Thermal Physics and Heat Transfer Fundamentals

  • Fourier's law: q = −kA(dT/dx), with k in W/(m·K); steady one-dimensional conduction is proportional to area and temperature gradient.

  • Convection: q = hA(Ts − T∞); h combines natural and forced effects and rises steeply with air velocity.

  • Radiation: q = εσA(Ts⁴ − Tsurr⁴), σ = 5.67×10⁻⁸ W/(m²·K⁴); absolute temperatures in kelvin are required.

  • Wien's displacement law: λmax(μm) ≈ 2898/T(K); a 300 K surface peaks near 9.7 μm, inside the LWIR band.

  • Kirchhoff's law: at a given wavelength and temperature ελ = αλ, so low-emissivity surfaces emit little and reflect much.

  • Emissivity spans 0–1: polished aluminium ≈ 0.05, oxidised steel ≈ 0.80, matte black paint ≈ 0.95, human skin ≈ 0.98.

  • Thermal diffusivity α = k/(ρcp) governs transient response speed; thermal resistance of a slab is R = L/k.

  • A temperature difference of 1 K equals 1 °C; K = °C + 273.15, and heat flux is expressed in W/m².

  • Natural convection on a vertical air-facing plate typically gives h = 3–10 W/(m²·K); forced air raises this to 10–100 W/(m²·K).

Quick reference

Infrared Equipment

  • LWIR (8–14 μm) suits near-ambient targets and transmits well in humid air; MWIR (3–5 μm) suits hot targets and high-temperature ranges.

  • Uncooled microbolometers operate at ambient temperature with NETD typically 30–80 mK and frame rates of 30–60 Hz.

  • Cooled photon detectors (InSb, MCT, QWIP) run at cryogenic temperature, giving NETD below 20 mK, short integration times and high frame rates.

  • IFOV (mrad) = FOV (mrad) / horizontal detector pixels; at working distance d the pixel footprint equals IFOV × d.

  • Focal length and detector size set the field of view; a narrower FOV shrinks spot size and increases resolvable detail.

  • NETD is the target-to-background difference producing a signal equal to detector noise; lower NETD means better sensitivity.

  • Germanium optics are opaque to visible light and transmit well from about 2 to 12 μm, so visual and thermal alignment differ.

  • Water vapour and CO₂ absorption reduce received signal; cameras compensate using distance, relative humidity and air temperature inputs.

  • Detector warm-up and stabilisation must complete before radiometric accuracy meets the manufacturer's published specification.

Quick reference

Camera Setup and Measurement Techniques

  • Radiometric accuracy requires four inputs: emissivity, reflected apparent temperature, distance/atmospheric transmission, and relative humidity with air temperature.

  • Reflected apparent temperature is measured with a crumpled aluminium foil reflector placed in front of the target and assigned ε ≈ 1.

  • A spot measurement is valid only when the target fills at least 3×3 pixels; smaller targets read a blend of target and background.

  • Defocus enlarges the effective spot and blends target with background, lowering the peak apparent temperature of small hot spots.

  • Level and span remap the display window to the colour scale; stored radiometric values are unchanged.

  • Palette choice (rainbow, iron, greyscale) affects display only and never changes measured temperatures.

  • For low-emissivity targets, matte tape or paint of known ε ≈ 0.95 provides a reliable comparison surface.

  • Isotherms and colour alarms highlight all pixels above, below or between set thresholds, enabling fast scanning of large areas.

  • Published emissivity tables are indicative; the assigned value must match surface condition, viewing angle and the camera's spectral band.

Quick reference

Electrical and Mechanical Inspection Applications

  • High-resistance joints, loose lugs and corroded contacts produce I²R heating that scales with the square of load current.

  • Electrical surveys are informative only under load; 40% of nominal current is a widely used minimum, with higher load giving better fault contrast.

  • Severity is graded by ΔT against a similar component under similar load: about 1–3 °C possible, 4–15 °C probable, above 15 °C major deficiency.

  • Phase imbalance shows as one phase or the neutral running hotter; all phases and the neutral are compared at the same load.

  • Solar loading and wind distort outdoor electrical scans; night or shaded surveys reduce the solar error.

  • Bearing defects, inadequate lubrication, misalignment and belt slip appear as elevated housing temperature relative to sister units.

  • Motor overheating arises from overload, voltage imbalance, single phasing or blocked cooling passages.

  • Steam trap failure, missing insulation, refractory damage and moisture ingress are located by abnormal surface temperature patterns.

  • Mechanical friction heating appears on the loaded side and shifts with rotational speed, so speed and load are recorded with each image.

Quick reference

IR Image Analysis and Interpretation

  • Low-emissivity shiny surfaces mirror nearby sources; the false pattern moves with the camera and is a reflection, not a real temperature.

  • A genuine thermal anomaly persists in shape and location as viewing angle changes and correlates with an expected heat source.

  • Reported temperature is apparent; correcting emissivity, reflected temperature and atmospheric transmission yields true surface temperature.

  • Comparative analysis of similar components under similar load is more reliable than absolute temperature thresholds.

  • Thermal bridges appear warm in heating season because framing conducts heat through the envelope faster than adjacent insulation.

  • Wet building materials have high thermal mass and evaporative cooling, appearing cooler by day and warmer at night than dry material.

  • Wind above roughly 5 m/s reduces surface temperature differences and can hide envelope insulation defects.

  • Minimum detectable ΔT is set by NETD plus scene noise; small targets need a larger temperature difference to be resolved.

  • Baseline images taken from fixed positions with fixed settings and load allow deterioration to be trended over time.

Quick reference

Standards, Reporting and Thermography Program Implementation

  • ISO 18436-7 defines three thermographer certification categories: Category 1 assistant, Category 2 practitioner, Category 3 programme leader.

  • ISO 18434-1 gives guidance on infrared thermography for condition monitoring and diagnostics of machines.

  • ASTM E1934 is the standard guide for examining electrical and mechanical equipment with infrared thermography.

  • ASTM C1060 covers qualitative thermographic surveys of building envelope insulation; ASTM E1186 covers air leakage detection.

  • A report records ambient temperature, wind, solar load, humidity, emissivity and reflected temperature settings, equipment ID and load.

  • Each finding includes paired visual and thermal images, measured temperatures, ΔT, severity class and a recommended action.

  • Camera calibration is verified against a blackbody reference at intervals set by the manufacturer or programme procedure, commonly annually.

  • A written programme procedure defines inspection routes, severity criteria, acceptance limits, reporting format and corrective-action tracking.

  • NFPA 70E governs electrical safe work practice, including arc-flash PPE, when thermographers open energised panel covers.