Craftsman Electricity: Motors, Controls, and HVAC Equipment

Craftsman Electricity · Work through your exam, one topic at a time.

All guide sections

Motors, Controls, and HVAC Equipment

Motors, Controls, and HVAC Equipment

This domain tests NEC Article 430 motor circuits and Article 440 HVAC equipment. You need to size branch-circuit conductors, overload protection, short-circuit protection, disconnects, and controllers from motor nameplate and table values.

Core rules

  • Motor branch-circuit conductors are at least 125% of the motor full-load current (FLC) from Tables 430.247–430.250.
  • Overload protection is sized from the motor nameplate current, typically 125% for continuous-duty motors; it protects the motor from overheating.
  • Short-circuit and ground-fault protection is sized from Table 430.52, often 250% of FLC for an inverse-time breaker, with next-standard-size allowances.
  • The disconnecting means must be within sight and readily accessible, and rated at least 115% of the motor FLC.
  • HVAC equipment uses the nameplate minimum circuit ampacity (MCA) for conductors and maximum overcurrent protection (MOP) for the branch-circuit protector.

Worked example

A 10 hp, 460 V, three-phase motor has a Table 430.250 FLC of 14 A. Branch conductors: 14 × 1.25 = 17.5 A, so 12 AWG copper at 20 A is acceptable. An inverse-time breaker may be sized up to 250% of FLC = 35 A, subject to Table 430.52. The overload is set from the nameplate current, not the 14 A table value.

Traps

  • Using table FLC for overload sizing instead of nameplate current.
  • Forgetting the 125% multiplier for conductors.
  • Using MCA and MOP interchangeably on HVAC nameplates.
  • Omitting the disconnect or locating it out of sight.