All case studies

Formaldehyde and Missing Product Documentation After Fit-Out

A 2,000 m² office fit-out for 60 workstations includes new carpet, composite-wood millwork, low-VOC paint, and adhesives. Two weeks after move-in, occupants report eye irritation and odors. Air testing shows TVOC at 1,200 µg/m³ and formaldehyde at 70 µg/m³. About 40% of installed products lack VOC-content documentation; one millwork product has a Health Product Declaration listing a carcinogen. The project has 58 points on its WELL v2 scorecard and is pursuing Materials 06 and Materials 07, plus Air 01. The landlord will not allow another full flush-out because of a tenant event in three weeks. The team must decide whether to remove finishes, increase ventilation, or wait, and must produce a documentation package that distinguishes product-level compliance from indoor air performance.

1. Evaluate the air results and the materials documentation. What is the immediate risk, and what should the team do first?

Read the worked answer

Immediate risk: formaldehyde at 70 µg/m³ exceeds the WELL Air 01 threshold of 50 µg/m³, and TVOC at 1,200 µg/m³ is high enough to explain eye irritation and odors. This is both an air-quality precondition risk and a materials-documentation failure. Occupants are already symptomatic, so waiting three weeks for the tenant event is not a defensible control strategy.

First actions:

  1. Increase outdoor-air ventilation and use temporary filtration, including gas-phase or chemisorption media where appropriate, to reduce formaldehyde and TVOC. A flush-out may help, but it cannot substitute for source removal if millwork or adhesives are the source.
  2. Identify the highest-emitting products. Review product schedules, installation dates and SDSs; use field screening or chamber testing where needed. Remove or isolate suspect millwork, carpet or adhesives.
  3. Re-test after remediation with accredited methods, calibrated equipment and chain of custody. Test occupied spaces under normal ventilation, not only during a flush.

Documentation risk: 40% of products lacking VOC-content documentation should be treated as unverified, not as compliant by default. The project cannot claim Materials 06 credit for products without evidence. The air result also shows that product-level claims do not guarantee indoor air performance; both lines of evidence are needed.

2. Recommend a corrective and documentation strategy that addresses Materials 06, Materials 07, and Air 01 without overclaiming.

Read the worked answer

Corrective strategy:

  • Source removal: replace or remove the highest-emitting composite-wood millwork, carpet or adhesives. If removal is not possible, seal or encapsulate only where the manufacturer confirms suitability.
  • Ventilation: increase outdoor-air delivery and run temporary filtration. Document ventilation rates and operating hours.
  • Phasing: if the tenant event cannot move, isolate the affected zone, increase ventilation and restrict occupancy until re-testing is complete.
  • Re-test: use accredited labs for formaldehyde and TVOC, with calibrated real-time instruments for screening. Record sampling locations, occupancy and HVAC mode.

Documentation strategy:

  • Build a product schedule with VOC content, test reports, SDSs, HPDs and EPDs.
  • Mark each product as verified, unverified or noncompliant. Do not count unverified products toward Materials 06.
  • For Materials 07, confirm that each declaration meets the feature's content and format requirements; an incomplete HPD should not be presented as compliant.
  • For Air 01, include lab reports, calibration certificates and a narrative linking the measured results to the remediation.

Judgment: the project should separate product-level compliance from indoor air performance in the submission. A product can have low VOC content and still contribute to indoor concentrations if the installed quantity is large or ventilation is inadequate. The team should present both the product evidence and the air-test evidence, and explain any remaining exceedance rather than hiding it behind product claims.

3. How should the Health Product Declaration listing a carcinogen be handled in the WELL submission?

Read the worked answer

First, determine whether the substance is restricted. An HPD is a disclosure, not automatically a prohibition. Check the substance against the WELL restricted-substance list used by the applicable Materials feature. If it is restricted, the product should be removed or replaced; documentation alone does not cure a restriction.

If it is not restricted: the finding is still relevant to Materials 07 and to occupant health. Document the substance, its concentration and the product quantity. Assess exposure and consider substitution as a materials-optimization strategy. Do not claim Materials 07 credit for an HPD that is incomplete or fails the feature's content requirements; transparency credit depends on the declaration meeting the specified format and scope.

Communication: tell the owner and design team that a carcinogen disclosure is a risk factor, not a pass or fail by itself. If the product remains, record the rationale, any exposure controls and the plan for future replacement. If the product is replaced, keep the HPD and substitution record in the documentation package.

Submission: present the HPD finding clearly, with the restricted-substance determination and the action taken. Avoid overclaiming that the project is 'hazard-free'; the defensible claim is that restricted substances were screened and disclosed hazards were managed according to the feature requirements. If the team cannot verify the product, mark it as unverified and exclude it from credit claims.