Punjab PSEB Sr. Sec. NSQF Power (Distribution Lineman) flashcards
Punjab PSEB Sr. Sec. NSQF Power (Distribution Lineman) · Build recall with a focused review session.
34 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's Law
- Current through a conductor is directly proportional to voltage and inversely proportional to resistance, expressed as V = I × R.
- Power Factor
- The ratio of real power in kW to apparent power in kVA, equal to cos φ. A low value means more current for the same useful power.
- RMS Value
- The effective value of an alternating quantity, equal to peak value divided by the square root of two, or 0.707 times the peak.
- 415 V Four-Wire System
- Three-phase low-voltage distribution with 415 V between lines and 240 V between any line and neutral, used for mixed domestic and small industrial loads.
- Radial Distribution System
- A layout where each consumer is fed from a single path from the source, simple and cheap but with no alternative supply on failure.
- Distributor versus Feeder
- A feeder is designed on current-carrying capacity and has no consumer taps; a distributor is tapped along its length and is designed on permissible voltage drop.
- Sag Formula
- For a level span, sag equals weight per unit length times span squared divided by eight times tension, showing sag rises with span and falls with tension.
- Corona Effect
- Ionisation of air around a conductor when surface voltage gradient exceeds about 30 kV/cm, causing power loss, audible noise and radio interference.
- Ferranti Effect
- Rise of receiving-end voltage above sending-end voltage on a long lightly loaded line, caused by charging current through line capacitance.
- ACSR Conductor
- Aluminium conductor steel reinforced: aluminium strands around a steel core, giving low weight, low cost and high tensile strength for long spans.
- Pin Insulator
- A rigid insulator fixed on a pin or cross-arm, used up to about 11 kV, where the conductor is tied with binding wire in a groove.
- Creepage Distance
- The shortest path along the insulator surface between line and earth; it must be increased in polluted coastal and industrial areas to prevent tracking.
- Transformer EMF Equation
- The induced EMF equals 4.44 times frequency times turns times maximum flux, showing voltage per turn is fixed by core flux and frequency.
- Buchholz Relay
- A gas-operated protective device fitted between transformer tank and conservator that alarms on slow gas accumulation and trips on violent oil surge.
- Open-Circuit Test
- A transformer test with one winding open that measures no-load current and iron loss, which stays constant at all loads.
- Stay Wire Angle
- A guy wire set at about 45 degrees to the ground, anchored in undisturbed soil, to resist the unbalanced pull at angle and terminal poles.
- Earth Resistance Limit
- The maximum measured resistance of a substation earth electrode, commonly 5 ohms for distribution substations and 1 ohm for large stations.
- Tension Stringing
- Pulling conductors under controlled tension with a puller and tensioner so they do not drag on ground, crops or roads during erection.
- Sag Template
- A sighting board or chart used to set the correct conductor sag for the ruling span and conductor temperature during stringing.
- XLPE Cable
- Cross-linked polyethylene insulated cable with conductor and insulation screens, used for modern distribution because it withstands higher temperature than PVC.
- Stress Cone
- A shaped termination of the insulation screen that spreads the electric field at a cable end, preventing tracking and breakdown at joints and terminations.
- Cable Bending Radius
- The minimum radius, about twelve to fifteen times cable diameter, below which a cable must not be bent or its insulation and screens are damaged.
- Multiplying Factor
- The CT ratio times PT ratio applied to a meter reading for high-voltage metering, giving the actual energy consumed at the primary side.
- RCCB Function
- A device that trips on imbalance between phase and neutral current, protecting people from earth leakage but not from overload or short circuit.
- Permit to Work
- A written authorisation issued after isolation, locking, tagging and earthing, naming the circuit and work, and signed before work starts.
- CPR Compression Ratio
- Thirty chest compressions at 100 to 120 per minute with 5 to 6 cm depth, followed by two rescue breaths, repeated until help arrives.
- Prove Dead
- Testing an isolated circuit with a voltage detector to confirm zero voltage before applying temporary earths and touching conductors.
- Megger Test Voltage
- Insulation resistance is measured at 500 V for low-voltage circuits and at 1 kV or 5 kV for high-voltage cables and machines.
- Fall-of-Potential Method
- An earth resistance test using current and potential spikes driven at specified spacing, with the electrode under test connected to the instrument.
- Thermography
- Infrared imaging of joints, conductors and insulators to find abnormal temperature rise caused by loose connections or overload before failure occurs.
- Shift Handover Record
- A written note of circuits isolated, permits issued, work in progress and equipment out of service, passed to the next shift for continuity.
- Break-Even Point
- The sales volume at which total revenue equals total cost, so the business makes neither profit nor loss; used to price contract work.
- NSQF Level for Lineman
- The Power Distribution Lineman job role is placed at NSQF Level 4, with progression to supervisor roles at higher levels through experience and assessment.
- Risk Assessment
- A structured evaluation of a task that rates each hazard by likelihood and severity, then sets controls before work begins.