LA Fire Alarm: Power Supplies, Batteries, and Secondary Power

LA Fire Alarm · Work through your exam, one topic at a time.

All guide sections

Power Supplies, Batteries, and Secondary Power

This domain tests primary and secondary power for fire alarm systems under NFPA 72 Chapter 10. You must know the dedicated-circuit requirement, the standby and alarm durations, and the battery sizing formula with its aging margin.

Core rules

  • The primary supply is a dedicated 120 VAC branch circuit, marked “Fire Alarm,” with no other loads and protected against accidental disconnection.
  • Secondary power is typically sealed lead-acid batteries. Commercial systems require 24 hours of standby followed by 5 minutes of alarm; voice evacuation systems commonly require 15 minutes of alarm.
  • Battery capacity is calculated as standby current × 24 hours plus alarm current × alarm minutes ÷ 60, then multiplied by a 1.25 aging/derating factor.
  • The charger must restore the battery within the code time and be listed for fire alarm use.
  • Voltage drop must be checked at the end of battery discharge, not only at nominal voltage.

Worked example

A panel draws 0.25 A standby and 1.5 A alarm. Standby energy is 0.25 × 24 = 6.0 Ah. Alarm energy is 1.5 × 5 ÷ 60 = 0.125 Ah. The subtotal is 6.125 Ah; multiplied by 1.25 gives 7.66 Ah. Select the next standard battery size, 8 Ah, and verify it fits the cabinet and charger rating.

Traps

  • Using 5 minutes for a voice system that requires 15 minutes.
  • Omitting the 1.25 derating factor.
  • Sizing from nameplate current instead of measured standby and alarm loads.
  • Sharing the fire alarm circuit with other equipment.
  • Ignoring end-of-discharge voltage drop on long NAC runs.