LA HVAC flashcards
LA HVAC · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Lower Flammability Limit
- The minimum concentration of a flammable refrigerant in air that will support combustion; A2L refrigerants such as R-32 and R-454B have LFLs near 12–14% by volume.
- Lockout/Tagout
- A procedure that isolates hazardous energy with a personal lock and tag before service; verify zero voltage with a CAT-rated meter after isolating the disconnect.
- Nitrogen Purge
- A low flow of dry nitrogen through copper while brazing; it displaces oxygen and prevents internal oxidation (scale) that would contaminate the refrigerant circuit.
- Vacuum Decay Test
- Pull the system to 500 microns, isolate the pump, and confirm the vacuum holds for 10–15 minutes; a rising reading indicates a leak or moisture.
- Ton of Refrigeration
- A cooling rate equal to 12,000 Btu per hour, 200 Btu per minute, or 3.517 kilowatts; it is the standard capacity unit for HVAC equipment.
- Superheat
- The difference between the actual suction line temperature and the saturated suction temperature at the same pressure; it confirms vapor leaving the evaporator.
- Subcooling
- The difference between the saturated liquid temperature at the liquid line pressure and the actual liquid line temperature; it confirms solid liquid at the metering device.
- Thermostatic Expansion Valve
- A metering device that modulates refrigerant flow to hold a set evaporator superheat, responding to bulb pressure, evaporator pressure, and spring force.
- Refrigerant Glide
- The temperature spread between bubble and dew points of a zeotropic blend; R-407C has significant glide while R-410A has only about 0.2°F.
- Manual J Load Calculation
- ACCA's residential method for sizing heating and cooling loads from envelope U-values, window solar gain, infiltration, and internal gains at design conditions.
- Equal Friction Method
- A duct sizing approach that assigns a constant pressure drop per unit length, commonly 0.08–0.10 in. w.c. per 100 ft, to each duct section.
- External Static Pressure
- The total pressure the blower must overcome in the supply and return ducts, filter, and coil; residential air handlers are typically rated near 0.5 in. w.c.
- CFM per Ton
- The airflow rate per ton of cooling capacity; about 400 cfm/ton is standard, 350 improves latent removal, and 450 raises sensible capacity.
- Temperature Rise
- Supply air temperature minus return air temperature across a furnace; it must fall within the rating plate range, commonly 35–65°F, or airflow is wrong.
- Stoichiometric Air
- The exact air quantity needed for complete combustion; natural gas requires about 10 ft³ of air per ft³ of gas, and burners run 25–50% excess air.
- Flue CO2 Reading
- The carbon dioxide percentage in flue gas; natural gas at perfect combustion is about 11.7%, and lower readings indicate excess dilution air.
- Manifold Gas Pressure
- The pressure at the burner manifold; typical natural gas setting is 3.5 in. w.c. and LP gas is 10–11 in. w.c., always confirmed against the data plate.
- Flame Sensor Current
- The microamp signal a flame rectification sensor sends to the control; readings below about 0.5 µA cause lockout on flame failure.
- Section 608 Certification
- The federal EPA credential required to buy or handle regulated refrigerants; venting is prohibited and recovery is required for appliances of 5 lb or more.
- Superheat Charging Method
- For fixed-orifice systems, measure suction pressure, convert to saturated temperature, and subtract it from suction line temperature; target 8–12°F.
- Subcooling Charging Method
- For TXV systems, convert liquid line pressure to saturated temperature and subtract it from liquid line temperature; target 8–12°F at design conditions.
- Recovery Cylinder Limit
- A refrigerant recovery cylinder may never be filled above 80% of its capacity by weight; use a scale and respect the DOT working pressure.
- Ohm's Law
- The relationship E = I × R, where voltage equals current times resistance; combined with P = E × I it supports circuit diagnosis and load checks.
- Run and Start Windings
- In a single-phase compressor, the run winding has lower resistance than the start winding; the common terminal shows the highest resistance to both others.
- Run Capacitor Test
- A good run capacitor measures within about 6% of its marked microfarad value on a capacitance meter; a bulged or leaking capacitor is replaced.
- Three-Phase Power Formula
- Watts equal volts times amps times 1.732 times power factor; a balanced motor draws equal current on all three legs within about 10%.
- Condensate Trap Depth
- The trap must be deeper than the fan's static pressure, typically 2–3 in., with the drain sloping at least 1/8 in. per ft toward the discharge.
- Suction Line Velocity
- Suction line velocity should stay between 700 and 1,200 fpm to carry oil back to the compressor without excessive pressure drop or noise.
- SMACNA Seal Classes
- Duct leakage standards ranging from Class A (tightest) to Class C; residential work commonly requires Class C or better on all joints and seams.
- LSLBC Mechanical License
- The Louisiana State Licensing Board for Contractors credential required for mechanical (HVAC) contracting above the residential threshold; proof of insurance and bonding applies.
- Louisiana Mechanical Code
- The state mechanical code is based on the International Mechanical Code, with parish amendments; permits and inspections are required before equipment installation or replacement.
- Margin versus Markup
- Margin is profit divided by price; markup is profit divided by cost. A 30% margin equals a 42.9% markup, so the two must never be interchanged in bids.