KY Fire Sprinkler study materials
KY Fire Sprinkler study resources

KY Fire Sprinkler cheat sheet

KY Fire Sprinkler · Keep the key ideas within reach.

Quick reference

NFPA 13 Sprinkler System Design and Installation

  • Light hazard design density starts at 0.10 gpm/ft² over 1,500 ft²; Ordinary Group 1 at 0.15 gpm/ft² over 1,500 ft²; Ordinary Group 2 at 0.20 gpm/ft² over 1,500 ft² (NFPA 13 density/area curves).

  • Maximum protection area per sprinkler: 225 ft² for light hazard, 130 ft² for ordinary hazard pipe schedule systems; hydraulic designs follow the density/area curves and spacing rules of Chapter 8-19.

  • Standard spray upright/pendent spacing: max 15 ft between sprinklers and max 15 ft from wall on noncombustible unobstructed construction (light hazard); reduce to 12 ft where required by construction type.

  • Minimum clearance: 1 in. (25 mm) below deflector to ceiling for standard spray sprinklers; 18 in. (457 mm) below noncombustible ceiling for storage sprinklers unless listed otherwise.

  • Sprinkler temperature rating: ordinary 135-170°F, intermediate 175-225°F, high 250-300°F, ultra-high 325-650°F. Choose rating at least 25°F above max ambient ceiling temperature.

  • Quick-response sprinklers may use the design area reduction (30% reduction, min 1,500 ft²) only where allowed by NFPA 13 and with wet systems, light/ordinary hazard, and no sloped combustible ceilings.

  • Branch line and cross main sizing: pipe schedule tables (light hazard 1 in. to 2 sprinklers, 1¼ in. to 3, 1½ in. to 5, 2 in. to 10, 2½ in. to 30, 3 in. to 60, 3½ in. to 100, 4 in. and larger 100+).

  • Hanger spacing: 12 ft max for 1 in. and smaller pipe, 15 ft max for 1¼ in. and larger; one hanger within 3 ft of the end of the pipe and within 6 ft of a change in direction (NFPA 13 Ch. 17).

Quick reference

NFPA 13R and 13D Residential and Limited-Area Systems

  • NFPA 13R applies to residential occupancies up to and including four stories above grade plane; buildings taller than four stories require NFPA 13.

  • NFPA 13D applies to one- and two-family dwellings and manufactured homes; it is not a life-safety code and does not require a fire department connection or water flow alarm.

  • 13D design: one sprinkler at 13 gpm minimum for 1-2 sprinkler systems; two sprinklers at 13 gpm each for larger; total flow not required to exceed 26 gpm for one- and two-family dwellings.

  • 13D water supply must supply the system demand for at least 10 minutes (7 minutes if the system has a tank with automatic refill or is connected to a municipal supply).

  • 13R design density: 0.05 gpm/ft² over the entire floor area of the most remote room, or 0.10 gpm/ft² over the four most remote sprinklers, whichever is greater; minimum 13 gpm per sprinkler.

  • 13R sprinkler spacing max 12 ft between sprinklers and 6 ft from walls; max coverage 144 ft² per sprinkler (may be increased to 196 ft² where listed).

  • 13R/13D systems do not require sprinklers in bathrooms under 55 ft², closets under 24 ft², attics, garages, or concealed spaces of certain construction if the exceptions in the standard are met.

  • 13R systems require a single control valve with waterflow switch; 13D systems need a shutoff valve and may omit the waterflow alarm where permitted.

Quick reference

NFPA 14 Standpipe and Hose Systems

  • Class I standpipe: 2½ in. hose valve for fire department use; Class II: 1½ in. hose valve with hose for occupant use; Class III: both 1½ in. and 2½ in. valves.

  • Minimum residual pressure at the topmost outlet: 100 psi for Class I and Class III; 65 psi for Class II; 100 psi for combined systems where the standpipe demand is the greater.

  • Standpipe flow: 500 gpm for the hydraulically most remote standpipe plus 250 gpm for each additional standpipe, with a max of 1,250 gpm total in a building.

  • Maximum horizontal and vertical travel to a hose valve: 130 ft of hose plus 30 ft of stream; hose valves spaced so all portions of the floor are within the reach.

  • Dry standpipes must be capable of being drained; automatic dry pipe valves or manual valves with a fire department connection are permitted; air pressure maintained to prevent tripping.

  • Fire department connection: 100 psi at the FDC at the standpipe system demand; FDC must be located within 100 ft of a public hydrant and accessible to the fire department.

  • Standpipe pipe sizing by schedule: 2½ in. for 1-2 risers, 4 in. for 3 or more risers in a combined system; hydraulic design is permitted as an alternative.

  • Hose valves must be 3-6 ft above the floor, accessible, and protected in cabinets when required; valves must have caps and chains.

Quick reference

NFPA 20 Fire Pumps and Water Supply

  • Fire pump rated flow: pump must be selected so the rated point is at or below 150% of rated flow on the curve; the pump must produce at least 65% of rated pressure at 150% of rated flow.

  • Pump must be capable of delivering at least 95% of rated pressure at zero flow (shutoff) without exceeding 140% of rated pressure; churn pressure is limited to 140% of rated.

  • Net positive suction head (NPSH) required must be less than NPSH available at all flows; NPSH margin is typically 10% or per NFPA 20.

  • Fire pump driver sizing: electric motor sized so it does not overload at any point on the pump curve; diesel driver rated for the pump's maximum brake horsepower.

  • Automatic transfer switch, controller, and power supply must be dedicated and arranged for automatic starting; weekly churn test for electric pumps is required by NFPA 25.

  • Fire pump testing (NFPA 25): weekly no-flow (churn) test for electric pumps; annual flow test at 100%, 150%, and peak; monthly inspection of diesel fuel and battery condition.

  • Fire pump must be located in a fire-rated room with 2-hour separation or protected by sprinklers where the building code requires; suction piping must be as short and direct as possible.

  • Jockey pump: maintains system pressure and is set to start before the fire pump; typically set at 10 psi above fire pump start and stops at the fire pump start pressure.

Quick reference

NFPA 24 Private Fire Service Mains and Underground Piping

  • Private fire service main minimum size is 4 in. for hydrant supply mains; 6 in. minimum where the main serves a fire department connection or where required by the authority having jurisdiction.

  • Underground piping must be buried below the frost line; typical minimum cover is 30 in. to the top of pipe unless local frost depth dictates deeper (Kentucky varies by region).

  • Thrust blocks or restrained joints are required at all changes in direction, tees, dead ends, and hydrant branches; thrust block size depends on soil bearing and test pressure.

  • Hydrostatic test: 200 psi for 2 hours or 50 psi above working pressure, whichever is greater; test before backfilling where possible and with exposed joints.

  • Flushing: minimum 10 ft/s flow velocity through the main before testing; flushing must continue until water runs clear.

  • Hydrant spacing: typically 300 ft to 500 ft as required by the local code; hydrants must be located within 50 ft of the fire department connection and accessible.

  • Gate valves on private mains: valve must be installed on each branch and at intervals not exceeding 800 ft in a looped system; indicator posts required for buried valves.

  • Tapping and connection to public main must follow the water purveyor's requirements; backflow prevention and metering may be required by the local utility.

Quick reference

NFPA 25 Inspection, Testing, and Maintenance

  • Weekly: inspection of gauges (wet, dry, preaction), waterflow alarm devices, and fire pump churn test for electric pumps.

  • Monthly: inspection of alarm valves, dry pipe valves, deluge valves, and fire pump system including diesel fuel level, battery condition, and controller indicators.

  • Quarterly: waterflow alarm test, valve status check, and hydrant inspection; annual: main drain test, flow test of hydrants, and fire pump flow test at 100%, 150%, and peak.

  • Main drain test: static pressure reading, then open drain fully and record residual pressure; a drop of more than 10% from the previous test indicates a problem in the supply.

  • Five-year: internal inspection of sprinkler piping and gauges, and full flow test of standpipes; sprinkler gauge replacement every 5 years for dry systems.

  • Sprinkler replacement: fast-response sprinklers at 20 years, then every 10 years; standard-response at 50 years, then every 10 years; replace any sprinkler showing corrosion, paint, or damage.

  • Dry pipe valve trip test: annually with the main drain open; record the time to trip and the air pressure; compare with the previous year's results.

  • Records must be maintained and made available to the AHJ; NFPA 25 requires retention of inspection and test records for at least one year or as required by the AHJ.

Quick reference

Hydraulic Calculations and Pipe Sizing

  • Hazen-Williams formula: p = 4.52 Q^1.85 / (C^1.85 d^4.87), where p is friction loss in psi/ft, Q is flow in gpm, d is inside diameter in inches, and C is the roughness coefficient (120 for steel, 150 for copper/PVC).

  • C-factor values: black steel 120, galvanized 120, cement-lined 140, copper 150, PVC/CPVC 150; use the correct value for the pipe material in the calculation.

  • Design area: the hydraulically most demanding area of operation; reduce the design area by 30% for quick-response sprinklers (min 1,500 ft²) where permitted by NFPA 13.

  • Density/area curves: the required density is selected from the curve based on hazard classification; the area may be increased or decreased based on the curve's slope.

  • Balancing: the flow at each branch line must be balanced so that the pressure at each node is consistent; use the loop or node method to solve the network.

  • Velocity limit: keep water velocity in the sprinkler system at or below 20 ft/s for steel pipe to limit erosion and noise; 15 ft/s is often used for design.

  • Safety margin: add 10-15 psi to the calculated demand to account for uncertainties and to ensure the supply meets the demand; compare the supply curve to the demand curve.

  • Pipe sizing by schedule: light hazard branch lines 1 in. for 2 sprinklers, 1¼ in. for 3, 1½ in. for 5, 2 in. for 10, 2½ in. for 30, 3 in. for 60, 3½ in. for 100, 4 in. and larger for 100+.

Quick reference

Plans, Permits, and Submittal Review

  • Plan submittal must include: hydraulic calculations, sprinkler layout, pipe sizes, hanger locations, water supply curve, and the contractor's license and permit application.

  • Working plans must be drawn to scale and show the entire system including risers, cross mains, branch lines, and the location of all sprinklers and valves.

  • Hydraulic calculations must be submitted with the plans and must show the design area, density, and the supply curve; calculations must be signed by a licensed engineer or designer.

  • Permit required before installation, alteration, or repair of a sprinkler system; the AHJ reviews plans and issues the permit; inspections occur at rough-in, final, and hydrostatic test.

  • Shop drawings must be approved by the AHJ before installation; the contractor must keep approved plans on site during construction.

  • As-built drawings must be submitted at completion; they must reflect the actual installed system and any field changes.

  • Kentucky requires a licensed sprinkler contractor and certified installer; the license number must appear on the permit application and plans.

  • Submittal review checklist: water supply adequacy, hazard classification, sprinkler spacing, hydraulic calculations, and compliance with NFPA 13 and the Kentucky Building Code.

Quick reference

Kentucky Fire Prevention and Building Codes and Licensing Law

  • Kentucky Fire Prevention Code (KFP) is based on the International Fire Code (IFC) and is enforced by the State Fire Marshal; local jurisdictions may adopt amendments.

  • Kentucky Building Code is based on the International Building Code (IBC); sprinkler requirements follow the IBC and NFPA 13 for the occupancy classification.

  • Sprinkler contractor licensing: Kentucky requires a license from the Department of Housing, Buildings and Construction; a certified installer must be employed by the licensed contractor.

  • Permits: application to the local AHJ or the State Fire Marshal, with plans and fees; the AHJ issues the permit and conducts inspections.

  • Fire alarm and sprinkler plans must be reviewed by the AHJ; the contractor must notify the AHJ before covering any piping and before the final inspection.

  • Kentucky requires a Certificate of Occupancy after final inspection; the AHJ may require a fire flow test and a water supply analysis before approval.

  • Violations of the fire code may result in fines, stop-work orders, or revocation of the contractor's license; the State Fire Marshal has enforcement authority.

  • Continuing education: licensed sprinkler contractors and installers must complete continuing education as required by the Department of Housing, Buildings and Construction.

Quick reference

Jobsite Safety, Materials, and Coordination

  • Personal protective equipment: hard hat, safety glasses, high-visibility vest, steel-toe boots, and gloves are required on all construction sites; fall protection above 6 ft.

  • Pipe handling: use proper lifting techniques; two-person lifts for pipe over 10 ft; do not roll pipe off a truck without a spotter.

  • Lockout/tagout: before working on a system connected to a water supply, isolate and lock the control valve; verify zero pressure before opening the system.

  • Hot work: a hot work permit is required for welding, cutting, or grinding; a fire watch must be maintained for 30 minutes after hot work is complete.

  • Material storage: pipe must be stored on dunnage and kept dry; CPVC must be protected from sunlight and stored away from heat sources.

  • Coordination: sprinkler piping must be coordinated with structural, mechanical, and electrical trades; use BIM or coordination drawings to avoid clashes.

  • Testing safety: hydrostatic testing requires the area to be clear of personnel; use a test cap and gauge; do not stand in front of a test cap during pressurization.

  • Excavation safety: trench protective systems required for trenches 5 ft or deeper; keep spoil piles at least 2 ft from the edge of the trench.