- Plumbing fixture unit
- A unit of measure expressing the load a fixture imposes on the drainage or water supply system. Drainage fixture units size drains; water supply fixture units size supply piping.
- Trap seal depth
- The vertical distance from the crown weir of a trap to the top of the dip, which must be at least 2 inches and no more than 4 inches to prevent sewer gas passage.
- Building drain
- The lowest pipe of a drainage system that receives soil and waste inside the building. It extends 30 inches beyond the building wall and becomes the building sewer there.
- Developed length
- The total pipe length measured along the centerline including fittings, used to size water supply piping. Equivalent fitting lengths are added to the measured run.
- Wet vent
- A vent that also serves as a drain for fixtures on the same floor. It must be at least 2 inches and may serve only fixtures within one bathroom group.
- Air gap
- The unobstructed vertical distance through free atmosphere between a water supply outlet and a fixture's flood level rim, at least twice the outlet diameter and never less than 1 inch.
- Backwater valve
- A device installed on a building drain or sewer that closes automatically when flow reverses, preventing sewage backup into fixtures located below the upstream manhole level.
- Temperature and pressure relief valve
- A safety valve on every water heater that opens at the tank's rated pressure or at a temperature no higher than 210 degrees F, discharging through a full-size gravity drain.
- Drainage fixture unit values
- Code-assigned loads by fixture: water closet 3, lavatory 1, bathtub 2, kitchen sink 2, floor drain 1. These values are summed to size the building drain.
- Stack vent
- The extension of a soil or waste stack above the highest horizontal drain, extending above the roof and sized no smaller than the stack it serves.
- Grease interceptor
- A device required for commercial kitchens that separates grease from waste before discharge. It must be sized by fixture capacity and be accessible for cleaning.
- Fixture trap arm limit
- The maximum developed length from the trap weir to the vent fitting, such as 3 1/2 feet for 1 1/4-inch pipe and 5 feet for 1 1/2-inch pipe.
- Water service minimum size
- The smallest permitted building water service is 3/4 inch, and the smallest permitted fixture supply is 3/8 inch, sized by water supply fixture units.
- Residual fixture pressure
- The minimum pressure required at a fixture outlet: 8 psi for flush valve fixtures and 15 psi for tank-type fixtures, measured while the fixture is flowing.
- Horizontal drain slope
- Drainage pipe must slope uniformly at not less than 1/4 inch per foot for 2 1/2-inch and smaller pipe and 1/8 inch per foot for 3-inch and larger pipe.
- Vent termination height
- A vent stack must extend at least 6 inches above the roof and 3 feet above any roof surface within 10 feet, and stay 10 feet from windows and air intakes.
- Kentucky license tiers
- A master plumber may contract for plumbing work and employ others; a journeyman works under supervision; an apprentice must be registered and directly supervised.
- Permit and inspection sequence
- A permit is required before installation or alteration. Rough-in inspection occurs before concealment, followed by water and drainage testing and a final inspection.
- No-hub cast iron coupling
- A listed coupling joining hubless cast iron soil pipe, tightened to the manufacturer's specified clamp torque and used for service-weight and extra-heavy-weight pipe.
- PEX installation limit
- PEX tubing must be listed to ASTM F876/F877 with listed fittings, and may not be installed within 18 inches of a water heater outlet unless the manufacturer approves.
- Thermal expansion tank
- A tank required on a closed domestic water system to absorb the volume increase caused by heating water, controlling pressure that would otherwise stress the system.
- Garage water heater elevation
- A water heater in a garage must have its ignition source raised at least 18 inches above the floor, or be a flammable-vapor-ignition-resistant model.
- Primary and secondary roof drains
- A roof drainage system requires a primary drain and a secondary drain or scupper so that blockage of the primary will not cause water to accumulate on the roof.
- Storm and sanitary separation
- Storm drainage must not connect to the sanitary drainage system; the two systems remain separate, independently vented, and discharge to different destinations.
- Clinical sink requirements
- A bedpan washer or clinical sink needs a trap and flushing rim, plus a backflow preventer on its water supply, in health care occupancies.
- Medical gas installer
- Medical gas and vacuum piping must follow NFPA 99 and manufacturer instructions and may be installed only by appropriately licensed medical gas installers.
- Gas piping sediment trap
- A sediment trap installed downstream of the appliance shutoff valve on the gas supply, unless the appliance is designed to prevent sediment accumulation.
- Gas piping test pressure
- Fuel gas piping is tested at not less than 1 1/2 times working pressure, with a minimum of 3 psi held for 10 minutes, or as the code specifies.
- Isometric orientation
- On a plumbing isometric, vertical lines represent vertical pipe while lines at 30 degrees to horizontal represent horizontal pipe running in two directions.
- Slope percentage conversion
- Divide the drop by the run and multiply by 100. A 1/4 inch per foot slope equals 0.25 divided by 12 times 100, or about 2.08 percent.
- Cleanout locations
- Cleanouts are required at each stack base, at the building drain, at the drain-to-sewer junction, and at intervals not exceeding 100 feet in horizontal runs.
- Trap primer purpose
- A device that delivers water to a trap to maintain its seal where evaporation occurs, such as floor drains in garages, mechanical rooms, and unoccupied spaces.