LA Fire Alarm study materials
LA Fire Alarm study resources

LA Fire Alarm flashcards

LA Fire Alarm · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Dedicated branch circuit
An unswitched circuit supplying only the fire alarm panel, with a lockable disconnect or labeled breaker and a visible disconnect means, so power cannot be removed accidentally.
Battery amp-hour sizing
Required amp-hours equal standby current times standby hours plus alarm current times alarm hours, then multiplied by a derating factor for end-of-life capacity.
Pathway survivability Level 2
Circuits in a protected environment plus a 2-hour rated enclosure for the control equipment, used where the system must survive a fire for a defined period.
Class A versus Class B
Class A circuits return to the panel and survive a single open; Class B circuits do not return and lose the entire circuit on a single open.
Manual pull station location
Within 5 ft of the exit door, mounted 42 to 48 in. above the floor in the adopted edition, and unobstructed along the path of egress.
Spot smoke detector spacing
Use the manufacturer's listed spacing on a smooth ceiling, with 0.7 times that spacing to walls and a 4 in. minimum distance from the wall.
Public-mode audibility
At least 15 dBA above the ambient sound level or 5 dBA above the maximum sound level lasting 60 seconds, whichever is greater.
Strobe synchronization
Visible appliances in the same field of view must flash in sync; unsynchronized flashing is not acceptable and must be corrected.
NAC voltage-drop calculation
Compute the voltage at the end of each notification appliance circuit to confirm every appliance still operates at its listed minimum voltage.
Waterflow switch
An initiating device on a sprinkler system that alarms on sustained flow, typically set to alarm within 90 seconds of flow.
Tamper switch
A supervisory device that reports an off-normal valve position; it annunciates as supervisory, not as an alarm, and is not interchangeable with a waterflow switch.
Addressable device
A device that reports individually by address, allowing the panel to identify the exact device rather than only the zone.
Record of completion
The NFPA 72 form filled out at installation documenting the system as built; it is the baseline for future inspection, testing, and maintenance.
Annual testing baseline
Most initiating devices and notification appliances require annual testing; some devices require semi-annual or quarterly testing per the ITM tables.
Impairment procedure
Notify the AHJ, the building owner, and the monitoring company before taking a system out of service; document the impairment and the restoration.
Acceptance test
The AHJ-witnessed test at completion; the record of completion and as-built drawings must be available at the test.
Riser diagram content
A drawing showing every circuit, its class, its pathway survivability level, and the devices on it, submitted with the fire alarm plans.
Code-compliance matrix
A table mapping each code requirement to the code section and the design feature that satisfies it, used to demonstrate compliance at plan check.
Code hierarchy
LAMC amendments layer on the California Fire Code and adopted NFPA 72; where requirements conflict, the stricter one governs unless stated otherwise.
Listing requirement
Equipment must be listed by a nationally recognized testing laboratory for the specific application; manufacturer self-approval is not accepted.
Lockout/tagout on panel
Tag the fire alarm panel and notify the monitoring company before working on it, then restore normal supervision before leaving the site.
Bypass documentation
Record every bypass placed on a supervised circuit and restore it before leaving; never leave a system in bypass at the end of the shift.
Daily report content
Record the work performed, the devices tested, any impairments, and relevant conditions; it supports the ITM record and the owner's documentation.
Duct smoke detector
Required where the code requires HVAC shutdown; install per the manufacturer's listed airflow and straight-duct requirements.
Beam detector supervision
The receiver supervises the beam; loss of beam is a trouble, not an alarm, unless the system is specifically designed otherwise.
Remote annunciator
Must display the same alarm, supervisory, and trouble conditions as the main panel and must itself be supervised.
Plenum-rated cable
Required in environmental air spaces unless installed in a raceway that is itself plenum-rated, per the adopted code and the listing.
Splicing rule
Splices are permitted only in listed junction boxes with listed connectors; no splices in conduit bodies unless listed for the purpose.
Battery load test
A test of the battery under load plus a check of the charger; a battery that fails the load test must be replaced, not just recharged.
Voice intelligibility
Voice evacuation messages must be understandable in every occupied space, verified by an intelligibility measure such as STI.
Revised submittal
Changes after approval require a revised submittal; field changes that deviate from the approved plans are not permitted without AHJ approval.
Occupancy alarm trigger
The California Fire Code as amended by the LAFD sets occupancy-based alarm requirements; the LAMC amendments layer additional requirements on top.