- NEC Article 90 scope
- Article 90 states the NEC covers electrical installations, including conductors, equipment, and optically powered systems, but excludes utility-owned installations and certain other systems.
- Approved equipment
- Approved means acceptable to the authority having jurisdiction; listing by a recognized testing laboratory is common evidence, and labeled equipment must be installed per instructions.
- Working clearance height
- The dedicated electrical working space must be at least 6.5 feet high, 30 inches wide, and extend from the floor or platform to the structural ceiling.
- Shall versus should
- In the NEC, 'shall' indicates a mandatory requirement, 'shall not' a prohibition, and 'should' a recommendation or advisory practice rather than an enforceable rule.
- NM cable support
- Nonmetallic-sheathed cable must be secured every 4.5 feet and within 12 inches of each box, unless specifically permitted otherwise by the Code.
- Conduit fill percentages
- Chapter 9 Table 1 permits 53 percent fill for one conductor, 31 percent for two conductors, and 40 percent for three or more conductors in a raceway.
- Box fill counting
- Box fill counts each conductor, each clamp, each device, and each equipment grounding conductor using Article 314.16 volume allowances before comparing with the box volume.
- Parallel conductor rules
- Parallel conductors must be 1/0 AWG or larger, identical in material, size, insulation, and length, and terminated so current divides equally.
- Continuous load factor
- For branch circuits, feeders, and services, continuous loads are calculated at 125 percent of their ampere rating, then added to noncontinuous loads.
- Kitchen small appliance circuits
- A dwelling kitchen must have at least two 20-ampere small-appliance branch circuits for countertop receptacles, and these circuits may not supply other outlets.
- Receptacle wall spacing
- In dwelling units, receptacle outlets along walls must be spaced so no point on the wall is more than 6 feet from a receptacle.
- Voltage drop recommendation
- NEC informational notes recommend no more than 3 percent voltage drop on a branch circuit and no more than 5 percent total from service to load.
- Equipment grounding conductor
- The equipment grounding conductor provides a low-impedance path for fault current back to the source, allowing overcurrent protection to operate quickly.
- Ground rod supplement
- A single ground rod must have 25 ohms or less resistance; if not, a supplemental electrode is required, unless the single rod meets the value.
- Small conductor protection
- Unless specifically permitted, 14 AWG copper is protected at 15 amperes, 12 AWG at 20 amperes, and 10 AWG at 30 amperes.
- GFCI protection
- Ground-fault circuit-interrupter protection is required for receptacles in bathrooms, kitchens, outdoors, garages, unfinished basements, and other specified wet or hazardous areas.
- Ohm's law
- Ohm's law states that voltage equals current times resistance, V = I × R, and can be rearranged to find current or resistance.
- Three-phase power
- For a balanced three-phase circuit, power in kilowatts equals the square root of three times line voltage times line current times power factor, divided by 1000.
- Power factor
- Power factor is true power divided by apparent power, P/S; it equals the cosine of the angle between voltage and current in a sinusoidal circuit.
- Wye line voltage
- In a balanced wye connection, line voltage equals the square root of three times phase voltage, while line current equals phase current.
- Motor branch conductors
- Motor branch-circuit conductors are sized at 125 percent of the motor full-load current from the Code tables, not the motor nameplate current.
- Motor disconnect location
- A motor disconnecting means must be within sight of the motor and controller, or capable of being locked open, as permitted by Article 430.
- Motor overload protection
- Motor overload protection guards the motor against excessive current from overloads; it is sized from the motor nameplate current and is separate from short-circuit protection.
- HVAC disconnect
- For air-conditioning and refrigeration equipment, a disconnecting means must be within sight and readily accessible from the equipment, as required by Article 440.
- Class I location
- A Class I hazardous location contains or may contain flammable gases or vapors in quantities sufficient to produce explosive or ignitable mixtures.
- Pool equipotential bonding
- Swimming pool bonding connects metal parts, equipment, and pool water to a common equipotential grid to reduce voltage differences and shock risk.
- Rapid shutdown
- Photovoltaic systems on buildings require rapid shutdown so conductors within the array and outside the array are reduced to a safe voltage for firefighters.
- Massachusetts Electrical Code
- The Massachusetts Electrical Code is 527 CMR 12.00, which adopts the National Electrical Code with Massachusetts amendments and is enforced by local wiring inspectors.
- Master electrician role
- A Massachusetts master electrician is licensed to perform electrical work and obtain electrical permits; journeyman electricians work under a master's supervision.
- Local wiring inspector
- The local wiring inspector enforces the Massachusetts Electrical Code in the municipality, issues permits, and inspects electrical installations for compliance.
- Limited approach boundary
- The limited approach boundary is the distance from exposed energized parts that unqualified persons must not cross; only qualified persons with proper protection may enter.
- Lockout tagout
- Lockout/tagout isolates energy sources with locks and tags, and the qualified worker verifies absence of voltage before beginning work on equipment.