LA HVAC: Cooling Equipment, Refrigerants, and Charging Procedures

LA HVAC · Work through your exam, one topic at a time.

All guide sections

Cooling Equipment, Refrigerants, and Charging Procedures

This domain tests equipment ratings, refrigerant handling, and the charging method that matches the metering device.

Equipment and ratings

  • SEER2 and EER2 replaced SEER and EER; capacity at design conditions comes from the AHRI matched combination, not the outdoor unit alone.
  • Airflow runs about 350 to 450 CFM per ton; a healthy air temperature split is roughly 16 to 22 F.

Refrigerants

  • R-410A is a near-azeotropic blend with small but real glide; it is charged as a liquid from the cylinder.
  • R-32 and R-454B are A2L mildly flammable refrigerants. Nameplate charge limits, ignition sources, and leak detection requirements come from the mechanical code.
  • Recover, recycle, and evacuate per EPA Section 608. Never vent.

Charging by method

  • TXV or EEV: charge to the subcooling target on the nameplate.
  • Fixed orifice or piston: charge to the superheat target from the manufacturer chart, using indoor wet bulb and outdoor dry bulb.
  • Weigh in the charge when line length exceeds the factory charge, using the per-foot correction.
  • Evacuate to 500 microns and confirm a decay test before releasing charge.

Worked example

Nameplate target is 10 F subcooling. Liquid pressure is 410 psig on R-410A, about 119 F saturation. Target liquid-line temperature is 119 - 10 = 109 F. Measured liquid-line temperature is 115 F, so subcooling is 119 - 115 = 4 F. The system is undercharged; verify airflow and check for leaks, then add liquid refrigerant and recheck.

Traps that cost marks

  • Charging a TXV system to a superheat target.
  • Vapor-charging a blend and fractionating the cylinder.
  • Adding refrigerant before checking airflow; low airflow mimics an undercharge with high superheat and low suction pressure.
  • Using an R-22 PT chart on an R-410A system.