Light hazard density
NFPA 13 light hazard design density starts at 0.10 gpm/ft² over a 1,500 ft² design area; actual density may be adjusted along the density/area curve.
Sprinkler deflector clearance
Standard spray sprinklers require at least 1 in. (25 mm) of clearance between the deflector and the ceiling to allow the spray pattern to develop properly.
Sprinkler temperature rating
Ordinary sprinklers are rated 135-170°F; intermediate 175-225°F; high 250-300°F. Select a rating at least 25°F above the maximum ceiling temperature.
Hanger spacing
NFPA 13 permits hangers at 12 ft maximum for pipe 1 in. and smaller and 15 ft maximum for pipe 1¼ in. and larger, with a hanger near each change in direction.
Quick-response design area reduction
Quick-response sprinklers may reduce the design area by 30% (minimum 1,500 ft²) on wet systems in light or ordinary hazard occupancies where the standard permits.
NFPA 13R height limit
NFPA 13R applies to residential occupancies up to and including four stories above grade plane; buildings taller than four stories require full NFPA 13 protection.
13D water supply duration
NFPA 13D requires the water supply to meet the system demand for at least 10 minutes, or 7 minutes where a tank with automatic refill or a municipal supply is used.
13R design density
NFPA 13R design density is 0.05 gpm/ft² over the most remote room or 0.10 gpm/ft² over the four most remote sprinklers, whichever is greater.
13R sprinkler spacing
Residential sprinklers under NFPA 13R are spaced a maximum of 12 ft apart and 6 ft from walls, with maximum coverage of 144 ft² per sprinkler.
Class I standpipe
A Class I standpipe provides 2½ in. hose valves for fire department use and requires 100 psi residual pressure at the topmost outlet.
Class II standpipe
A Class II standpipe provides 1½ in. hose valves with attached hose for occupant use and requires 65 psi residual pressure at the topmost outlet.
Standpipe flow demand
Standpipe systems require 500 gpm for the most remote standpipe plus 250 gpm for each additional standpipe, with a maximum total of 1,250 gpm.
Hose valve height
Standpipe hose valves must be located 3 to 6 ft above the floor, accessible, and equipped with caps and chains to protect the threads.
Fire pump 150% rule
A fire pump must deliver at least 65% of rated pressure at 150% of rated flow, and at least 95% of rated pressure at zero flow (shutoff).
Fire pump churn pressure
Churn pressure (shutoff) must not exceed 140% of the pump's rated pressure to protect the system components from overpressure.
Jockey pump setting
The jockey pump is set to start about 10 psi above the fire pump start pressure and stops at the fire pump start pressure, maintaining system pressure.
Fire pump weekly test
NFPA 25 requires a weekly no-flow churn test for electric fire pumps and inspection of diesel fuel level and battery condition monthly.
Private main minimum size
NFPA 24 requires private fire service mains to be at least 4 in. for hydrant supply and 6 in. where the main serves a fire department connection.
Underground hydrostatic test
Private fire mains are hydrostatically tested at 200 psi for 2 hours, or 50 psi above working pressure if greater, before backfilling where possible.
Thrust block locations
Thrust blocks or restrained joints are required at all changes in direction, tees, dead ends, and hydrant branches to resist unbalanced pressure forces.
Main drain test
The main drain test records static and residual pressure; a drop of more than 10% from the previous test indicates a problem with the water supply.
Sprinkler replacement interval
Fast-response sprinklers are replaced at 20 years and then every 10 years; standard-response sprinklers at 50 years and then every 10 years.
Dry pipe valve trip test
NFPA 25 requires an annual dry pipe valve trip test with the main drain open, recording trip time and air pressure for comparison with prior years.
Hazen-Williams formula
Friction loss p = 4.52 Q^1.85 / (C^1.85 d^4.87), where Q is gpm, d is inside diameter in inches, and C is the roughness coefficient.
Hazen-Williams C factors
C = 120 for black steel, 140 for cement-lined pipe, and 150 for copper and PVC/CPVC; use the value matching the installed pipe material.
Water velocity limit
Sprinkler piping is typically designed to keep water velocity at or below 20 ft/s for steel pipe to limit erosion and noise; 15 ft/s is common.
Hydraulic safety margin
Add 10-15 psi to the calculated system demand to account for uncertainties and ensure the supply curve stays above the demand curve.
Working plan contents
Working plans must be drawn to scale and show all risers, cross mains, branch lines, sprinklers, valves, pipe sizes, and hanger locations.
Plan approval requirement
Sprinkler plans must be approved by the authority having jurisdiction before installation; approved plans must be kept on site during construction.
Kentucky sprinkler license
Kentucky requires a licensed sprinkler contractor and certified installer; the license number must appear on the permit application and submitted plans.
Kentucky Fire Prevention Code
The Kentucky Fire Prevention Code is based on the International Fire Code and is enforced by the State Fire Marshal, with local amendments permitted.
Hot work fire watch
A hot work permit is required for welding, cutting, or grinding, and a fire watch must be maintained for at least 30 minutes after the work is complete.