The 4-Ton Swap in Baton Rouge: Load vs. Duct Reality

LA HVAC · Put your knowledge to work in context.

All case studies

The 4-Ton Swap in Baton Rouge: Load vs. Duct Reality

Single-story 2,650 sq ft slab house in Baton Rouge, built 1978, 8-ft ceilings, original single-pane windows, ducts entirely in a vented attic that hits 140°F in July. The 4-ton condenser failed and the homeowner wants it swapped, same size, by Friday. Your Manual J run at 75°F DB / 50% RH indoors and 95°F DB / 79°F WB outdoors returns 32,400 Btu/h total: 24,900 Btu/h sensible and 7,500 Btu/h latent. The existing duct system is one 20 x 8 trunk with 18-in flex runouts and nine 6-in supplies; four of the supplies have 20-ft flex runs. With a flow hood, the supplies total 1,150 cfm. Total external static measured at the air handler is 0.92 in. w.c. with a clean filter. The homeowner says, 'Don't put another weak one in - go to 5 tons, I want it cold.'

1. Size the replacement. Justify the number and explain to the homeowner why bigger is worse here.

Read the worked answer

The load is 32,400 Btu/h total, so the equipment is a 3-ton (36,000 Btu/h) nominal selection - and even that must be checked against expanded ratings at 95°F outdoor and 75/63 entering wet bulb, because in Louisiana the sensible capacity falls off at design ambient while the latent load does not.

Why not 4 tons, and certainly not 5:

  • Latent control. At 7,500 Btu/h latent, a 3-ton with roughly 0.75–0.8 SHR removes the moisture if it runs long enough. An oversized 5-ton short-cycles, the coil never gets cold-soaked, and you get a cold, clammy house at 72°F with 62% RH - which is exactly the complaint that leads to a callback.
  • Airflow. A 5-ton needs 2,000 cfm. The existing ducts deliver 1,150. You would be forcing 2,000 cfm through a 1,150-cfm duct system: static goes through the roof, the blower curve falls off, and you get neither the airflow nor the capacity you paid for.
  • The measured 0.92 in. w.c. is already excessive. The duct system is a 4-ton-era system that cannot even support 3 tons as it sits.

Present it as a package: 3 tons of correctly rated equipment plus duct corrections, or the homeowner is buying a bigger box that performs worse.

2. Identify the duct deficiencies and specify the fixes, with numbers.

Read the worked answer

Deficiencies and fixes:

  • Trunk undersized. A 20 x 8 trunk is 160 sq in. of free area, ~1,400 cfm at 0.1 in. w.c. friction, but the long runouts and fittings drop the available pressure. Replace with an appropriately sized trunk - a 24 x 10 or an equivalent rectangular plus takeoff layout - and support it independently of the flex.
  • Runouts too small for the length. A 6-in flex at 20 ft with a compression-fitting loss is roughly 60–70 cfm, not the 100+ assumed. Four supplies in that condition are starving. Either upgrade those runs to 8 in. or shorten and straighten them; eliminate the sharp 90° turns and the sagging loops.
  • Static reduction. Target 0.5 in. w.c. total external static at design airflow. That means filter grille area, an appropriately sized return, and a clean transition - the 0.92 you measured is mostly the duct and return, not the coil.
  • Attic heat gain. The 140°F attic adds 15–25% to the effective load on the flex runs. Buried or R-8 ducts and a radiant barrier are cheaper than a ton of equipment.

Verify the fix with a flow hood afterward: nine supplies at 3 tons should total about 1,200 cfm, no single supply below its design, and static at or under 0.5 in. w.c.

3. The homeowner still wants the 5-ton. What do you put in the proposal, and what do you refuse to do?

Read the worked answer

You put the recommendation in writing with the numbers, and you refuse to install a 5-ton on the existing duct system without a signed acknowledgment that it is a customer-directed deviation - or you decline the job.

What belongs in the proposal:

  • Manual J summary: 32,400 Btu/h total, 24,900 sensible, 7,500 latent, and the selected 3-ton model with its expanded rating at 95°F/79°F WB showing it meets the load.
  • Existing conditions documented: 1,150 cfm measured, 0.92 in. w.c. static, attic duct in a 140°F space.
  • Duct scope with quantities and a post-install airflow and static verification.
  • If a 5-ton is installed, the required duct system and the price to build it - never a 5-ton on the old ducts.

What you refuse: installing oversized equipment with no duct work and no humidity control plan. That configuration guarantees short cycling, elevated indoor RH, and a callback you will own. Note in the file that the homeowner was advised of the latent and airflow consequences; that note is what protects you when the complaint comes in August.