or landfilling is prohibited.